7. Additional function of the KLplus/KL24plus and KLbasic/KL24base control unit
37 / 54
Feed the suction hose into the precipitant container far enough to ensure suction from
the base.
Connect the suction and pressure hoses to the hose nozzles of the pump and fix them
with the cap nuts.
Switch the phosphate pump on via the menu item ‘Manual Operation’ and check that
the precipitant is sucked in correctly. Swap the hose connections if necessary.
The suction hose can optionally be equipped with a suction lance.
Overview precipitant pumps
7.3.5
Compact
DP12
DP24
Figure 13: Compact precipitant pump
Figure 14: DP12 and DP24 precipitant pumps
Delivery volume: 5.5 ml/min
Reference values for adjusting pump performance for precipitant pump compact
P
1
2
3
4
5
6
7
8
9
10
[ml/min]
1,5
5,5
11,0
15,0
19,0
22,5
26,0
30,5
35,0
37,5