765041996
Rev. 001
14
‐20 if the P4 parameter is set at 0, 2 or 3, the condenser fan shall
work in parallel with the compressor
‐21 the condenser fan is switched on provided that the compressor is switched on and is switched off when the condenser temperature falls below the value set with parameter F11 provided that the compressor is switched off
‐22 the compressor is switched off 10 s after the activation of the input; if the input is activated during defrost or when the evaporator fan is deactivated, the activation will not have any effect on the compressor
‐23 to avoid damaging the connected load, set the parameter when
the device is switched off (“stand‐by” status).