PRODUCT DESIGN

GPH13 (M Series) Package Units are designed for outdoor
installations only in either residential or light commercial ap-
plications and are available in 2, 2.5, 3, 3.5, 4 & 5 ton sizes.
They are designed for 208/230 volt single phase applications.

The connecting ductwork (Supply and Return) can be con-
nected for either horizontal or vertical airflow.  In the vertical
application, a matching Roof Curb is recommended and a
horizontal duct cover kit is required.

A return air filter must be installed behind the return air grille(s)
or provision must be made for a filter in an accessible loca-
tion within the return air duct. The minimum filter area should
not be less than those sizes listed in the Specification Sec-
tion. Under no circumstances should the unit be operated
without return air filters.

A 3/4" pipe is provided for removal of condensate water from
the indoor coil. A trap must be provided to have proper con-
densate drainage. (Do not reduce the drain line size).

Refrigerant flow control is achieved by use of restrictor ori-
fices.

All heat pump models also have a suction line accumulator
installed between the reversing valve and the compressor.
The object of the accumulator is to:

1. Provide a liquid refrigerant storage vessel during prolonged

system off cycles.

2. Store excess liquid refrigerant not needed by the system

while running.

3. Return oil and saturated vapor to the compressor at a

controlled rate.

4. Retain stored excess refrigerant during a sudden system

pressure fluctuation such as seen in defrost cycles.

Refrigerant flow control is achieved by use of restrictor
orifices. These models use the FasTest Access Fitting
System, with a saddle that is either soldered to the suction
and liquid lines or is fastened with a locking nut to the access
fitting box (core) and then screwed into the saddle.

 Do not

remove the core from the saddle until the refrigerant
charge has been removed. Failure to do so could result
in property damage or personal injury.

The single phase units use permanent split capacitor (PSC)
design compressors. Starting components are not required
for these units. A low microfarad run capacitor assists the
compressor to start and remains in the circuit during opera-
tion.

The outdoor fan motors are single phase capacitor type mo-
tors. Some models use PSC type indoor blower motors while
others use EEM type blower motors. EEM motors are ener-
gized by a 24V signal from the thermostat and are constant
torque motors with very low power consumption.

The EEM features an integral control module.

Air for condensing (cooling cycle) or evaporation (heating
cycle) is drawn through the outdoor coil by a propeller fan,
and is discharged vertically out the top of the unit. The out-
door coil is designed for .0 static. No additional restriction
(ductwork) shall be applied.

Conditioned air is drawn through the filter(s), field installed,
across the coil and back into the conditioned space by the
indoor blower.

Package Heat Pump indoor sections are designed to accept
optional components such as auxiliary electric heaters and
circuit breakers. Provisions for these components have been
made at time of manufacture.

GPH13 series package units use the Compliant Scroll com-
pressor; there are a number of design characteristics which
are different from the traditional reciprocating compressor.

- Due to their design Scroll compressors are inherently more
tolerant of liquid refrigerant. 

NOTE

: Even though the com-

pressor section of a Scroll compressor is more tolerant of
liquid refrigerant, continued flood back or flooded start condi-
tions may wash oil from the bearing surfaces causing prema-
ture bearing failure.

- These Scroll compressors use "POE" or polyolester oil which
is NOT compatible with mineral oil based lubricants like 3GS.
"POE" oil must be used if additional oil is required.

- Compliant scroll compressors perform “quiet” shutdowns
that allow the compressor to restart immediately without the
need for a time delay. This compressor will restart even if the
system has not equalized.

- Operating pressures and amp draws may differ from stan-
dard reciprocating compressors. This information may be
found in the “Cooling Performance Data” section.

Location and Clearances

NOTE: 

To ensure proper condensate drainage, unit must be

installed in a level position.

Содержание GPH 13 M Series

Страница 1: ...Series Multi Position Package Heat Pump Units with R410A RT6332013r1 November2010 This manual is to be used by qualified professionally trained HVAC technicians only Goodman does not assume any respon...

Страница 2: ...re a license to install or service heating and air conditioning equipment WARNING WARNING WARNING WARNING G P H 13 36 M 4 1 A A PRODUCT TYPE Package Unit PRODUCT FAMILY H Heat Pump PRODUCT SERIES 13 U...

Страница 3: ...ow these regulations may harm the environment and can lead to the imposition of substantial fines These regulations may vary by jurisdiction Should questions arise contact your local EPA office WARNIN...

Страница 4: ...ompressors Starting components are not required for these units A low microfarad run capacitor assists the compressor to start and remains in the circuit during opera tion The outdoor fan motors are s...

Страница 5: ...ordinances or in their absence with the latest edition of the Uniform Mechanical Code Section 305 NOTE Unit can also use roof curb and platform for leveling where necessary to utilize bottom discharg...

Страница 6: ...60 60 9 50 32 400 GPH1330M41 HKR05A CA 24 27 30 30 4 75 16 200 HKR08A CA 34 39 40 40 7 0 23 800 HKR10A CA 45 52 60 60 9 5 32 400 HKR15A CA 45 52 60 60 22 25 30 30 14 25 48 600 GPH1336M41 HKR05A CA 24...

Страница 7: ...30M41 GPH1336M41 GPH1342M41 LARGE CHASSIS GPH1348M41 GPH1360M41 BLOWER ACCESS PANEL 2 34 51 47 SUPPLY 1 3 8 A RETURN POWER WIRE ENTRANCE 4 1 8 2 1 8 6 16 16 5 B B CONTROL WIRE ENTRANCE CONDENSATE DRAI...

Страница 8: ...RCURRENT PROTECTION 1 30 35 40 COMPRESSOR TYPE SCROLL SCROLL SCROLL RATED LOAD AMPS 12 8 16 0 16 7 LOCKED ROTOR AMPS 58 3 77 79 CONDENSER HORSEPOWER 1 4 1 4 1 4 FAN MOTOR RPM 830 830 830 FULL LOAD AMP...

Страница 9: ...NT PROTECTION 1 40 50 60 COMPRESSOR TYPE SCROLL SCROLL SCROLL RATED LOAD AMPS 17 9 21 8 26 4 LOCKED ROTOR AMPS 112 117 134 CONDENSER HORSEPOWER 1 4 1 4 1 4 FAN MOTOR RPM 1075 1075 1075 FULL LOAD AMPS...

Страница 10: ...GPC13MED102 Downflow Economizer For A C Medium Chassis GPC13MED103 Downflow Economizer For A C Large Chassis GPH13MED102 Downflow Economizer For Heat Pump Medium Chassis GPH13MED103 Downflow Economize...

Страница 11: ...382 363 330 CFM 1521 1454 1388 1311 1230 1144 1055 939 WATTS 534 521 510 490 477 461 442 420 CFM 1122 1078 1032 972 915 804 687 558 WATTS 338 330 321 310 300 283 264 250 CFM 1387 1331 1264 1209 1119...

Страница 12: ...100 130 140 150 100 90 80 70 60 50 40 30 20 10 OUTPUT BTU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULAS BTU...

Страница 13: ...24 8 26 6 21 1 21 8 23 6 25 3 19 6 20 2 21 8 23 4 S T 0 88 0 78 0 59 0 38 0 91 0 81 0 61 0 40 0 93 0 83 0 63 0 41 0 96 0 86 0 65 0 42 1 00 0 89 0 68 0 43 1 00 0 90 0 68 0 44 Delta T 21 19 16 11 21 19...

Страница 14: ...26 244 257 268 254 273 289 301 289 311 328 342 329 354 374 390 370 398 421 439 409 440 465 485 LO PR 110 117 128 136 117 124 135 144 121 129 141 150 127 135 148 157 133 142 155 165 138 147 160 171 MBh...

Страница 15: ...2 2 25 5 26 3 28 5 30 5 23 7 24 4 26 4 28 3 S T 0 88 0 78 0 59 0 38 0 91 0 81 0 61 0 40 0 93 0 83 0 63 0 41 0 96 0 86 0 65 0 42 1 00 0 89 0 68 0 43 1 00 0 90 0 68 0 44 Delta T 20 18 15 10 20 18 15 10...

Страница 16: ...227 244 258 269 255 274 290 302 290 312 329 344 330 355 375 391 371 400 422 440 410 442 466 486 LO PR 107 113 124 132 113 120 131 139 117 125 136 145 123 131 143 152 129 137 150 159 133 142 155 165 MB...

Страница 17: ...8 4 30 5 31 4 34 0 36 4 28 2 29 1 31 5 33 8 S T 0 84 0 75 0 57 0 37 0 87 0 78 0 59 0 38 0 89 0 80 0 60 0 39 0 92 0 82 0 62 0 40 0 95 0 85 0 65 0 42 0 96 0 86 0 65 0 42 Delta T 21 19 16 11 21 19 16 11...

Страница 18: ...33 250 264 276 261 281 297 309 297 319 337 352 338 364 384 401 380 409 432 451 420 452 477 498 LO PR 110 117 127 136 116 123 134 143 120 128 140 149 126 134 147 156 132 141 154 164 137 146 159 169 MBh...

Страница 19: ...44 4 35 2 36 3 39 3 42 1 32 6 33 6 36 4 39 0 S T 0 83 0 74 0 56 0 36 0 86 0 77 0 58 0 38 0 88 0 79 0 60 0 39 0 91 0 82 0 62 0 40 0 95 0 85 0 64 0 41 0 96 0 86 0 65 0 42 Delta T 21 19 16 11 21 19 16 11...

Страница 20: ...222 239 253 264 249 268 284 296 284 305 322 336 323 348 367 383 364 391 413 431 402 432 456 476 LO PR 104 110 120 128 110 117 127 135 114 121 132 141 120 127 139 148 125 133 146 155 130 138 151 160 MB...

Страница 21: ...1 6 41 0 42 2 45 6 49 0 37 9 39 1 42 3 45 4 S T 0 90 0 81 0 61 0 39 0 94 0 84 0 63 0 41 0 96 0 86 0 65 0 42 0 99 0 89 0 67 0 43 1 00 0 92 0 70 0 45 1 00 0 93 0 70 0 45 Delta T 20 18 15 10 20 19 15 11...

Страница 22: ...236 254 268 279 264 285 301 313 301 324 342 356 343 369 389 406 385 415 438 457 426 458 484 505 LO PR 106 113 124 132 112 120 131 139 117 124 136 145 123 131 143 152 129 137 149 159 133 142 155 165 MB...

Страница 23: ...2 1 49 3 50 8 55 0 59 0 45 7 47 0 50 9 54 6 S T 0 83 0 74 0 56 0 36 0 86 0 77 0 58 0 38 0 88 0 79 0 60 0 39 0 91 0 82 0 62 0 40 0 95 0 85 0 64 0 41 0 96 0 85 0 65 0 42 Delta T 21 19 16 11 21 20 16 11...

Страница 24: ...36 255 269 280 265 286 302 315 302 325 343 358 344 370 391 407 387 416 439 458 427 460 486 506 LO PR 103 110 120 128 109 116 127 135 114 121 132 141 119 127 139 148 125 133 145 155 129 138 150 160 MBh...

Страница 25: ...6 7 0 KW 2 74 2 68 2 63 2 58 2 55 2 53 2 48 2 43 2 29 2 24 2 19 2 17 2 15 2 10 2 05 2 00 1 95 1 90 AMPS 13 6 12 7 12 0 11 4 11 1 10 9 10 4 9 9 9 6 9 2 8 9 8 7 8 6 8 2 7 8 7 5 7 0 6 5 COP 3 87 3 74 3...

Страница 26: ...6 KW 3 90 3 83 3 75 3 68 3 63 3 60 3 53 3 46 2 48 2 43 2 38 2 36 2 34 2 29 2 24 2 19 2 14 2 09 AMPS 19 0 17 7 16 7 15 8 15 3 15 0 14 3 13 7 13 1 12 6 12 1 11 9 11 8 11 2 10 6 10 1 9 5 8 7 COP 4 29 4 1...

Страница 27: ...LOW VOLTAGE DEFROST RELAY LOW VOLTAGE JUNCTION BOX FEMALE PLUG CONNECTOR REVERSING VALVE COIL RUN CAPACITOR FOR COMPRESSOR AND FAN START ASSIST TRANSFORMER WIRE CODE BK BLACK BL BLUE BR BROWN GR GREE...

Страница 28: ...NNECTOR REVERSING VAVLE COIL RUN CAPACITOR FOR COMPRESSOR AND FAN START ASSIST TRANSFORMER HIGH PRESSURE SWITCH WIRE CODE BK BLACK BL BLUE BR BROWN GR GREEN OR ORANGE PU PURPLE RD RED WH WHITE YL YELL...

Отзывы: