10 Refer to the locally applicable Building
Regulations, BS 5410:1 and OFTEC Installation
Requirements (Books 2 and 3) for further guidance
on conventional flue systems.
It is important to ensure that the flue system is sealed
and that condensate cannot escape. Up to 1.5 l/h of
condensate can be produced in a conventional flue
system.
Only use flue systems suitable for oil fired condensing
boilers.
Do not use fire cement. The use of high temperature
silicone sealants is recommended.
Grant EZ-Fit Flexi Pack conventional flue system
(Orange System) - See Fig. 13
A range of Flexi pack conventional flue lining kits are
available from Grant UK. The packs have been
specifically produced for Grant Vortex Combi
condensing boilers.
Contents of Grant EZ-Fit Flexi Pack
The pack includes a smooth bore flexible stainless steel
100 mm diameter flue liner with chimney top clamping
plate, a rigid to flexi adaptor for the top of the liner, a rigid
to flexi adaptor for the bottom of the liner, a terminal, a
boiler connector (CFCA15/46) suitable for all Grant
Vortex condensing boilers and a connector from the
boiler adaptor to rigid flue system.
5 - GENERAL BOILER INFORMATION
Apart from a conventional flue, several balanced flue
options are available for use with Grant Combi boilers.
All are suitable for use with Class C2 kerosene and Class
D Gas oil
(kerosene only for the Vortex Combi).
When using Gas oil, the flue must terminate a
minimum of 2 metres above outside ground level.
Note:
None of the flue sections in the following
system can be cut.
1
Low level horizontal balanced flue (Yellow system)
Available in Short (for single thickness brick walls)
and Standard kits.
Extensions are available which extend the flue by
225 mm, 450 mm or 675 mm. 90° and 45° elbows
are also available.
The maximum flue length - from the centre of the
boiler flue outlet to the outer face of the wall - is 2
metres (with or without elbows included). No more
than 2 x 45° or 1 x 90° elbow should be fitted per
system.
IMPORTANT: For Vortex Combi boilers with the
flue to the left hand side - leave a minimum gap of
150 mm between the side of the boiler and the wall
to accommodate the condensate trap.
2
High level (horizontal) balanced flue (White
system)
Allows the flue to rise vertically within the building
before exiting through the wall horizontally.
The maximum flue length - from the top of the
boiler flue outlet to the outer face of the wall - is 4
metres for the Combi V3 and Combi Max and 6
metres for the Vortex Combi.
Extensions are available which extend the flue by
225 mm, 450 mm or 950 mm. An adjustable
extension of 275 to 450 mm is also available.
A 45° elbow is also available. No more than 2 x 45°
elbows should be fitted per system. Each elbow
reduces the overall maximum length of the system by
1 metre.
3
Vertical balanced flue (White system)
Allows the flue to rise vertically from the boiler to
exit through the roof.
The maximum flue length - from the top of the
boiler flue outlet to the terminal - is 6 metres for
the Combi V3 and Combi Max and 8 metres for the
Vortex Combi.
Part No.
GFKIT6
GFKIT8
GFKIT10
GFKIT11
Description - Flexi Pack
Flexi pack with 6 m liner, terminal and adaptors
Flexi pack with 8 m liner, terminal and adaptors
Flexi pack with 10 m liner, terminal and adaptors
Flexi pack with 11 m liner, terminal and adaptors
Part No.
WX150/200
WX250/200
WX450/200
WX950/200
WXA250/200
WE45/200
Description - Extensions
150 mm extension with locking band
250 mm extension with locking band
450 mm extension with locking band
950 mm extension with locking band
195-270 mm adjustable extension with locking band
45° elbow with locking band
Extensions
A range of white powder coated twin wall extensions
are available to connect the boiler to the flexible liner.
The external diameter of the extensions is 150 mm.
Extensions are supplied with locking bands.
Flue extensions cannot be cut.
An adjustable extension is available. 45° elbows are
also available.
The rigid flue between the boiler and flexible flue liner
should incorporate an adjustable section to allow
inspection and cleaning of the flue system.
Balanced flue options
5.8
Содержание Combi 70 V3
Страница 26: ...Combi V3 Combi Max and Vortex Combi models 26 5 GENERAL BOILER INFORMATION Fig 14 External flue Green system...
Страница 58: ...Combi V3 Combi Max and Vortex Combi models 58 13 FAULT FINDING Riello RDB burner fault finding 13 7...
Страница 60: ...Combi V3 Combi Max and Vortex Combi models 60 14 BURNER SPARE PARTS Burner Heads...
Страница 63: ...63 Combi V3 Combi Max and Vortex Combi models...