Appendix A - I/O Signal Descriptions
3A6338B
19
Appendix A - I/O Signal Descriptions
This section provides details about the CGM Automation Input and Output Signals.
Automation Inputs (signals from EFR system to PLC)
Heartbeat to PLC
Heartbeat to PLC is a Boolean signal that toggles at a
frequency of 1 Hz. This signal toggles so the PLC can
confirm the EFR is connected.
NOTE:
The EFR is monitoring the fieldbus connection
as well. If the fieldbus connection stops transferring
data, the EFR will automatically shut down.
System On
System On is a Boolean signal that represents the
active state of the machine.
NOTE:
The system must be ON or active for the
machine to dispense.
System Ready
System Ready State is a Boolean signal that represents
when the machine is ready to receive the next
command.
NOTE:
the system will not be ready to receive the next
command if the EFR is dispensing, loading a sequence,
or if an active alarm is present.
Active Alarms
Active Alarms is a Boolean signal that represents the
active alarms on the EFR.
NOTE:
When an alarm is present, the EFR requires the
operator’s attention and will shut down immediately.
Active Deviations
Active Deviations is a Boolean signal that represents the
active deviations on the EFR.
NOTE:
When a deviation is present, the EFR is warning
the operator of potential problem(s) that may need
immediate attention to avoid shutdown time.
Active Advisories
Active Advisories is a Boolean signal that represents the
active advisories on the EFR.
NOTE: When an advisory is present, the EFR is warning
the operator of potential problem(s) that may need
attention in the future to avoid shutdown time.
Current Sequence is Playing
Current Sequence is Playing is a Boolean signal that
represents when the sequence is dispensing/running.
Current Sequence is Paused
Current Sequence is Paused is a Boolean signal that
represents when the sequence is paused.
Current Sequence is Stopped
Current Sequence is Stopped is a Boolean signal that
represents when the sequence is stopped.
Dispense Valve Open
Dispense Valve Open is a Boolean signal that
represents when the valve is open.
System is Priming
System is Priming is a Boolean signal that represents
when the system is priming.
System is Purging
System is Purging is a Boolean signal that represents
when the system is purging.
System is Parking
System is Parking is a Boolean signal that represents
when the system is parking.
System is Depressurizing
System is Depressurizing is a Boolean signal that
represents when the system is depressurizing.