06 Electrical Connection
WARNING
•
Pay attention to the silkscreens L1, L2, N, PE on the AC terminal. Connect the AC cables to
the corresponding terminals. The inverter may be damaged if the cables are connected
inappropriately.
•
Make sure that the whole cable cores are inserted into the AC terminal holes. No part of
the cable core can be exposed.
• Make sure that the cables are connected securely. Otherwise, the terminal may be too hot
to damage the inverter when the inverter is working.
Inverter model
AC circuit breaker
GW5000-MS-US30
30A
GW6000-MS-US30
35A
GW7600-MS-US30
40A
GW9600-MS-US30
50A
GW11K4-MS-US30
60A
Model
RCD specifications
GW5000-MS-US30
300mA
GW6000-MS-US30
GW7600-MS-US30
GW9600-MS-US30
GW11K4-MS-US30
A type A RCD(Residual Current Device) shall be added to protect the equipment when the DC
component of the leakage current exceeds limits. Recommended RCD specifications:
Step 1
Make the AC output cable.
Step 2
Disassemble the DC routing hole’s end cap.
Step 3
Use the cable gland for routing wires.
Step 4
Plut the AC connector into the inverter.