11
7.3.Description.of.indicators.and.circuit.board.jumpers
The.LEDs.located.on.the.Ethernet.port.indicate.the.physical.connection’s.state.(Link,.green).and.
transfer.activity.(Activity,.red).
The.
IPRST
jumper.is.used.to.reset.the.network.configuration.to.factory.settings..To.do.this,.you.
must.close.the.jumper.contacts.and.wait.for.the.Link.and.Activity.LEDs.to.go.out..Afterwards,.the.
jumper.must.be.opened.again.
The.
BOOT
jumper.is.used.to.put.the.terminal.into.bootloader.mode..This.mode.allows.you.to.
restore.the.terminal.to.normal.function.if.its.firmware.becomes.corrupted..To.enable.bootloader.
mode,.you.must.close.the.
BOOT
jumper.with.the.power.off.and.then.power.on.the.terminal..After.
the.terminal.is.powered.on,.the.contacts.must.be.opened..The.terminal’s.display.should.show.the.
message.“BOOT”..The.process.of.loading.the.terminal’s.firmware.is.described.in.more.detail.in.the.
terminal’s.Operating.Manual..
8. INSTALLATION
8.1.Installation.notes
When deciding where to install the terminal, the following should be taken into account:
-.The.recommended.height.for.the.terminal.is.120-150.cm.from.the.floor,.for.reasons.of.conveni-
ence.in.positioning.the.palm.on.the.scanner,.presenting.a.card.and.viewing.events.on.the.LCD.screen..
Access.to.the.terminal.should.be.free.and.unobstructed.to.allow.for.convenient.positioning.of.the.
palm..
-.If.installing.multiple.terminals,.they.must.be.placed.no.closer.than.80.cm.away.from.each.other.in.
order.to.minimize.mutual.interference.from.their.in-built.RFID.card.readers.
-.Installing.a.terminal.within.1.m.of.any.external.RFID.readers.or.other.sources.of.electromagnetic.
interference.is.not.recommended..Nearby.sources.of.electromagnetic.interference.may.negatively.
affect.the.operation.of.the.built-in.RFID.card.reader.
-.It.is.recommended.to.leave.some.length.in.the.cables.attached.to.the.terminal,.enough.to.remove.
the.terminal.from.the.wall.and.access.its.jumpers.
-.If.the.device.is.installed.on.a.metal.surface,.the.range.of.its.RFID.card.reader.may.be.reduced.
When installing cables, please observe the following recommendations:
-.Cables.must.be.installed.in.accordance.with.the.operational.code.for.electrical.installations;
-.Do.not.lay.cables.within.30.cm.of.sources.of.electromagnetic.interference;
-.All.cables.must.only.intersect.power.cables.at.a.right.angle;
-.Any.cable.extensions.must.be.soldered.