Section 4: Electrical

Page 13

OVER-TEMPERATURE CUT-OUT

This immersion heater is fitted with a Cotherm type TSR 

thermostat that incorporates an independent non-self-

resetting over-temperature cut-out to prevent excessive water 

temperatures.
The reset pin is located in a small opening to the side of the 

control dial and indicated by small triangle with the word ‘safety’. 

Refer to Figure 4-3. 
In normal operation the reset pin will be approximately 2-3mm 

below the surface of the plastic thermostat housing. 

Should the over-temperature cut-out operate, the reset pin will be 

pushed up to become level or slightly above the surface of the 

housing.

To reset the over-temperature cut-out:

• 

Isolate the volumiser / immersion element from the mains 

electrical supply.

• 

Wait for the temperature in the volumiser to fall sufficiently.

• 

Using a suitably sized implement, push the reset pin using 

hand pressure only to return it to its normal operating 

position.

! WARNING !

Ensure the volumiser / immersion heater is isolated from 

the mains before attempting to reset to 

over-temperature cut-out.

If the immersion heater needs to be replaced it must be fitted to 

the volumiser using the gasket provided on the unit. Only use a 

correctly shaped spanner. Stilsons or pipe grips should NOT be 

used. The use of sealing compound is not recommended.

! WARNING !

Always ensure that the immersion heater cap is not 

covered.

Содержание Aerona3 HPID10R32

Страница 1: ...UK DOC 0183 Rev 1 0 November 2022 Grant External Volumiser Installation Instructions...

Страница 2: ...e Grant External Volumiser SPECIAL TEXT FORMATS The following special text formats are used in these instructions for the purposes listed below WARNING Warning of possible human injury as a consequenc...

Страница 3: ...5 Unpacking 6 3 6 Installation procedure 6 3 7 System connections 7 4 ELECTRICAL 11 4 1 General 11 4 2 Electrical connections 11 4 3 Immersion heater 12 5 OPERATION 14 5 1 General 14 5 2 Aerona heat p...

Страница 4: ...External Volumiser to the heat pump The 3kW electric immersion element is supplied factory fitted and located inside a removable panel at the right hand side of the volumiser viewed from the front It...

Страница 5: ...coated Insulation Mineral wool Immersion Heater Make Cotherm TSR Output kW 3 Electrical supply 230V 50Hz 1ph 2 1 TECHNICAL SPECIFICATION 2 TECHNICAL DATA 2 2 DIMENSIONS Figure 2 1 Grant External Volu...

Страница 6: ...the heat pump and the front face of the external volumiser If the rear face of the volumiser is 50mm from the wall this will leave a distance of approximately 400mm between the wall and the back of t...

Страница 7: ...re the heat pump feet to the AV mounts The gap between the rear of the heat pump and the front of the External Volumiser should be approximately 100mm Refer to Figure 3 6 If not then slacken the four...

Страница 8: ...ize of heat pump the volumiser is connected to Refer to the following details for the model of heat pump being fitted 3 7 1 AERONA HPID6R32 HEAT PUMP As the INLET on the top of the external volumiser...

Страница 9: ...3 4 5 6 7 8 6 9 Figure 3 11 External volumiser connection to HPID10R32 heat pump exploded image Table 3 3 Key to Figure 3 11 Item Description Source 1 External volumiser N A 2 Volumiser inlet connecti...

Страница 10: ...with heat pump 8 Heat pump flow connection 1 BSP N A 9 Volumiser outlet connection 28mm compression Supplied on Volumiser 10 Heat pump return connection 1 BSP N A Figure 3 13 External volumiser conne...

Страница 11: ...he supplementary immersion heater uses a dedicated power supply from a correctly sized circuit breaker in the consumer unit The final supply connection must be made from a weatherproof lockable isolat...

Страница 12: ...for external volumiser connection diagram 4 3 IMMERSION HEATER The Grant External Volumiser is supplied factory fitted with a pre wired 3kW Cotherm Type TSR immersion heater WARNING The immersion hea...

Страница 13: ...level or slightly above the surface of the housing To reset the over temperature cut out Isolate the volumiser immersion element from the mains electrical supply Wait for the temperature in the volum...

Страница 14: ...tting menus via the heat pump remote controller refer to Aerona installation instructions Section 9 3 Set the parameters as detailed in the table below Table 5 1 Aerona heat pump parameter settings fo...

Страница 15: ...e Industrial Estate Swindon SN5 8YG Telephone 44 0 1380 736920 Fax 44 0 1380 736991 Email info grantuk com Website www grantuk com Product 30Ltr EXTERNAL VOLUMISER C W 3KW BACKUP HEATER Model HPIDVOL3...

Страница 16: ...artment on 44 0 1380 736920 who will arrange for a competent service engineer to rectify the fault Remember before you contact Grant Engineering UK Limited Ensure the External Volumiser has been insta...

Страница 17: ...Limited must be informed of the new owner s details The Company will endeavour to provide prompt service in the unlikely event of a problem occurring but cannot be held responsible for any consequence...

Страница 18: ...Page 18 Notes NOTES...

Страница 19: ...Notes Page 19 NOTES...

Страница 20: ...GRANT ENGINEERING UK LIMITED Frankland Road Blagrove Industrial Estate Swindon SN5 8YG Tel 44 0 1380 736920 Fax 44 0 1380 736991 Email info grantuk com www grantuk com...

Отзывы: