Goodman GPG13 Скачать руководство пользователя страница 8

8

WARNING

T

O PREVENT PROPERTY DAMAGE OR SERIOUS PERSONAL INJURY DUE TO

FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS

DETECTING WARNING DEVICE.

I

F THE PROPANE GAS UNIT IS INSTALLED IN AN EXCAVATED AREA OR A 

CONFINED SPACE, A WARNING DEVICE IS REQUIRED DUE TO:

• 

P

ROPANE GAS IS HEAVIER THAN AIR AND ANY LEAKING GAS CAN

  SETTLE IN ANY LOW AREAS OR CONFINED SPACES. 

• 

P

ROPANE GAS ODORANT MAY FADE,  MAKING  THE GAS UNDETECTABLE

  EXCEPT WITH A WARNING DEVICE.

ELECTRICAL WIRING

T

HERMOSTAT

 L

OCATION

Mount the thermostat approximately five feet above the floor,
in an area that has an inside, vibration-free wall  and has good
air circulation.
Movement of air must not be obstructed by furniture, door,
draperies, etc. The thermostat must not be mounted where it
will be affected by drafts, hot or cold water pipes or air ducts in
walls, radiant heat from fireplace, lamps, the sun, television,
etc. Consult the Instruction Sheet packaged with thermostat
for mounting instructions.
All units have one stage of heating and one stage of
mechanical cooling. Units which will have economizers may
use thermostats with one or two stages of cooling.
*PG1360***1A ONLY: These models have two stages of
mechanical cooling. A 1-stage heat, 2-stage cooling
thermostat is recommended for these models.

The units are designed for operation on 60 hertz current and
at voltages as shown on the rating plate. All internal wiring in
the unit is complete. It is necessary to bring in the power supply
to the contactor as shown on the unit wiring diagram which is
supplied with each unit. 24 volt wiring must be connected
between the unit control panel and the room thermostat.

C

3

2

1

6

5

9

8

11

12

Y

R

4

7

10

G

W

G

W

Y

R

2

T1

C22

P2

P3

FUSE 3 AMP MAX

P1

12

1

7

4

4

5

3

3

6

9

FS

6

10

7

F1

11

8

11

10

12

9

K1

12

T2

BR

E

AK F

O

R

 T

W

O

 S

T

A

G

E

C

O

M

P

R

E

SSO

R

24V

A

C

 5

0

/60H

z 400m

A

 M

A

X

.

L1

DI

K2

L1

HE

A

T

UNUS

E

D

K4

K3

C

OOL

1 068

-83-

40

0 A

MO

D

E

L

1068-

400

B180

99-18

AN

S

Z

2

1.

2

0

 AU

T

O

M

A

T

IC

 I

G

N

IT

IO

N

 S

Y

ST

E

M

L2

L2

L2

L2

EC

O

N

120

135

150

S

P

E

E

D-

UP

LOW VOLTAGE

CONNECTOR

Low Voltage Wiring

T

ANKS

 

AND

 P

IPING

Complete information regarding tank sizing for vaporization,
recommended regulator settings and pipe sizing is available
from most regulator manufacturers and propane gas suppliers.
Since propane gas will quickly dissolve white lead or most
standard commercial compounds, special pipe dope must be
used. Shellac base compounds resistant to the actions of
liquefied petroleum gases such as Gasolac

®

, Stalactic

®

,

Clyde’s

®

 or John Crane

®

 are satisfactory.

See below for typical propane gas piping.

200 PSIG
Maximum

5 to 15 PSIG
(20 PSIG Max.)

Continuous

11" W.C.

Second Stage
Regulator

First Stage
Regulator

Typical Propane Gas Piping

Sizing Between First and Second Stage Regulator
Maximum Propane Capacities listed are based on 1 PSIG Pressure Drop at 10
PSIG Setting.  Capacities in 1,000 BTU/HR

3/8"

1/2"

5/8"

3/4"

7/8"

1/2"

3/4"

30

309

700

1,303

2,205

3,394

1,843

3,854

40

265

599

1,115

1,887

2,904

1,577

3,298

50

235

531

988

1,672

2,574

1,398

2,923

60

213

481

896

1,515

2,332

1,267

2,649

70

196

446

824

1,394

2,146

1,165

2,437

80

182

412

767

1,297

1,996

1,084

2,267

90

171

386

719

1,217

1,873

1,017

2,127

100

161

365

679

1,149

1,769

961

2,009

150

130

293

546

923

1,421

772

1,613

200

111

251

467

790

1,216

660

1,381

250

90

222

414

700

1,078

585

1,224

300

89

201

378

634

976

530

1,109

350

82

185

345

584

898

488

1,020

400

76

172

321

543

836

454

949

To convert to Capacities at 15 PSIG Settings -- Multiply by 1.130
To convert to Capacities at 5 PSIG Settings -- Multiply by 0.879

PIPE OR

TUBING

LENGTH,

FEET

NOMINAL PIPE SIZE,

SCHEDULE 40

TUBING SIZE, O.D., TYPE L

Sizing Between Single or Second Stage Regulator and Appliance*
Maximum Propane Capacities Listed are Based on 1/2" W.C. Pressure Drop at
11" W.C. Setting.  Capacities in 1,000 BTU/HR

3/8"

1/2"

5/8"

3/4"

7/8"

1/2"

3/4"

1"

1-1/4"

1-1/2"

10

49

110

206

348

539

291

608

1,146

2,353

3,525

20

34

76

141

239

368

200

418

788

1,617

2,423

30

27

61

114

192

296

161

336

632

1,299

1,946

40

23

52

97

164

253

137

284

541

1,111

1,665

50

20

46

86

146

224

122

255

480

985

1,476

60

19

42

78

132

203

110

231

436

892

1,337

80

16

36

67

113

174

94

198

372

764

1,144

100

14

32

59

100

154

84

175

330

677

1,014

125

12

28

52

89

137

74

155

292

600

899

150

11

26

48

80

124

67

141

265

544

815

200

10

22

41

69

106

58

120

227

465

697

250

9

19

36

61

94

51

107

201

412

618

300

8

18

33

55

85

46

97

182

374

560

350

7

16

30

51

78

43

89

167

344

515

400

7

15

28

47

73

40

83

156

320

479

*DATA IN ACCORDANCE WITH NFPA PAMPHLET NO. 54

NOMINAL PIPE SIZE,

SCHEDULE 40

TUBING SIZE, O.D., TYPE L

PIPE OR

TUBING

LENGTH,

FEET

Table 3 - Propane Gas Pipe Sizing

Содержание GPG13

Страница 1: ...Requirements Embodied in The American National Standard National Standard of Canada Shown Below ANSI Z21 47 CSA 2 3 Central Furnaces RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION ATTENTION INSTALLING...

Страница 2: ...11 HEATING 11 COOLING 11 FAN ONLY 12 Startup Adjustments and Checks 12 HEATING STARTUP 12 COOLING STARTUP 15 Troubleshooting 15 IGNITION CONTROL ERROR CODES 15 ABNORMAL OPERATION HEATING 16 ABNORMAL O...

Страница 3: ...L TO SHUT OFF TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY WARNING THIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH MAY CAUSE S...

Страница 4: ...the outdoor air i e combustion air for the unit will be frequently contaminated by compounds containing chlorine or fluorine Common sources of such compounds include swimming pool chemicals and chlor...

Страница 5: ...TION ELECTRIC SHOCK OR CARBON MONOXIDE THIS UNIT MUST BE PROPERLY INSTALLED REPAIRED OPERATED AND MAINTAINED This unit is approved for outdoor installation ONLY To assure that your unit operates safel...

Страница 6: ...TION AND OR EQUIPMENT DAMAGE HIGH ALTITUDE KITS ARE FOR U S INSTALLATIONS ONLY AND ARE NOT APPROVED FOR USE IN CANADA The rating plate is stamped with the model number type of gas and gas input rating...

Страница 7: ...E A MATCH OR OPEN FLAME TO TEST FOR LEAKS NEVER EXCEED SPECIFIED PRESSURES FOR TESTING HIGHER PRESSURE MAY DAMAGE GAS VALVE AND CAUSE OVERFIRING WHICH MAY RESULT IN PREMATURE HEAT EXCHANGE FAILURE THI...

Страница 8: ...acturers and propane gas suppliers Since propane gas will quickly dissolve white lead or most standard commercial compounds special pipe dope must be used Shellac base compounds resistant to the actio...

Страница 9: ...SI Z21 20 AUTOMATIC IGNITION SYSTEM L2 L2 L2 L2 ECON 120 135 150 SPEED UP LOW VOLTAGE CONNECTOR Y Y2 Low Voltage Wiring PG1360 1A Only Refer to the unit wiring diagram for electrical connections When...

Страница 10: ...onal Board of Fire Underwriters for the Installation of Air Conditioning Warm Air Heating and Ventilating Systems Pamphlets No 90A and 90B The supply duct from the unit through a wall may be installed...

Страница 11: ...lower will deenergize This allows any additional heat in the heat exchanger to be transferred to the conditioned space PG13 48 60 1A ONLY HEAT FAN OFF delay is fixed at 180 seconds Airflow level is 50...

Страница 12: ...lout protection device is located on the burner bracket The reason for elevated temperatures at the control should be determined and repaired prior to resetting this manual reset control WARNING TO AV...

Страница 13: ...gas being delivered to the unit 3 INPUT GAS HTG VALUE x 3600 SEC PER CUBIC FOOT Example Natural gas with a heating value of 1000 BTU per cubic foot and 34 seconds per cubic foot as determined by Step...

Страница 14: ...utward from the burner without curling floating or lifting off Temperature Rise Check Check the temperature rise through the unit by placing thermometers in supply and return air registers as close to...

Страница 15: ...does not operate Compressor Protection Devices The compressor includes components which are designed to protect the compressor against abnormal operating conditions WARNING TO PREVENT PERSONAL INJURY...

Страница 16: ...and carefully clean with steel wool Check wiring Check wiring for opens shorts and miswiring Important If you have to frequently reset your gas electric package unit it means that a problem exists th...

Страница 17: ...bris CONDENSER EVAPORATOR AND INDUCED DRAFT MOTORS Bearings on the air circulating blower motor condenser motor and the combustion fan motor are permanently lubricated No additional oiling is required...

Страница 18: ...rical power and gas supply CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION CAUTION ALWAYS VERIFY PROPER OPERATION AFTER...

Страница 19: ...Seconds 0 7 30 0 60 Circulator Blower Outdoor Fan and Compressor Thermostat ON OFF ON OFF ON OFF Legend PG10 12 24 60 PG1324 42 PG1348 60 100 50 Light Signal Refer to Abnormal Heating or Cooling Opera...

Страница 20: ...SUPPLY ENTRANCE CONDENSATE DRAIN CONNECTION 3 4 NPT FEMALE 16 1 8 19 1 8 EVAPORATOR CONTROL PANEL ACCESS PANEL 4 3 4 B 7 15 16 16 B 5 1 2 1 3 8 16 2 3 4 A 18 7 16 FLUE EXHAUST 51 47 BLOWER ACCESS PAN...

Страница 21: ...H OPTIONAL CONNECTED AT L1 L2 NOTE 4 B BL Y R FS R O R H C F Y BR CAP1 BL B PU 4 SPEED MOTOR ALS Y Y PS PU W G G W R BL Y Y PU R C Y Y2 Y1 Y BL 6 5 2 3 G 4 1 Y PU PL RS MV GAS VALVE MV GV PU W R BL GV...

Страница 22: ...ER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH B4312003 REV B Wiring is subject to change Always...

Страница 23: ...TC OT1 O T2 BR CM PU B Y COMP B B S C R CH OPTIONAL BL C LS R R BL BL PU BL R PU R R G G Y W PU Y1 Y 208 230 1 60 POWER SUPPLY B NOTE 2 B B BL BL BL BL B PU L1 B R CC L2 T1 T2 R B Y GRD R Y R Y2 CH O...

Страница 24: ...ENSER MOTOR CC CONTACTOR CH CRANKCASE HEATER FS FLAME SENSOR COMPONENT LEGEND CAP CAPACITOR L2 L2 MARKED TERMINAL LINE VOLTAGE LOW VOLTAGE UNMARKED TERMINAL WIRING WIRE SPLICE Y Y C Y2 Y2 1 REPLACEMEN...

Страница 25: ...PU B Y COMP B B S C R CH OPTIONAL BL C LS R R BL BL PU BL R PU R R G G Y Y Y2 W PU Y1 Y 208 230 1 60 POWER SUPPLY B NOTE 2 B B BL BL BL BL B PU L1 B R CC L2 T1 T2 R B Y GRD R Y1 PU PU BL BL BL PU Y Y...

Страница 26: ...NSER MOTOR CC CONTACTOR CH CRANKCASE HEATER FS FLAME SENSOR COMPONENT LEGEND CAP CAPACITOR L2 L2 MARKED TERMINAL LINE VOLTAGE LOW VOLTAGE UNMARKED TERMINAL WIRING WIRE SPLICE SOL SOLENOID 2 STAGE nd Y...

Страница 27: ...U PU PU BL BR 1 4 3 2 5 6 F C 240 24V 1 C 2 208 3 NOTE 4 GAS VALVE NOTE 5 ALT HONEYWELL W R GAS VALVE PLF Y1 Y2 Y C R W G CH OPTIONAL CONNECTED AT L1 L2 NOTE 3 NOTE 4 NOTE 2 208 230 3 60 CH OPTIONAL P...

Страница 28: ...ALS LS 8 6 3 RS PLF 6 5 2 3 C 1 4 GV FALSE FLAME SENSED OUTPUT DELAY OPEN LIMIT SWITCH COMPRESSOR ANTI CYCLE TIMER MAIN LIMIT OPEN STICKING GAS VALVE BAD SWITCH 3 MIN COMP WITHOUT INDUCER ON PRESSURE...

Страница 29: ...ECON 120 150 11 8 12 9 7 10 4 2 5 6 3 1 DI L1 FS HEAT UNUSED L2 GND POWER SUPPLY 208 230 3 60 CH OPTIONAL CONNECTED AT L1 L2 NOTE 3 Y1 Y2 CH OPTIONAL NOTE 5 PLF T1 T2 T3 T4 T5 NOTE 4 NO TE2 SEE NOTE 6...

Страница 30: ...CITOR WITH ECONOMIZER OPTION WH GR RD PU BL BL YL RD GR WH NO ECONOMIZER WH W W 0140G00087 Y C W R G Y C R G PU Y1 BL YL Y2 C GR RD G R THERMOSTAT FIELD WIRING 2 STAGE COOLING NOTE 3 TR NOTE NOTE 7 NO...

Страница 31: ...IONAL 460 3 60 SEE NOTE 6 BK BK PU RD BK YL RD GND RD BK BK RD CH OPTIONAL CONNECTED AT L1 L2 NOTE 2 SEE NOTE 3 SEE NOTE 5 TO THERMOSTAT VM GAS VALVE IGN FS MV ALT HONEYWELL GAS VALVE MV W R GV 5 4 1...

Страница 32: ...TYPE OF INSULATION AS ORIGINAL USE COPPER CONDUCTOR ONLY 0140G00088 4 ACCESSORY ECONOMIZER PLUG ON SELECT MODELS ADJACENT SPEED REPLACE THE BLACK MOTOR LEAD AT IBR 3 WITH RED 3 460V UNITS ARE SINGLE...

Страница 33: ...WH WH RD BK PU BL W R GAS VALVE GAS VALVE ALT HONEYWELL TO THERMOSTAT R C G Y W COOL P1 ECON 11 8 12 9 7 10 4 2 5 6 3 1 DI L1 FS HEAT UNUSED L2 GND POWER SUPPLY 460 3 60 CH OPTIONAL CONNECTED AT L1 L...

Страница 34: ...PTION WH GR RD PU BL BL YL RD GR WH NO ECONOMIZER WH W W 0140G00089 Y C W R G Y C R G PU Y1 BL YL Y2 C GR RD G R THERMOSTAT FIELD WIRING 2 STAGE COOLING NOTE 2 TR NOTE NOTE 6 NOTE 6 4 SEE NOTE 7 EM R...

Страница 35: ...135 ECON 120 150 11 8 12 9 7 10 4 2 5 6 3 1 DI L1 FS HEAT UNUSED L2 GND POWER SUPPLY 208 230 1 60 CH OPTIONAL CONNECTED AT L1 L2 NOTE 3 Y1 Y2 CH OPTIONAL NOTE 5 PLF T1 T2 T3 T4 T5 NOTE 4 N OTE2 SEE N...

Страница 36: ...ZER OPTION WH GR RD PU BL BL YL RD GR WH NO ECONOMIZER WH W W 0140G00267 Y C W R G Y C R G PU Y1 BL YL Y2 C GR RD G R THERMOSTAT FIELD WIRING 2 STAGE COOLING NOTE 3 TR NOTE NOTE 7 NOTE 7 5 NOTE 2 EM R...

Страница 37: ...Ton 2 1 2 Ton 3 Ton 3 1 2 4 Ton 5 Ton Min Filter Size 1 20 x 20 x 1 1 20 x 25 x 1 1 25 x 25 x1 2 20 x 20 x 1 2 20 x 25 x 1 MINIMUM CLEARANCES NOTE Roof overhang should be no more than 36 3 MIN 12 MIN...

Страница 38: ...38 THIS PAGE LEFT BLANK INTENTIONALLY...

Страница 39: ...39 THIS PAGE LEFT BLANK INTENTIONALLY...

Страница 40: ...significantly reduce the most frequent causes of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it...

Отзывы: