Initial Start-Up

The 

PROFITEST PV

SUN

 is supplied with power from four AA batteries 

(1.5 V IEC LR6). The batteries must be inserted before the instru-
ment can be used.

Remove the battery compartment lid on the back of the in-
strument by loosening the two Phillips head screws.

Insert the batteries. Be sure to observe the polarity symbols 
which are embossed into the floor of the battery compart-
ment.

Replace the battery compartment lid and retighten the 
screws.

Attention!

!

The test instrument may only be operated with installed 
battery compartment lid.

9

Measurements

Warning!

The photovoltaic system’s plug connectors may not be 
disconnected under load. Please observe warnings and 
instructions provided by the plug manufacturer.

Caution! Dangerous Voltage

Solar modules continuously generate current, even when 
shaded. Regulations for working with live voltage must 
be adhered to during all work.

Switching the PROFITEST PV

SUN

 On

The test instrument is switched on by pressing the 

 key.

After the test instrument has been switched on, background 
illumination can be switched on by briefly pressing the same 
key once again.

Briefly pressing the key a third time switches background illu-
mination back off.

The test instrument can be switched off by pressing and hold-
ing the key for longer than 2 seconds.

9.1

Testing Protective Conductor Continuity 
per EN 62446 (VDE 0126-23) (> 200 mA)

If a protective conductor or an equipotential bonding conductor is 
included at the DC side of the photovoltaic system, its electrical 
connection must be tested for continuity.
The connection to the main grounding terminal must also be tested.

Warning!

Disconnect all solar modules from the system before 
performing the measurement.

Compensation for Measurement Cable Resistance

Ohmic measurement cable resistance can be subtracted from the 
measurement results automatically. Proceed as follows in order to 
determine the resistance offset value:

Switch the 

PROFITEST PV

SUN

 test instrument on.

Connect the measurement cables to the (–) and (

) sockets 

and short-circuit the plug-on test probes.

Press and hold the 

COMP

 key for at least 2 seconds in order to 

trigger offset resistance measurement. 
Symbol 

 briefly appears. 

The following display appears after completion of the mea-
surement: 

R

LOW

: 0.0 



.

The measured 

R

OFFSET

 

value is not displayed, but is permanently stored 

internally and is subtracted from the actual result of all subsequent 

R

LOW

 

measurements, until a new offset resistance value is acquired.
If the measured value of the connected cable is > 5 

 the symbol 

 briefly appears. Compensation of measurement cable resis-

tance is not possible.

Protective Conductor Resistance Measurement

Connect the (–) socket to a protective conductor terminal at 
the solar module and the (

) socket to the equipotential bond-

ing busbar.

Briefly press the 

R

LOW

 key.

Measurement is started. The 

R

LOW

 resistance value measured for 

the protective conductor system appears at the display: 
Example

Attention!

!

Measurement results may be distorted due parallel con-
nected impedances at load current circuits, as well as 
equalizing current.

9.2

Polarity Test / Measuring Open Circuit Voltage U

0

 

per EN 62446 (VDE 0126-23)

Warning!

Disconnect the solar module under test from the system 
before performing measurement.

Connect the 

PROFITEST PV

SUN

 test instrument to the module 

with the help of suitable solar plugs.

U0: 0 V
R

LOW

: 0.1 

R

ISO

: ---

www.

.com

[email protected]

1.800.561.8187

Содержание PROFITEST PVSUN

Страница 1: ...Operating Instructions PROFITEST PVSUN and PVSUN MEMO Test Instruments for Testing PV Modules and Strings per DIN EN 62446 VDE 0126 23 3 349 672 15 11 3 16 www com information itm com 1 800 561 8187 ...

Страница 2: ...g instructions 1 USB interface cable PROFITEST PVSUN MEMO only 2 Significance of Symbols Meanings of Symbols on the Instrument Warning concerning a point of danger attention observe documentation Protection class II device continuous doubled or reinforced insulation This device may not be disposed of with the trash Fur EC mark of conformity Meanings of Symbols in the Operating Instructions Caution...

Страница 3: ...sured the instrument must be removed from service and secured against unintentional use Safety of the user is no longer assured if the instrument Demonstrates apparent damage No longer performs the desired measurements Has been stored for too long under unfavorable conditions Has been subjected to mechanical stressing during transport The instrument may not be opened dismantled or modified in any ...

Страница 4: ...terminal must also be tested Warning Disconnect all solar modules from the system before performing the measurement Compensation for Measurement Cable Resistance Ohmic measurement cable resistance can be subtracted from the measurement results automatically Proceed as follows in order to determine the resistance offset value Switch the PROFITEST PVSUN test instrument on Connect the measurement cab...

Страница 5: ...r module under test from the system before performing measurement Attention Insulation measurement per EN 62446 is executed be tween short circuited and terminals Connect the PROFITEST PVSUN test instrument to the module with the help of suitable solar plugs Connect the ground terminal at the PROFITEST PVSUN to the module frame Switch the PROFITEST PVSUN test instrument on The module s open circui...

Страница 6: ...ressing the RISO 250V 500V 1000V key The last selected value is saved after a short period of time and is then cleared from the display Example Executing the Insulation Resistance Measurement Press the RISO 250V 500V 1000V key and read the measured value from the display Example Note If the minimum permissible limit value is fallen short of 1 M or 0 5 M appears for RISO 9 6 Ground Fault Test If th...

Страница 7: ...ch between objects and strings Symbol indicates whether objects or strings are active e g OBJ Object1 Standard measurement display without memory function The storage function is not activated before switch over to storage display see screenshot below Standard measurement display with activated storage function If a measurement is per formed the measured values are stored under the object and stri...

Страница 8: ...lect directory C Programme PVSUN MEMO Control Center USB Driver unless you have changed the installation path Ignore the message regarding unknown provenance of the software Complete the driver installation Please check PVSUN MEMO Memory COMxx should be displayed in the device manager under Connections Start the installed program PVSUN MEMO Control Center Click on icon Search device 11 4 Creation ...

Страница 9: ...e 0 to 10 Test current 200 mA Resolution 0 1 Accuracy 1 rdg 1 d No of measurements Approx 500 low resistance measurements batteries 1 5 V per IEC LR6 Display LCD Backlit multiple display Dot matrix 128 x 64 pixels Reference Conditions Ambient temperature 23 C 2 K Relative humidity 40 to 75 Battery voltage 6 V 1 V Ambient Conditions Operating temperature 0 to 40 C Storage temperature 10 C to 60 C R...

Отзывы: