Installation
8
313444E
Dip Switch Settings: Models With Timers
Pause (off) Time (F
The Pause (off) Time is set using dip switches DS3 and
DS1 to select the time to deliver the required lube vol-
ume per hour.
For example:
If 12 cycles per hour are
required 60 ÷ 12 = 5; set the pause time to 5 minutes.
NOTE:
Do not exceed 20 minutes Pause (off) time.
Work (on) Time (F
The Work (on) Time is set using the DS2 dipswitches.
NOTE:
A Work (on) Time of 20 seconds will normally be
sufficient.
J1 is used to Yes or No. When set to Yes, the lube cycle
will immediately power up.
Pressure Switch (F
For timer models, J2 must be set to the monitored posi-
tion.
F
IG
. 3