20
10.0 TECHNICAL INFORMATION
B*C Cast Iron Boiler specifications
Riello Burner
40 F3
40 F5
40 F10
Unit Model
B*C – E6-0085-**
B*C – E7-0121-**
B*C –E7-0152-** B*C – E7-0174-**
B*C – E8-0194-**
B*C – E8-0224-**
Number of sections
3 SECTIONS
4 SECTIONS
5 SECTIONS
6 SECTIONS
7 SECTIONS
8 SECTIONS
Firing Rate (USGPH)
0,60
0.80
1,25
1.39
1.60
1.80
Input (BTU/h)
84,000
112,000
175,000
194,000
224,000
252,000
Output (BTU/h)
73,000
98,000
152,000
167,000
195,000
222,000
Nozzle
0,50 70B
0,65 60B
1,00 60W
1.10 60W
1.35 45B
1.50 45B
Pump Pressure (psi)
160
145
160
160
145
145
Turbulator Setting
0
1
3
2
1
2
Air Gate Adjustment
3.2
2.8
3.0
4.8
3.0
3.0
Energy Star Approved
YES
YES
YES
YES
YES
YES
AFUE (%)
87.4
87.4
87.3
87.1
87.4
87.5
CO2 (%)
13
13
13
13
13
13
(*)
In the Unit Model number, is specific information of the product for administration only.
** = 3H for Honeywell control L7248 (high limit only, cold start application)
** = 3L for Fuel Smart HydroStat 3250 (high limit cold start operation or low limit operation)
GRANBY B*C CAST IRON SERIES
Appliance
Model
No. de
section
Length
(inches)
Shipping
weight
(lbs)
Water
Content
(gal.)
Supply Outlet
(inches)
Return Outlet
(inches)
B*C – E6-0085-**
3
18-7/8"
370
5.5
1-1/4"
1-1/4"
B*C – E7-0121-**
4
22-1/2"
437
6.9
1-1/4"
1-1/4"
B*C –E7-0152-**
5
26-3/4"
503
8.2
1-1/4"
1-1/4"
B*C – E7-0174-**
6
31-1/8"
569
9.5
1-1/4"
1-1/4"
B*C – E8-0194-**
7
35-1/2"
639
10.8
1-1/4"
1-1/4"
B*C – E8-0224-**
8
39-3/4"
705
12.2
1-1/4"
1-1/4"
WARNING: Do not operate if any controls have been submerged. Contact a
qualified technician for inspection prior to use.
Содержание B*C-3 sections
Страница 25: ...24...
Страница 26: ...25 Trouble Shouting the HydroStat 3250...
Страница 29: ...28 13 0 EXPLODED PARTS VIEW Exploded Parts View...