5
TROUBLESHOOTING
Symptom
Probable Cause
Corrective Action
A�
Meter counter does
1� Broken counter assembly�
Replace counter�
not operate. (Nor-
mal fuel delivery) 2. Foreign material in counter Remove and clean counter
assembly or nutator assembly� assembly or nutator assembly�
3� Broken nutator disc pin or
Install new nutator assembly�
defective nutator assembly�
4� Missing or worn bevel gear�
Replace bevel gear�
B�
Meter counter does
1� Clogged strainer in meter�
Clean or replace strainer�
not operate�
(Little or no fuel flow)
2� Other system components
Check all system components
malfunctioning�
tank to nozzle for clogs and/or
malfunctions� Repair as necessary�
3� Foreign material in nutator
Remove and clean nutator
assembly�
assembly�
C� Fuel leakage�
1�
Leakage at counter drive shaft�
Replace coverplate assembly�
2� Leakage between coverplate Remove coverplate and inspect
and housing�
for damaged, missing or
incorrectly seated seal� Replace
as required�
3. Leakage at fittings.
Remove fittings and inspect for
damaged, missing or incorrectly
seated seals� Replace as required�
4� Leakage at threads�
Remove meter and reseal all
threaded connections with
thread tape or pipe thread
sealing compound approved
for use with flammable liquids
.
SPECIFICATIONS
Gallon Models
Litre Models
Unit of Measure
U.S. Gallon
Litre
Flow Range
5 to 30 GPM
19 to 114 LPM
Typical Accuracy
± 2%
± 2%
Type
Nutating Disc
Nutating Disc
Housing Material
Aluminum
Aluminum
Maximum Working Pressure
50 PSIG
3�4 bar
Inlet/Outlet Fitting Size
1"
1"
Threads
NPT NPT
Maximum Batch Total
999�9
9999
Maximum Cumulative Total
9,999,999�9
99,999,999
Approximate Ship Weight
8�1 lbs�
3�7 kg
Maximum Dimensions: Width: 8�0 inches
20�3 cm
Height: 7.0 inches
17.8 cm
Depth: 6�0 inches
15�2 cm
Note: Accuracy is factory calibrated using kerosene grade (JET A). Field Calibration