8
OPERATION OPTIONS DIP SWITCHES 1, 2, 3 AND 4
(refer to wiring diagram on page 13)
DIP switches position settings
:
DIP 1: Must be set to OFF
DIP 2: Must be set to OFF
DIP 3 set to OFF: No HP coil or HP coil in return
DIP 3 set to ON: HP Coil in supply (Default)
DIP 4: Must be set to OFF
OPERATION OPTIONS DIP SWITCHES A, B, C
These switches are used to select the correct kW/H output of the furnace. See chart below.
BTU SETTING TABLE (DIP OPTION SWITCHES)
DIP
5KW
10KW
15KW
18KW
20KW
23KW
27KW
A
OFF
ON
OFF
ON
OFF
ON
OFF
B
OFF
OFF
ON
ON
OFF
OFF
ON
C
OFF
OFF
OFF
OFF
ON
ON
ON
OPERATION OPTION DIP SWITCH D - QUIET COMFORT FEATURE
When the Quiet Comfort Feature has been activated at DIP switch D and the continuous circulation
fan switch is in the ON position, the LED light on the front of the furnace will flash AMBER.
This
feature will activate one of the heating elements at 50% of its capacity for a maximum period
of three (3) hours unless a call for heat is made by the thermostat, which will reset the three
(3) hour timer. The feature allows for preheated continuous circulating air to provide added
comfort in the home.
DEICING MODE (WITH HEAT PUMP ONLY)
When this unit is installed in accordance with a heat pump unit. While the heat control enters its
deicing cycle, depending on the position of DIP Switch 3 (explained above in the DIP Switches
Position Settings) the furnace control will activate one or more electric elements to generate heat
to mitigate the cooling of circulating air caused by the heat pump deicing cycle.
CIRCUIT BREAKERS
The 16A furnace mounted circuit breaker on the front of the appliance provides fan motor over
amp protection. This circuit protection only applies to the fan motor.
The higher amperage heating element circuit breaks provide overload circuit protection in the event
one or more of the heating elements should fail. Should this happen, one or more of the circuit
breakers will trip to the off position.
Do not attempt to reset the breaker or access the control
panel. Call a licensed servicing contractor immediately.
Warning
Do not use these circuit breakers the power off to the furnace. Prior to removing any of the furnace access
panels ensure that the power has been safely turned off at the main electrical disconnect switch.
.
Содержание Conforto KLE 10 TO 27kW
Страница 14: ...14...