background image

15

they rotate freely. Check for bolts and screws that may 

have jarred loose during shipment to the job site. Re-

tighten if necessary. Re-tighten all electrical connections.

f

IEld

 d

Uct

 c

onnEctIonS

Verify that all duct connections are tight and that there is no 

air bypass between supply and return.

P

RE

-

StaRtUP

 P

REcaUtIonS

 

It is important to your safety that the unit has been properly 

grounded during installation. Check  ground lug connection 

in main control box for tightness prior to closing circuit 

breaker or disconnect switch. Verify that supply voltage 

on line side of disconnect agrees with voltage on unit 

identification plate and is within the  utilization voltage 

range as indicated in Appendix B Electrical Data.

System Voltage - 

That nominal voltage value assigned 

to a circuit or system for the purpose of designating its 

voltage class.

Nameplate Voltage - 

That voltage assigned to a piece of 

equipment for the purpose of designating its voltage class 

and for the purpose of defining the minimum and maximum 

voltage at which the equipment will operate. 

Utilization Voltage - 

The voltage of the line terminals 

of the equipment at which the equipment must give fully 

satisfactory performance. Once it is established that supply 

voltage will be maintained within the utilization range under 

all system conditions, check and calculate if an unbalanced 

condition exists between phases. Calculate percent voltage 

unbalance as follows. 

AIR FLOW ADJUSTMENTS

When the final adjustments are complete, the current 

draw of the motor should be checked and compared to 

the full load current rating of the motor. The amperage 

must not exceed the service factor stamped on the motor 

nameplate. The total airflow must not be less than that 

required for operation of the furnace.

If an economizer is installed, check the unit operating 

balance with the economizer at full outside air and at 

minimum outside air.

notE: n

EvER

 

RUn

 

HIGH

 

StaGE

 cfM 

bEloW

 300 cfM 

PER

 

ton

 

EvaPoRatoR

 

fREEZInG

 

oR

 

PooR

 

UnIt

 

PERfoRMancE

 

IS

 

PoSSIblE

.

EEM - S

tandaRd

 S

tatIc

 d

RIvE

 M

otoR

Adjust the CFM for the unit by changing the position of 

the low voltage leads on the terminal block TB1. Refer to 

Appendix A for blower performance at each speed tap. 

Refer to Appendix D for maximum and minimum allowed 

airflow for heating and cooling.

notE: I

f

 

MoRE

 

tHan

 

onE

 

lEad

 

IS

 

EnERGIZEd

 

SIMUltanEoUSly

tHE

 

MotoR

 

WIll

 

RUn

 

at

 

tHE

 

HIGHER

 

SPEEd

.

Fan speed for G (Fan), Y1 (Low Cool) are fixed setting on 

TB1/T1 and cannot be moved.  

Fan speed for W1 (Low Heat) is fixed setting on TB1/T2 

and cannot be moved.

Purple wire Y2 (High Cool) and Brown wire W2 (High Heat) 

are connected to TB1/T3. These wires can be moved 

together or separately and placed on unoccupied terminal 

T4 or T5.

n

otE

foR

 

PRoPER

 

oPERatIon

 y2 

and

 W2 

SHoUld

 

HavE

 

a

 

HIGHER

 

SPEEd

 

SEttInG

 

tHan

 

tHE

 G, y1 

and

 W1 

SPEEd

 

SEttInG

.

For gas heat units, the airflow must be adjusted so that the 

air temperature rise falls within the ranges given stated on 

Data Plate.

E

lEctRIcal

 I

nPUt

 c

HEck

Make preliminary check of evaporator fan ampere draw 

and verify that motor nameplate amps are not exceeded. A 

final check of amp draw should be made upon completion 

of air balancing of the duct system (see Appendix B).

GAS SYSTEM CHECK

P

RE

-o

PERatIon

 c

HEckS

1.  Close the manual gas valve external to the unit.

2.  Turn off the electrical power supply to the unit.

3.  Change heating setpoint to its lowest possible setting.

4.  Remove the heat exchanger door on the side of the 

unit by removing screws.

5.  This unit is equipped with an ignition device which 

automatically lights the main burner. DO NOT try to 

light burner by any other method.

6.  Move the gas control valve switch to the OFF position.

7. 

Wait five minutes to clear out any gas.

8.  Smell for gas, including near the ground. This is 

important because some types of gas are heavier 

than air. If you have waited five minutes and you do 

smell gas, immediately follow the warning WHAT TO 

DO IF YOU SMELL GAS on page 2 of this manual. 

If having waited for five minutes and no gas smell is 

noted, move the gas control valve switch to the ON 

position.

9.  Replace the heat exchanger door on the side of the 

unit.

10. Open the manual gas valve external to the unit.

11. Turn on the electrical power supply to the unit.

12. Change heating setpoint to desired setting.

Содержание GPG16 M Series

Страница 1: ...ING This forced air central unit design complies with requirements embodied in The American National Standard National Standard of Canada ANSI Z21 47 CSA 2 3 Gas fired central furnaces WARNING PROP 65...

Страница 2: ...any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot...

Страница 3: ...ese installation and operating instructions all local building codes and ordinances or in their absence with the latest edition of the National Fuel Gas Code NFPA54 ANSI Z223 1 and National Standard o...

Страница 4: ...g material according to local codes Pre Installation Checks Carefully read all instructions for the installation prior to installing unit Ensure each step or procedure is understood and any special co...

Страница 5: ...ngs building openings or openable windows must be maintained in accordance with the latest edition of the National Fuel Gas Code ANSI Z223 1 NFPA 54 Minimum horizontal clearance of 48 from the furnace...

Страница 6: ...ir into the unit fresh air intake NOTE If the 36 minimum clearance is used on the control panel side of unit a flue extension kit needs be to installed to prevent flue gas recirculation See table belo...

Страница 7: ...the unit must not be less than 60 Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables Spreader bars must be of sufficient length so that cables do not come in...

Страница 8: ...ng from sharp edges follow national electrical code and all local codes and ordinances Do not route wires through removable access panels CAUTION Conduit and fittings must be weather tight to prevent...

Страница 9: ...k connections control box note depending on the options installed the location of the components may vary in some models WARNING Failure of unit due to operation on improper line voltage or with exces...

Страница 10: ...efer to unit wiring diagrams for thermostat or remote sensor connections GAS SUPPLY PIPING WARNING To prevent personal injury or death due to improper installation adjustment alteration service or mai...

Страница 11: ...threads only Pipe joint compound must be resistant to the action of the fuel used 3 Use ground joint unions 4 Install a drip leg to trap dirt and moisture before it can enter the gas valve The drip le...

Страница 12: ...to convert units to propane gas NOx screens must be removed before converting to LP Remove burner assembly and pull NOx screens from each burner tube When all the screens are out reassemble the burner...

Страница 13: ...supply gas pressure is less than 11 0 w c or greater than 13 0 w c 6 All pipe connections should be sealed with a pipe thread compound which is resistant to the fuel used with the furnace A soapy wat...

Страница 14: ...Checks procedure provides a step by step sequence which if followed will assure the proper startup of the equipment in the minimum amount of time Air balancing of duct system is not considered part o...

Страница 15: ...Motor Adjust the CFM for the unit by changing the position of the low voltage leads on the terminal block TB1 Refer to Appendix A for blower performance at each speed tap Refer to Appendix D for maxi...

Страница 16: ...16 Wiring Example...

Страница 17: ...rmal manifold pressure for High fire is 3 5 w c on natural gas and 10 0 w c for propane gas Low fire natural gas 2 0 w c 6 0 w c low fire propane gas Minimum gas supply pressure is 5 0 w c for natural...

Страница 18: ...Gas Only Check It is the responsibility of the contractor to adjust the gas input to the unit To measure the gas input use a gas meter and proceed as follows 1 Turn off gas supply to all other applian...

Страница 19: ...speed will lower the temperature rise A slower blower speed will increase the temperature rise NOTE Blower speed MUST be set to give the correct air temperature rise through the unit as marked on the...

Страница 20: ...prior to resetting this manual reset control WARNING To avoid property damage personal injury or death due to fire or explosion a qualified servicer must investigate the reason for the rollout protec...

Страница 21: ...the compressor control circuits will be ready to respond to a subsequent call for cooling Refrigeration Performance Check Check that compressor RLA corresponds to values shown in Appendix B RLA draw c...

Страница 22: ...remove the filter access panel on return side of the unit Cabinet Finish Maintenance Use a fine grade automotive wax on the cabinet finish to maintain the finish s original high luster This is especi...

Страница 23: ...dicates an internal fault check power supply to unit for proper voltage check all fuses circuit breakers and wiring Disconnect electric power for five seconds If LED remains off after restoring power...

Страница 24: ...ce 4 FLASH CODE If the primary limit switch opens the gas valve is immediately deenergized the induced draft and air circulating blowers are energized The induced draft and air circulator blowers rema...

Страница 25: ...62 859 0 62 0 2 1901 912 0 66 0 4 1787 909 0 66 0 4 1824 966 0 70 0 6 1702 955 0 69 0 6 1737 1014 0 73 0 8 1625 1005 0 73 0 8 1658 1067 0 77 0 2 2132 954 0 91 0 2 2175 1014 0 97 0 4 2056 993 0 95 0 4...

Страница 26: ...4 70 0 70 0 7 2 6 5 50 6 49 9 70 0 70 0 Power Supply Model Number Electrical Rating Compressor Outdoor Fan Motor Indoor Fan Motor Optional Electric Heat Optional Powered Convienience Outlet FLA Optio...

Страница 27: ...CURB LOCATION EMBOSS FOR THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal...

Страница 28: ...28 APPENDIX D MIN MAX AIRFLOW UNIT HEAT RANGE HIGH FIRE RATE BTU HR HEATING MINIMUM SCFM COOLING MINIMUM SCFM MAXIMUM SCFM GPG1660140M41 HIGH 140 000 1615 1500 2500 AIR FLOW RANGE FOR HIGH STAGE...

Страница 29: ...RD YL YL BL VMC A1 A2 LS RD RD BK BK YL YL BK BK PU PU BK BK RS BK BK BK BK LPS ALS GAS PLM GAS PLF GR GY PU PU BL BR TN PU PU PU BL BR TN VM L1 L2 T1 T2 VMC F3 F3 FB3 4 BK RD PK BL BR GR YL WH PU GR...

Страница 30: ...30...

Страница 31: ...31...

Страница 32: ...o the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty regis...

Отзывы: