Goodman *MH80453A Series Скачать руководство пользователя страница 42

42

GME8

B

LOWER

 P

ERFORMANCE

 D

ATA

Tons AC

at 0.5"

0.6

0.7

0.8

ESP

CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM

T1 - YELLOW

1.5

875

59

793

65

736

70

674

77

592

88

556

509

460

T2 - RED

2.0

1032

50

965

54

914

57

861

60

810

64

756

712

659

T3 - ORANGE

2.5

1217

43

1153

45

1098

47

1051

49

1009

51

964

918

877

T4 - BLUE

3.0

1365

38

1313

39

1268

41

1221

42

1172

44

1129

1086 1054

T5 - BLACK

3.5

1549

33

1505

34

1460

36

1420

37

1378

38

1350

1305 1268

T1 - YELLOW

2.5

1268

53

1198

56

1151

58

1092

61

1041

64

988

932

883

T2 - RED

3.0

1362

49

1305

51

1261

53

1212

55

1170

57

1121

1074 1021

T3 - ORANGE

3.5

1576

42

1519

44

1473

45

1426

47

1398

48

1341

1290 1252

T4 - BLUE

4.0

1755

38

1711

39

1657

40

1627

41

1579

42

1548

1502 1463

T5 - BLACK

5.0

2183

31

2128

31

2094

32

2060

32

2014

33

1992

1944 1847

T1 - YELLOW

3.0

1466

58

1415

60

1357

63

1306

65

1248

68

1202

1144 1088

T2 - RED

3.5

1642

52

1596

53

1552

55

1499

57

1449

59

1388

1352 1306

T3 - ORANGE

4.0

1750

49

1750

49

1707

50

1667

51

1610

53

1574

1531 1486

T4 - BLUE

4.0

1870

46

1805

47

1782

48

1737

49

1701

50

1656

1606 1571

T5 - BLACK

5.0

2297

37

2297

37

2224

38

2106

40

2014

42

1896

1813 1669

Notes:

•  Temperature rise data is based on 2nd-stage heat.  First-stage heat is 75% of rise indicated above.

•  INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.

•  This chart is for information only.  For satisfactory operation, external static pressure 

should

 not exceed value shown on the rating plate.

•  The above chart is for U.S. furnaces installed at 0-2000 feet. At higher altitudes, a properly derated unit will have approximately the same
    temperature rise at a particular CFM, while ESP at the CFM will be lower.

•  Factory Motor Speed Setting: T1 = 1st Stage Ht, T2 = 2nd Stage Ht, T5 = Cooling.

GME81155CXC*

•  CFM in chart is without filter(s).  Filters do not ship with this furnace, but must be provided by the installer. If the furnace requires  two
    return filters, this chart assumes both filters are installed.

•  All furnaces ship as high-speed cooling and medium-speed heating. Installer must adjust blower cooling and heating speed as needed.

•  For most jobs, about 375 - 400 CFM per ton when cooling is desirable.

(CFM & Temperature Rise vs. External Static Pressure)

0.1

0.2

0.3

0.4

0.5

Model

Heating Speed

As Shipped

Motor Speed

EXTERNAL STATIC PRESSURE (Inches Water Column)

GME80703BXC*

GME80905CXC*

(

)

Содержание *MH80453A Series

Страница 1: ...onsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of common sense a matter of thinking before acting Most dealers...

Страница 2: ...VENTED INTO THIS CHIMNEY CHANNEL 15 CHECK 3 CHIMNEY CROWN CONDITION 16 CHECK 4 DEBRIS IN CLEANOUT 16 CHECK 5 LINER CONDITION 16 CHECK 6 DILUTION AIR 16 CHECK 7 COMPLETE THE INSTALLATION 16 FIX 1 LINER...

Страница 3: ...RATION 27 FURNACE START UP 27 FURNACE SHUTDOWN 27 GAS SUPPLY PRESSURE MEASUREMENT 27 GAS MANIFOLD PRESSURE MEASUREMENT ANDADJUSTMENT 30 GAS INPUT RATE MEASUREMENT NATURAL GAS ONLY 31 TEMPERATURE RISE...

Страница 4: ...SERVICER ONLY 35 IGNITER QUALIFIED SERVICER ONLY 35 BURNERS 35 BEFORE LEAVING AN INSTALLATION 36 REPAIR AND REPLACEMENT PARTS 36 TROUBLESHOOTING CHART 37 BLOWER PERFORMANCE DATA 40 M H S 8 39 D H S8...

Страница 5: ...CE CLOSED IN THE EVENT THAT THE BUILDING MAY BE EXPOSED TO FREEZING TEMPERATURES AND WILL BE VACANT ANY HYDRONIC COIL UNITS SHOULD BE DRAINED AS WELL AND IN SUCH CASE ALTERNATIVE HEAT SOURCES SHOULD B...

Страница 6: ...and the person at the same electrostatic potential these steps will help avoid expos ing the integrated control module to electrostatic discharge This procedure is applicable to both installed and no...

Страница 7: ...Blower Door Interlock Switch Integrated Control Module Transformer Circulator Blower 1 2 3 4 5 6 7 8 9 1 Tubular Heat Exchanger 2 Pressure Switch 3 Flue Pipe Connection 4 Induced Draft Blower 5 Gas Li...

Страница 8: ...ransformer 13 Integrated Control Module 14 Blower Door Interlock Switch 15 Circulator Blower 16 Gas Line Entrance Alternate Tubular Heat Exchanger Flue Pipe Connection Gas Line Entrance Alternate Indu...

Страница 9: ...he home page Next click on the word Product Registration located on the left side of the Warranty page and complete the forms in the manner indicated on the Product Registration page To register yourA...

Страница 10: ...Ventilation Air Requirements Centrally locate the furnace with respect to the proposed or existing air distribution system Ensure the temperature of the return air entering the furnace is between 55 F...

Страница 11: ...enting system are not in operation a Seal any unused openings in the venting system Do not connect this furnace to a chimney flue that serves a separate appliance designed to burn solid fuel For count...

Страница 12: ...ll the thermostat where it may be influenced by any of the follow ing Drafts or dead spots behind doors in corners or under cabinets Hot or cold air from registers Radiant heat from the sun Light fixt...

Страница 13: ...NDUCED DRAFT BLOWER ROTATION Vent the furnace in accordance with the National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition In Canada vent the furnace in accordance with the National Standard of Ca...

Страница 14: ...80 AFUE FURNACE IS VENTED WITHOUT ADEQUATE DILUTION AIR DO NOT CONNECT AN 80 FURNACE TO A MASONRY CHIMNEY UNLESS THE FURNACE IS COMMON VENTED WITH A DRAFT HOOD EQUIPPED APPLIANCE OR THE CHIMNEY IS LIN...

Страница 15: ...Solid fuel appliances include fireplaces wood stoves coal fur naces and incinerators Proper Chimney Termination Check 1 Chimney channel free of solid and liquid fuel appliances Check 2 Change venting...

Страница 16: ...hrough the draft hood of a natural draft appliance only if the appliance s vent connector does not include a vent damper If dilution air will not be available the chimney must be relined Fix 4 Liquid...

Страница 17: ...Flexible liners specifically intended and tested for gas applications are listed in the UL Gas and Oil Equipment Directory UL Standard 1777 CHECK 7 COMPLETE THE INSTALLATION If Checks 1 through 6 hav...

Страница 18: ...LECTRICAL WIRING WARNING LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING CAUTION HIGH VO...

Страница 19: ...upplied wire tabs when rotating junction box to the left side Low voltage wires may be connected to the terminal strip IMPORTANT NOTE To avoid possible equipment malfunction route the low voltage wire...

Страница 20: ...by 10 Set the heat anticipator on the thermostat to match this reading Example If the reading on the ammeter is 4 divide this by 10 The anticipator setting will be 4 amps 115VOLT LINE CONNECTION OF A...

Страница 21: ...ll altitudes and with either fuel the air temperature rise must be within the range listed on the fur nace nameplate Should this appliance be converted to LP refer to the instructions included in the...

Страница 22: ...g piping Use pipe joint compound on male threads only Pipe joint compound must be resistant to the action of the fuel used Use ground joint unions Install a drip leg to trap dirt and moisture before i...

Страница 23: ...g its manual shutoff valve before pressure testing of gas sup ply piping system with test pressures equal to or less than 1 2 psig 3 48 kPa PROPANE GAS TANKS AND PIPING IF THE GAS FURNACE IS INSTALLED...

Страница 24: ...ct system must be used with the return duct connected to the furnace NOTE Ductwork must never be attached to the back of the furnace For installations requiring more than 1800 CFM use a bottom return...

Страница 25: ...er mainte nance with the building owner Filters do not ship with this furnace but must be provided by the installer Filters must com ply with UL900 or CAN ULCS111 standards If the furnace is installed...

Страница 26: ...ized on low heat speed following a fixed thirty second blower on delay Electronic air cleaner terminals are energized with circulator blower Furnace is now operating in low stage heating mode Furnace...

Страница 27: ...are energized Circulator blower runs integrated control module monitors safety circuits continuously R and G thermostat contacts open completing the call for fan Circulator blower is de energized Ele...

Страница 28: ...VALVE PRESSURE REGULATOR CAUTION The line pressure supplied to the gas valve must be within the range specified below The supply pressure can be measured at the gas valve inlet pressure boss or at a h...

Страница 29: ...he gas piping drip leg See Honeywell VR9205 gas valve figure or White Rodgers 36G54 gas valve figure for location of inlet pressure boss NOTE If measuring gas pressure at the drip leg or Honeywell VR9...

Страница 30: ...at outlet pressure boss plug Honeywell valve or screw White Rodgers valve Bubbles forming indicate a leak SHUT OFF GAS AND REPAIR ALL LEAKS IMMEDIATELY 8 Measure the gas manifold pressure with burner...

Страница 31: ...c 3 5 w c Propane Low Stage 5 7 6 3 w c 6 0 w c High Stage 9 7 10 3 w c 10 0 w c Manifold Gas Pressure Gas GAS INPUT RATE MEASUREMENT NATURAL GAS ONLY The gas input rate to the furnace must never be g...

Страница 32: ...te for the applicable Specification Sheet referred to in this manual 3 Relocate desired motor leads to the circulator blower heat and cool speed terminals on the integrated control module Terminals ar...

Страница 33: ...er door The auxiliary limit control is designed to pre vent furnace operation in case of main blower failure on hori zontal installations It may also open if the power supply is interrupted while the...

Страница 34: ...ng any ungrounded object DIAGNOSTIC CHART Refer to the troubleshooting chart in the Appendix for assis tance in determining the source of unit operational problems The red diagnostic LED blinks to ass...

Страница 35: ...rack in an upright upflow installation follow the directions provided with external filter rack kit For further details see your distributor INDUCED DRAFTAND CIRCULATORBLOWER MOTORS The bearings in th...

Страница 36: ...peration Review the Owner s Manual with the homeowner and discuss proper furnace operation and maintenance Leave literature packet near furnace REPAIR AND REPLACEMENT PARTS When ordering any of the li...

Страница 37: ...switch contacts sticking Shorts in pressure switch circuit Inspect pressure switch hose Repair if neces sary Inspect flue for blockage proper length elbows and termination Correct pressure switch setp...

Страница 38: ...heck flue and air inlet piping for blockage proper length elbows and termination Correct as necessary Check rollout limit Replace if necessary Check induced draft blower for proper performance Replace...

Страница 39: ...and blue wires connected to transformer Turn power OFF prior to repair Normal operation LED is steady on STEADY Furnace not operating Integrated control module diagnostic LED is flashing EIGHT 8 flas...

Страница 40: ...85 766 743 730 709 683 666 604 HIGH 4 0 2051 1983 1895 35 1812 37 1725 39 1627 1530 1439 M H S 80904B MED 3 5 1736 38 1708 39 1652 40 1611 41 1540 43 1475 1394 1307 MEDIUM MED LO 3 0 1493 45 1668 40 1...

Страница 41: ...4 0 5 Model Heating Speed As Shipped Motor Speed EXTERNAL STATIC PRESSURE Inches Water Column 0 6 Tons AC at 0 5 0 6 0 7 0 8 ESP CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM HIGH 3 0 1353...

Страница 42: ...7 37 2297 37 2224 38 2106 40 2014 42 1896 1813 1669 Notes Temperature rise data is based on 2nd stage heat First stage heat is 75 of rise indicated above INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPE...

Страница 43: ...ARTS MUST BE USED WHEN SERVICING 1 SET HEAT ANTICIPATOR ON ROOM THERMOSTAT AT 0 7 AMPS BLOWER PRIMARY LIMIT WH GR BK IGNITER SURFACE HOT PU RD 15 PIN PLUG C NO SWITCH PRESSURE BR SENSOR FLAME BK WH RO...

Страница 44: ...agram on the unit for the most up to date wiring M D H S8 WIRING DIAGRAM HIGH VOLTAGE D ISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT M ULTIPLE POWER SOURCES MAY BE PRESENT F AILURE TO...

Страница 45: ...WHITE PU TO 115VAC 1 60 HZ POWER SUPPLY WITH OVERCURRENT PROTECTION DEVICE JUNCTION BOX SWITCH LINE H DOOR L GND LINE N DISCONNECT N SWITCH TEMP FIELD SPLICE SWITCH PRESS PROT DEVICE OVERCURRENT EQUI...

Страница 46: ...HES PRESSURESWITCHSTUCKOPEN 2FLASHES PRESSURESWITCHSTUCKCLOSED STEADYON NORMALOPERATION OFF CONTROLFAILURE 5 1FLASH 0 1 2 3 4 PU 6FLASHES OPENROLLOUTOROPENFUSE COLORCODES PUPURPLE OR ORANGE YL YELLOW...

Страница 47: ...R ORANGE YL YELLOW 6 7 8 BKBLACK GRGREEN BRBROWN PKPINK RD RED GYGRAY BLBLUE WH WHITE PU OVERCURRENTPROTECTIONDEVICE JUNCTIONBOX MUSTBE WARNING SWITCH WIRINGTOUNIT BEFORESERVICING DISCONNECTPOWER LINE...

Страница 48: ...s are designed and manufactured with the same high quality standards regardless of size or effi ciency We have designed these units to significantly reduce the most frequent causes of product failure...

Отзывы: