p
rodUCt
S
pECifiCationS
p
rodUCt
S
pECifiCationS
SS-SSX16
www.goodmanmfg.com
3
S
pECifiCationS
SSX16
0241B*
SSX16
0301A*
SSX16
0361B*
SSX16
0421A*
SSX16
0481B*
SSX16
0591A*
Cooling Capacity
Nominal Cooling (BTU/h)
24,000
30,000
36,000
42,000
48,000
60,000
Decibels
73.5
73.5
73.5
75
74
73.5
Compressor
RLA
13.5
12.8
14.1
16.7
19.9
25.0
LRA
58.3
64
77
79
109
134
Condenser Fan Motor
Horsepower (RPM)
1/6
1/6
1/6
1/4
1/4
1/4
FLA
1.10
1.10
1.10
1.50
1.50
1.50
Refrigeration System
Refrigerant Line Size¹
Liquid Line Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction Line Size (“O.D.)
¾"
¾"
⅞"
1⅛"
1⅛"
1⅛"
Refrigerant Connection Size
Liquid Valve Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction Valve Size (“O.D.)
¾"
¾"
¾"
⅞"
⅞"
⅞"
Valve Connection Type
Sweat
Sweat
Sweat
sweat
Sweat
Sweat
Refrigerant Charge
97
96
102
109
138
251
Electrical Data
Voltage-Phase
208/230-1
208/230-1
208/230-1
208/230-1
208/230-1
208/230-1
Minimum Circuit Ampacity ²
18.0
17.1
18.7
22.4
26.4
32.8
Max. Overcurrent Protection ³
30
25
30
35
45
50
Min / Max Volts
197/253
197/253
197/253
197/253
197/253
197/253
Electrical Conduit Size
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
Ship Weight (lbs)
173
174
182
185
236
287
¹ Tested and rated in accordance with ARI Standard 210/240
² Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes
³ Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
Notes
• Always check the S&R plate for electrical data on the unit being installed.
• Installer will need to supply ⅞” to 1⅛” adapters for suction line connections.
• Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
• Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT NOT
THE INDOOR COIL.