Installation
6
3A3381E
Installation
Grounding
Pump: use a ground wire and clamp. See F
IG
. 1 Loosen
the locknut (W) of the grounding lug (Z). Insert one end
of the wire (Y) in the ground lug and tighten the locknut
securely. Connect the ground clamp to a true earth
ground. Order Part No. 237569, Ground Wire and
Clamp.
.
Air and fluid hoses: use only electrically conductive
hoses with a maximum of 500 ft. (150 m) combined
hose length to ensure grounding continuity. Check the
electrical resistance of hoses. If total resistance to
ground exceeds 25 megohms, replace hose immedi-
ately.
Hydraulic power supply: follow manufacturer’s recom-
mendations.
Surge tank: use a ground wire and clamp.
Dispense valve: ground through a connection to a
properly grounded fluid hose and pump.
Fluid supply container: follow local code.
Object being sprayed: follow local code.
Solvent pails used when flushing: follow local code.
Use only conductive metal pails, placed on a grounded
surface. Do not place the pail on a non-conductive sur-
face, such as paper or cardboard, which interrupts
grounding continuity.
To maintain grounding continuity when flushing or
relieving pressure: hold metal part of the spray gun or
valve firmly to the side of a grounded metal pail, then
trigger the gun or open the valve.
The equipment must be grounded to reduce the risk
of static sparking. Static sparking can cause fumes to
ignite or explode. Grounding provides an escape wire
for the electric current.
F
IG
. 1 Ground Wire
TI15854a
Z
Y
W