![Gossen MetraWatt MAVOWATT 210 ROGOWSKI Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/gossen-metrawatt/mavowatt-210-rogowski/mavowatt-210-rogowski_operating-instructions-manual_2247134017.webp)
Gossen Metrawatt GmbH
MAVOWATT 210
14
5.6
Characteristic Values
Data Interfaces
Ethernet
10 Mbit/s
USB
2.0
Protocols
Modbus, BACnet®
Internal
Memory
Storage capacity
8 GB
General
Sampling frequency
32 ksps (recorded
and real-time meters),
128 samples per cy-
cle (periodic waveform
snapshots)
Sag/dip, swell trigger resolution
1-cycle (uses IEC
61000-4-30 Class S
methods)
Voltage
Range
90 to 600 VRMS
CATIII
Accuracy
90 VRMS to
600 VRMS = ±0.1%,
<90 VRMS = 0.5%
Connections
4 safety banana volt-
age inputs - 3-phase
voltage and 1 neutral/
reference
Current
Input
0.333 VRMS full
scale, Connections:
BNC
Accuracy
±0.1% + probe
Frequency
Range
50 Hz = 45 Hz to
55 Hz,
60 Hz = 55 Hz to
65 Hz
Accuracy
50/60 Hz: ±0.001 Hz