The following limit values are indicated:
1)
Resistance between housing and mains plug for connector cables up to 5 meters long
2)
0.1
Ω
is added for each additional 7.5 meters of cable length, up to a maximum of 1
Ω
3)
For protection class I devices with activated heating elements
(if heating power > 3 kW and R
ISO
< 0.3 M
Ω
: leakage current measurement is required)
4)
This limit value refers to all-pole switches (corresponds to doubling the limit value or cutting actual
measuring current in half)
10
Technical Data
10.1 Test case
Power Supply
Nominal line voltage 230/400 V 50 Hz
Mains connection
230 V 1P+N+PE 16 A earthing contact plug with coupling socket
or
230/400 V 3P+N+PE 16 A CEE plug with coupling socket
or
230/400 V 3P+N+PE 32 A CEE plug with coupling socket,
max. 16 A !
Throughput rating:
Rated input per phase 16/20 A, 10 min., protection class I
Measuring category
300 V CAT II
Pollution degree
2
RCD (RCCB) 4-pole,
I
N
25 A, I
A
0.03 A
Protection, case:
IP 40 per DIN VDE 0470, part 1, connections: IP 20
Dimensions (WxHxD) Approx. 380 x 300 x 220 mm with cover
Weight
Approx. 7.5 kg
Measurement
Fault Condition per
Standard
Indication of Exceeded Limit Value
at the Test Instrument
Continuously Lit
Red Error Lamp
Display of Limit
Values
Continuous
Buzzing (beeper)
Protective conduc-
tor resistance
R
SL
> 0.3
Ω
1)
•
> 0.3
Ω
—
R
SL
> 1
Ω
2)
•
> 1
Ω
•
Insulation
resistance
Heater
3)
:
R
ISO
< 0.3 M
Ω
•
< 0.5 M
Ω
•
PCI:
R
ISO
< 1.0 M
Ω
•
< 2.0 M
Ω
—
PCII:
R
ISO
< 2.0 M
Ω
—
< 2.0 M
Ω
—
Equivalent leakage
current
I
EA
> 3.5 mA
•
—
—
•
> 7.0 mA
4)
•
Leakage/contact
current (verifica-
tion of absence of
voltage)
I
A
> 0.25 mA
•
> 0.25 mA
—
I
A
> 0.5 mA
•
> 0.5 mA
•
Differential current
I
Diff
≥
3.5 mA
•
—
•