Installation
3A8507C
3
Error Flash Patterns (LED)
Register TLM to Tank in Pulse
Level Software
Assign a TLM serial number to a tank in Pulse Level.
Navigate to URL: level.gracopulse.com
After creating user, organization, branch and site,
navigate to Devices (located in the upper right corner of
the screen). Associate the device to your organization
by entering the serial number and activation code.
When you create a tank for the site, the device will be
assignable.
Typical Installation
Mount Options
Identify a threaded opening on the top of the tank for
the sensor. The location should be vertical with a clear
path to the contents of the tank. There should be no
obstructions that could interfere with the signal.
1. If the hole is not threaded, place the foam gasket
(included with kit) over the opening.
2. Place the mounting adapter (included with kit) on
top of the foam gasket.
3. Use the two (2) stainless steel self-tapping,
counter-sunk screws (included with kit) to attach
the adapter to the tank. Do not over tighten.
4. Attach the sensor to the adapter. To form a secure
seal, make sure that the sensor is vertical on the
tank, that it is secured correctly to the base, and
that the threads have not crossed.
NOTE: If the tank does not contain a suitably positioned
opening at the top of the tank, reference
, page
No. of
Flashes
Function
Resolution
1
Unable to find WiFi
network
Verify that Connect to
WiFi was selected on
the browser
2
Unable to connect to
WiFi network
Improve WiFi signal
strength or enable
MAC filtering on the
router
3
WiFi password is
incorrect
Verify information
entered is correct
Verify that the WiFi
network’s security
supports WEP, WPA, or
WPA2 security
5
Pulse Level is
unavailable
Confirm that port 80 is
not blocked for your
device IP address
6
Invalid response
from the Pulse Level
Retry
7
Firmware download
failed
Check that the network
is up and stable before
trying again
8
Low battery
Change batteries
9
Critical failure
Replace the Tank Level
Monitor
F
IG
. 4