26
HEATING PERFORMANCE DATA
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1.
As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low
and high side pressures and power will not change.
2.
As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will
occur in low and high side pressures and power.
A properly operating unit should be within plus or minus
3 degrees
of the typical (
Delta T
) value shown.
A properly operating unit should be within plus or minus
7 PSIG
of the
HI PR
shown.
A properly operating unit should be within plus or minus
3 PSIG
of the
LO PR
shown.
A properly operating unit should be within plus or minus
3 Amps
of the typical value shown.
GPH13[48-60]M41*
EXPANDED PERFORMANCE DATA
MODEL: GPH1348M41*
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
-5
-10
MBh
57.2
54.1
51.0
47.6
45.5
44.1
41.0
37.8
32.8
30.2
27.8
26.3
25.3
22.7
20.1
17.6
15.0
12.3
Delta T
30.8
29.1
27.4
25.6
24.5
23.7
22.0
20.3
17.6
16.3
15.0
14.2
13.6
12.2
10.8
9.5
8.1
6.6
KW
3.90
3.83
3.75
3.68
3.63
3.60
3.53
3.46
2.48
2.43
2.38
2.36
2.34
2.29
2.24
2.19
2.14
2.09
AMPS
19.0
17.7
16.7
15.8
15.3
15.0
14.3
13.7
13.1
12.6
12.1
11.9
11.8
11.2
10.6
10.1
9.5
8.7
COP
4.29
4.14
3.97
3.79
3.66
3.58
3.39
3.20
3.86
3.64
3.42
3.27
3.17
2.91
2.63
2.35
2.05
1.72
EER
14.7
14.1
13.6
13.0
12.5
12.2
11.6
10.9
13.2
12.4
11.7
11.2
10.8
9.9
9.0
8.0
7.0
5.9
HI PR
372
357
343
328
320
314
302
290
278
265
255
249
244
235
226
217
209
202
LO PR
130
121
113
104
98
95
87
77
70
62
55
51
49
42
36
30
26
21
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
MODEL: GPH1360M41*
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
-5
-10
MBh
69.8
66.0
62.2
58.1
55.5
53.8
50.0
46.1
39.1
36.1
33.3
31.4
30.3
27.1
24.1
21.0
17.9
14.7
Delta T
35.9
34.0
32.0
29.9
28.5
27.7
25.7
23.7
20.1
18.6
17.1
16.2
15.6
14.0
12.4
10.8
9.2
7.5
KW
4.80
4.71
4.62
4.53
4.47
4.44
4.35
4.26
2.41
2.36
2.32
2.30
2.28
2.24
2.20
2.16
2.12
2.08
AMPS
24.1
22.5
21.2
20.1
19.4
19.1
18.1
17.3
16.7
16.0
15.4
15.0
14.9
14.2
13.4
12.8
12.0
11.0
COP
4.25
4.10
3.94
3.76
3.63
3.55
3.36
3.17
4.76
4.47
4.19
4.00
3.88
3.54
3.20
2.84
2.47
2.06
EER
14.5
14.0
13.5
12.8
12.4
12.1
11.5
10.8
16.3
15.3
14.3
13.7
13.2
12.1
10.9
9.7
8.4
7.1
HI PR
385
369
354
339
331
325
312
300
287
274
263
257
252
243
233
224
216
208
LO PR
134
124
116
107
101
97
89
80
72
64
56
52
50
43
37
31
27
21
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.