Combi V3, Combi Max and Vortex Combi models
10
Note:
All boilers are despatched for use with kerosene.
Notes:
1
The data given above is approximate only. The Kerosene table is based on the boiler being used with a low level balanced flue.
2
The above settings may have to be adjusted on site for the correct operation of the burner.
3
Gas Oil is
not
suitable for use with a low level balanced flue, unless the flue terminal is higher than 2.0 m above outside
ground level.
4
The installer
must
amend the boiler data label if the type of fuel and nozzle used are changed.
5
Net flue gas temperatures given are ± 10%.
6
** Net thermal efficiency (BSRIA).
7
Flue gas temperatures taken at combustion door test point will be approximately 25°C higher for the Combi 90 V3 and
Combi Max.
8
Flue gas temperature taken at the top of the boiler will be 20°C higher for the Combi 70 V3.
CO
2
(%)
12.0
(kW)
33.3
(Btu/h)
113 600
Heat Output
(kW)
36.8
(Btu/h)
125 500
Net Heat Input
Net eff. **
(%)
91.5
Head
type
T5
Nozzle
size
1.00/80°EH
Oil press.
(bar)
9.0
Smoke
No.
0 - 1
Fuel flow
rate (kg/h)
3.10
Net flue gas
temp. (°C)
190
Note:
Burners are supplied factory set at the outputs shown.
When commissioning, or when the type of fuel is changed, the air damper
must
be adjusted to obtain the correct CO
2
level and the Installer
must
amend the data label.
4 - BOILER TECHNICAL INFORMATION
Combi V3 and Combi Max oil boilers using class C2 kerosene
4.3
Combi V3 and Combi Max oil boilers using class D gas oil
4.4
Approximate air damper settings
4.5
(kW)
32.9
(Btu/h)
112 463
Heat Output
(kW)
36.0
(Btu/h)
122 910
Net Heat Input
Net eff. **
(%)
91.5
Head
type
T5
Nozzle
size
0.75/80°S
Oil press.
(bar)
11.0
Smoke
No.
0 - 1
Net flue gas
temp. (°C)
200
Fuel flow
rate (kg/h)
3.02
Flue gas mass
flow rate (kg/h)
34.8
38.7
CO
2
(%)
11.5
12.0
(kW)
20.5
26.4
(Btu/h)
70 000
90 000
Heat Output
(kW)
22.5
27.6
(Btu/h)
76 900
94 200
Net Heat Input
Net eff. **
(%)
93.0
95.8
Head
type
LD2SX short
LD3
Nozzle
size
0.60/60°EH
0.75/60°EH
Oil press.
(bar)
8.5
9.5
Smoke
No.
0 - 1
0 - 1
Fuel flow
rate (kg/h)
1.87
2.40
Net flue gas
temp. (°C)
211
180
Combi 70 V3 and Combi 90 V3 (Riello RDB1 burner)
Flue gas mass
flow rate (kg/h)
34.8
38.7
CO
2
(%)
11.5
12.0
(kW)
20.5
26.4
(Btu/h)
70 000
90 000
Heat Output
(kW)
22.5
27.9
(Btu/h)
76 900
95 250
Net Heat Input
Net eff. **
(%)
92.0
94.6
Head
type
LD2SX short
LD3
Nozzle
size
0.40/60°S
0.60/60°S
Oil press.
(bar)
12.0
12.0
Smoke
No.
0 - 1
0 - 1
Fuel flow
rate (kg/h)
1.60
1.97
Net flue gas
temp. (°C)
200
200
Combi Max (Riello RDB2.2 burner)
Combi 70 V3 and Combi 90 V3 (Riello RDB1 burner)
Combi Max (Riello RDB2.2 burner)
Flue gas mass
flow rate (kg/h)
51.5
CO
2
(%)
12.0
Flue gas mass
flow rate (kg/h)
51.5
Содержание Combi 70 V3
Страница 26: ...Combi V3 Combi Max and Vortex Combi models 26 5 GENERAL BOILER INFORMATION Fig 14 External flue Green system...
Страница 58: ...Combi V3 Combi Max and Vortex Combi models 58 13 FAULT FINDING Riello RDB burner fault finding 13 7...
Страница 60: ...Combi V3 Combi Max and Vortex Combi models 60 14 BURNER SPARE PARTS Burner Heads...
Страница 63: ...63 Combi V3 Combi Max and Vortex Combi models...