25
HEATING PERFORMANCE DATA
GPH13[24-42]M41*
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1.
As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low
and high side pressures and power will not change.
2.
As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will
occur in low and high side pressures and power.
A properly operating unit should be within plus or minus
3 degrees
of the typical (
Delta T
) value shown.
A properly operating unit should be within plus or minus
7 PSIG
of the
HI PR
shown.
A properly operating unit should be within plus or minus
3 PSIG
of the
LO PR
shown.
A properly operating unit should be within plus or minus
3 Amps
of the typical value shown.
EXPANDED PERFORMANCE DATA
MODEL: GPH1324M41*
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
28.9
27.4
25.8
24.1
23.0
22.3
20.7
19.1
16.7
15.4
14.2
13.4
12.9
11.6
10.3
9.0
7.6
6.3
Delta T
32.4
30.7
28.9
27.0
25.8
25.0
23.2
21.4
18.8
17.3
15.9
15.1
14.5
13.0
11.5
10.1
8.6
7.0
KW
2.14
2.10
2.06
2.01
1.99
1.97
1.94
1.89
2.32
2.26
2.21
2.18
2.16
2.10
2.05
2.00
1.95
1.89
AMPS
10.4
9.8
9.2
8.8
8.5
8.4
8.0
7.7
7.4
7.1
6.9
6.7
6.7
6.4
6.1
5.8
5.5
5.1
COP
3.96
3.82
3.67
3.50
3.38
3.30
3.13
2.95
2.11
1.99
1.88
1.80
1.75
1.61
1.47
1.31
1.15
0.97
EER
13.5
13.1
12.5
12.0
11.5
11.3
10.7
10.1
7.2
6.8
6.4
6.2
6.0
5.5
5.0
4.5
3.9
3.3
HI PR
379
364
350
334
326
320
308
295
283
270
260
253
249
239
230
221
213
205
LO PR
135
126
118
108
102
98
90
80
73
65
57
53
51
43
37
31
27
22
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
MODEL: GPH1330M41*
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
36.2
34.3
32.3
30.2
28.8
27.9
25.9
23.9
21.2
19.6
18.0
17.0
16.4
14.7
13.0
11.4
9.7
7.9
Delta T
31.9
30.2
28.4
26.6
25.4
24.6
22.9
21.1
18.7
17.3
15.9
15.0
14.4
13.0
11.5
10.0
8.6
7.0
KW
2.74
2.68
2.63
2.58
2.55
2.53
2.48
2.43
2.29
2.24
2.19
2.17
2.15
2.10
2.05
2.00
1.95
1.90
AMPS
13.6
12.7
12.0
11.4
11.1
10.9
10.4
9.9
9.6
9.2
8.9
8.7
8.6
8.2
7.8
7.5
7.0
6.5
COP
3.87
3.74
3.59
3.42
3.30
3.23
3.06
2.88
2.71
2.55
2.40
2.30
2.23
2.05
1.86
1.66
1.46
1.22
EER
13.2
12.8
12.3
11.7
11.3
11.0
10.5
9.8
9.2
8.7
8.2
7.9
7.6
7.0
6.4
5.7
5.0
4.2
HI PR
375
359
346
330
323
316
304
292
280
267
256
250
246
236
227
218
210
203
LO PR
131
122
114
105
99
95
88
78
70
63
55
51
49
42
36
30
27
21
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
MODEL: GPH1336M41*
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
43.0
40.7
38.3
35.8
34.2
33.1
30.8
28.4
24.4
22.6
20.8
19.6
18.9
17.0
15.0
13.1
11.2
9.2
Delta T
34.6
32.8
30.8
28.8
27.5
26.7
24.8
22.9
19.7
18.2
16.7
15.8
15.2
13.6
12.1
10.6
9.0
7.4
KW
3.10
3.04
2.98
2.92
2.89
2.86
2.81
2.75
2.36
2.31
2.26
2.24
2.22
2.17
2.12
2.07
2.02
1.97
AMPS
15.4
14.4
13.6
12.9
12.5
12.3
11.7
11.1
10.7
10.3
9.9
9.7
9.6
9.2
8.7
8.3
7.8
7.2
COP
4.06
3.92
3.76
3.58
3.46
3.39
3.21
3.02
3.03
2.86
2.69
2.57
2.50
2.29
2.08
1.85
1.62
1.36
EER
13.9
13.4
12.8
12.2
11.8
11.6
11.0
10.3
10.4
9.8
9.2
8.8
8.5
7.8
7.1
6.3
5.5
4.6
HI PR
403
386
371
355
347
340
327
314
300
287
276
269
264
254
244
234
226
218
LO PR
137
127
119
109
103
99
91
81
73
66
58
54
52
44
38
32
28
22
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
MODEL: GPH1342M41*
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
-5
-10
MBh
50.3
47.6
44.8
41.9
40.0
38.8
36.0
33.2
27.5
25.4
23.4
22.1
21.3
19.1
16.9
14.8
12.6
10.3
Delta T
35.8
33.9
31.9
29.8
28.5
27.6
25.6
23.6
19.6
18.1
16.7
15.7
15.1
13.6
12.0
10.5
9.0
7.3
KW
3.58
3.52
3.45
3.38
3.34
3.31
3.25
3.18
2.31
2.27
2.23
2.20
2.18
2.14
2.09
2.05
2.01
1.96
AMPS
17.6
16.5
15.6
14.8
14.3
14.1
13.4
12.8
12.3
11.9
11.4
11.2
11.1
10.6
10.0
9.6
9.0
8.3
COP
4.11
3.96
3.80
3.62
3.50
3.42
3.24
3.05
3.48
3.27
3.07
2.94
2.85
2.61
2.36
2.11
1.84
1.54
EER
14.0
13.5
13.0
12.4
12.0
11.7
11.1
10.4
11.9
11.2
10.5
10.0
9.7
8.9
8.1
7.2
6.3
5.3
HI PR
323
310
298
285
278
273
262
252
241
230
221
216
212
204
196
188
181
175
LO PR
141
131
122
112
106
102
94
84
75
67
59
55
53
45
39
33
29
22
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.