765041996
Rev. 001
12
A1
0
99
°C/°F (1)
10
0
5
0
5
room temperature or CPT temperature below which the minimum temperature alarm is triggered (code "AL"; it concerns the
working setpoint, that is to say, "working setpoint ‐ A1"); see also A11
0 = alarm absent
A4
0
99
°C/°F (1)
10
5
10
5
10
room temperature or CPT temperature above which the maximum temperature alarm is triggered (code “
AH
"
; it concerns the
working setpoint, that is to say, "working se A4”); see also A11
0 = alarm absent
A6
0
99
10 min
12
18
18
18
18
delay in maximum temperature alarm (code “
AH
"
) after the device is switched on (5)
A7
0
240
min
15
60
60
60
60
minimum temperature alarm delay (code "
AL
") and maximum temperature alarm delay (code "
AH
")
A8
0
240
min
15
60
60
60
60
delay in maximum temperature alarm (code “
AH
"
) from the conclusion of evaporator fan standstill (13)
A9
0
240
min
15
15
15
15
15
delay in maximum temperature alarm (code “
AH
"
) following the deactivation of the door switch input (14)
A11
0,1
15
°C/°F (1)
2
2
2
2
2
differential of A1 and A4 parameters
PARAM. MIN.
MAX.
U.M.
DEF.
GRAM FG
HAV
GRAM KG
HAV
GRAM FG
FAV
GRAM KG
FAV
EVAPORATOR FAN AND CONDENSATOR FAN
F0
0
4
‐‐‐
3
evaporator fan activity during normal operation 0 = switched off
1 = switched on; see also F4, F5, i10 and HE2 (15)
2 = in parallel with the compressor; see also F4, F5, F9, F15, F16, i10 and HE2 (16)
3 = depending on F1; see also F4, F5, i10 and HE2 (17) (18)
4 = switched off if the compressor is switched off, depending on F1 if the compressor is switched on; see also F4, F5, i10 and
HE2 (17) (19)
F1
‐99
99
°C/°F (1)
‐1
evaporator temperature above (if r5 = 0) or below (if r5 = 1) which the evaporator fan is switched off (only if F0 = 3 or 4) (7)
F2
0
2
‐‐
0
evaporator fan activity during defrost and dripping
0 = switched off
1 = switched on
2 = depending on F0
F3
0
15
min
2
maximum duration of the evaporator fan stop; see also F7 (during the evaporator fan stop the compressor can remain on, the
defrost outlet shall remain deactivated and the evaporator fan shall remain off)
F4
0
240
10 s
30
duration of the evaporator fan switch off during the "energy saving function"; see also F5, i5, i10 and HE2
F5
0
240
10 s
30
duration of the evaporator fan switch on during the "energy saving function"; see also F4, i5, i10 and HE2
F7
‐99
99
°C/°F (1)
5
evaporator temperature below which the evaporator fan is restarted (in respect to the working setpoint, that is to say
“working set‐point + F7”); see also F3
F9
0
240
s
10
evaporator fan stop delay after the stop of the compressor (only if F0 = 2)
F11
0
99
°C/°F (1)
15
condenser temperature above which the condenser fan is switched on (7) (20) (21)
F12
0
240
s
30
condenser fan stop delay after the stop of the compressor
F15
0
240
s
10
duration of the evaporator fan stop when the compressor is turned off; see also F8 (only if F0 = 2)
F16
0
240
60
60
60
60
duration of the evaporator fan operation when the compressor is turned off; see also F7 (only if F0 = 2)
PARAM.
MIN.
MAX.
U.M.
DEF.
GRAM FG
HAV
GRAM KG
HAV
GRAM FG
FAV
GRAM KG
FAV
DIGITAL INPUTS
i0
0
5
‐‐‐
5
2
2
2
2
effect caused by the activation of the door micro input; see also i2
0 = no effect
1 = COMPRESSOR AND EVAPORATOR FAN SWITCH‐OFF ‐ the compressor and evaporator fan will be switched off (for the
duration of the i3 time max. or until the input is deactivated; in the latter case the evaporator fan shall be turned on 5 s
after input deactivation) (22)
2 = EVAPORATOR FAN SWITCH‐OFF ‐ the evaporator fan shall be switched off (for the duration of the i3 time max. or until 5s
after input deactivation)
3 = ROOM LIGHTING SWITCH‐ON ‐ the room lighting shall be switched on (until 10 s after input deactivation)
4 = COMPRESSOR AND EVAPORATOR FAN SWITCH‐OFF AND ROOM LIGHTING SWITCH‐ON ‐ the compressor and evaporator
fan
will be switched off (for the duration of thr i3 time max. or until the input is deactivated; in the latter case the evaporator
fan shall be turned on 5 s after the input deactivation) and the room lighting shall be switched on (until 10 s after input
deactivation) (22)
5 = EVAPORATOR FAN SWITCH‐OFF AND ROOM LIGHTING SWITCH‐ON ‐ the evaporator fan will be switched off (for the
duration of the i3 time max. or until 5 s after input deactivation) and the room lighting shall be switched on (until 10 s after
input deactivation) (22)
i1
0
1
0
0
0
0
0
type of door switch input contact
0 = normally open (active input with closed contact)
1 = normally closed (active input with open contact)
i2
‐1
120
min
30
5
5
5
5
delay in signalling of door switch input alarm (code “
id
"
)
‐1 = the alarm will not be signalled
i3
‐1
120
min
15
‐1
‐1
‐1
‐1
maximum duration of the effect caused by the activation of the door micro on the compressor and evaporator fan
‐1 = the effect shall last until the input is deactivated
i5
0
6
‐‐‐‐
2
0
0
0
0
effect caused by the activation of the multifunction input
0 = no effect
1 = “ENERGY SAVING” FUNCTION ACTIVATION ‐ the “energy saving” function shall be activated (until the input is deactivated),
provided that the "rapid cooling" function is not in progress; see also r4
2 = MULTIFUNCTION INPUT ALARM ACTIVATION (code “
iA
"
) ‐ the device shall continue working regularly; see also i7
3 = AUXILIARY OUTPUT SWITCH‐ON ‐ the auxiliary output shall be switched on (until the input is deactivated)
4 = DEVICE SWITCH‐OFF ‐ the device shall be switched off (“stand‐by” mode, until the input is deactivated)
5 = COMPRESSOR THERMAL PROTECTION ALARM ACTIVATION (code “
Cth
"
) ‐ the compressor shall be switched off (until the
input is deactivated); see also i7
6 = GLOBAL THERMAL PROTECTION ALARM ACTIVATION (code “
th
"
) ‐ all the utilities shall be switched off (until the input is
deactivated and the device shall be switched off (“stand‐by” mode) and switched back on or the power supply is cut); see
also i7
i6
0
1
‐‐‐
0
0
0
0
0
type of multifunction input contact
0 = normally open (active input with closed contact)
1 = normally closed (active input with open contact)