M A I N T E N A N C E

Have the gas  heating section of the unit checked at least
once a year before the heating season begins, to be sure that
the combustion air inlet and flue outlet hoods are not blocked
by debris, which would prevent adequate combustion air and
a properly operating vent system.

F

ILTER

 R

EPLACEMENT

 

OR

 C

LEANING

A return air filter is not supplied with this unit; however, there
must be a means of filtering all of the return air. The filter(s)
may be located in the return air duct(s), or return air filter
grille(s). Consult with your installing dealer for the actual
location of the return air filter(s) for your unit.
Dirty filters are the most common cause of inadequate heating
or cooling performance. Filter inspection should be made at
least every two months; more often if necessary because of
local conditions and usage.
Dirty throwaway filters should be discarded and replaced with
a new, clean filter. Dirty permanent filters should be washed
with water, thoroughly dried and sprayed with a filter adhesive
before being reinstalled. (Filter adhesives may be found at
many hardware stores.) Permanent filters should last several
years. However, should one become torn or uncleanable, it
should be replaced.

C

ABINET

 F

INISH

 M

AINTENANCE

Use a fine grade automotive wax on the cabinet finish to
maintain the finish’s original high luster. This is especially
important in installations with extended periods of direct
sunlight.

C

LEAN

 O

UTSIDE

 C

OIL

  (Q

UALIFIED

 S

ERVICER

 O

NLY

)

The coil with the outside air flowing over it should be inspected
annually and cleaned as frequently as necessary to keep the
finned areas free of lint, hair and debris.

C

ONDENSER

, E

VAPORATOR

AND

  I

NDUCED

 D

RAFT

 M

OTORS

Bearings on the air circulating blower motor, condenser motor
and the combustion fan motor are permanently lubricated. No
additional oiling is required.

F

LAME

 S

ENSOR

 (Q

UALIFIED

 S

ERVICER

 O

NLY

)

A drop in the flame current can be caused by a nearly invisible
coating on the flame sensor. This coating, created by the fuel
or combustion air supply, can be removed by carefully cleaning
the flame sensor with steel wool.

NOTE: 

After cleaning, the microamp signal should be stable and in

the range of 4 - 6 microamps DC.

Flame
Sensor

Flame Sensor

F

LUE

 P

ASSAGES

 (Q

UALIFIED

 S

ERVICER

 O

NLY

)

At the start of each heating season, inspect and, if necessary,
clean the unit flue passage.

C

LEANING

 F

LUE

 P

ASSAGES

 (Q

UALIFIED

 S

ERVICER

 O

NLY

)

1. Shut off electric power and gas supply to the unit.
2. Remove burner assembly by disconnecting the gas line

and removing the manifold bracket from the partition panel.

3. Remove the flue from the induced draft blower and the

collector box cover from the partition panel.

4. The primary heat exchanger tubes can be cleaned using a

round wire brush attached to a length of high grade stainless
steel cable, such as drain cleanout cable. Attach a variable
speed reversible drill to the other end of the spring cable.
Slowly rotate the cable with the drill and insert it into one of
the primary heat exchanger tubes. While reversing the drill,
work the cable in and out several times to obtain sufficient
cleaning. Use a large cable for the large tube, and then
repeat the operation with a small cable for the smaller tube.
Repeat for each tube.

5. When all heat exchanger tubes have been cleaned,

replace the parts in the reverse order in which they were
removed.

6. To reduce the chances of repeated fouling of the heat

exchanger, perform the steps listed in “Startup,
Adjustments, and Checks”.

Содержание GPG13

Страница 1: ...Requirements Embodied in The American National Standard National Standard of Canada Shown Below ANSI Z21 47 CSA 2 3 Central Furnaces RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION ATTENTION INSTALLING...

Страница 2: ...11 HEATING 11 COOLING 11 FAN ONLY 12 Startup Adjustments and Checks 12 HEATING STARTUP 12 COOLING STARTUP 15 Troubleshooting 15 IGNITION CONTROL ERROR CODES 15 ABNORMAL OPERATION HEATING 16 ABNORMAL O...

Страница 3: ...L TO SHUT OFF TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY WARNING THIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH MAY CAUSE S...

Страница 4: ...the outdoor air i e combustion air for the unit will be frequently contaminated by compounds containing chlorine or fluorine Common sources of such compounds include swimming pool chemicals and chlor...

Страница 5: ...TION ELECTRIC SHOCK OR CARBON MONOXIDE THIS UNIT MUST BE PROPERLY INSTALLED REPAIRED OPERATED AND MAINTAINED This unit is approved for outdoor installation ONLY To assure that your unit operates safel...

Страница 6: ...TION AND OR EQUIPMENT DAMAGE HIGH ALTITUDE KITS ARE FOR U S INSTALLATIONS ONLY AND ARE NOT APPROVED FOR USE IN CANADA The rating plate is stamped with the model number type of gas and gas input rating...

Страница 7: ...E A MATCH OR OPEN FLAME TO TEST FOR LEAKS NEVER EXCEED SPECIFIED PRESSURES FOR TESTING HIGHER PRESSURE MAY DAMAGE GAS VALVE AND CAUSE OVERFIRING WHICH MAY RESULT IN PREMATURE HEAT EXCHANGE FAILURE THI...

Страница 8: ...acturers and propane gas suppliers Since propane gas will quickly dissolve white lead or most standard commercial compounds special pipe dope must be used Shellac base compounds resistant to the actio...

Страница 9: ...SI Z21 20 AUTOMATIC IGNITION SYSTEM L2 L2 L2 L2 ECON 120 135 150 SPEED UP LOW VOLTAGE CONNECTOR Y Y2 Low Voltage Wiring PG1360 1A Only Refer to the unit wiring diagram for electrical connections When...

Страница 10: ...onal Board of Fire Underwriters for the Installation of Air Conditioning Warm Air Heating and Ventilating Systems Pamphlets No 90A and 90B The supply duct from the unit through a wall may be installed...

Страница 11: ...lower will deenergize This allows any additional heat in the heat exchanger to be transferred to the conditioned space PG13 48 60 1A ONLY HEAT FAN OFF delay is fixed at 180 seconds Airflow level is 50...

Страница 12: ...lout protection device is located on the burner bracket The reason for elevated temperatures at the control should be determined and repaired prior to resetting this manual reset control WARNING TO AV...

Страница 13: ...gas being delivered to the unit 3 INPUT GAS HTG VALUE x 3600 SEC PER CUBIC FOOT Example Natural gas with a heating value of 1000 BTU per cubic foot and 34 seconds per cubic foot as determined by Step...

Страница 14: ...utward from the burner without curling floating or lifting off Temperature Rise Check Check the temperature rise through the unit by placing thermometers in supply and return air registers as close to...

Страница 15: ...does not operate Compressor Protection Devices The compressor includes components which are designed to protect the compressor against abnormal operating conditions WARNING TO PREVENT PERSONAL INJURY...

Страница 16: ...and carefully clean with steel wool Check wiring Check wiring for opens shorts and miswiring Important If you have to frequently reset your gas electric package unit it means that a problem exists th...

Страница 17: ...bris CONDENSER EVAPORATOR AND INDUCED DRAFT MOTORS Bearings on the air circulating blower motor condenser motor and the combustion fan motor are permanently lubricated No additional oiling is required...

Страница 18: ...rical power and gas supply CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION CAUTION ALWAYS VERIFY PROPER OPERATION AFTER...

Страница 19: ...Seconds 0 7 30 0 60 Circulator Blower Outdoor Fan and Compressor Thermostat ON OFF ON OFF ON OFF Legend PG10 12 24 60 PG1324 42 PG1348 60 100 50 Light Signal Refer to Abnormal Heating or Cooling Opera...

Страница 20: ...SUPPLY ENTRANCE CONDENSATE DRAIN CONNECTION 3 4 NPT FEMALE 16 1 8 19 1 8 EVAPORATOR CONTROL PANEL ACCESS PANEL 4 3 4 B 7 15 16 16 B 5 1 2 1 3 8 16 2 3 4 A 18 7 16 FLUE EXHAUST 51 47 BLOWER ACCESS PAN...

Страница 21: ...H OPTIONAL CONNECTED AT L1 L2 NOTE 4 B BL Y R FS R O R H C F Y BR CAP1 BL B PU 4 SPEED MOTOR ALS Y Y PS PU W G G W R BL Y Y PU R C Y Y2 Y1 Y BL 6 5 2 3 G 4 1 Y PU PL RS MV GAS VALVE MV GV PU W R BL GV...

Страница 22: ...ER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH B4312003 REV B Wiring is subject to change Always...

Страница 23: ...TC OT1 O T2 BR CM PU B Y COMP B B S C R CH OPTIONAL BL C LS R R BL BL PU BL R PU R R G G Y W PU Y1 Y 208 230 1 60 POWER SUPPLY B NOTE 2 B B BL BL BL BL B PU L1 B R CC L2 T1 T2 R B Y GRD R Y R Y2 CH O...

Страница 24: ...ENSER MOTOR CC CONTACTOR CH CRANKCASE HEATER FS FLAME SENSOR COMPONENT LEGEND CAP CAPACITOR L2 L2 MARKED TERMINAL LINE VOLTAGE LOW VOLTAGE UNMARKED TERMINAL WIRING WIRE SPLICE Y Y C Y2 Y2 1 REPLACEMEN...

Страница 25: ...PU B Y COMP B B S C R CH OPTIONAL BL C LS R R BL BL PU BL R PU R R G G Y Y Y2 W PU Y1 Y 208 230 1 60 POWER SUPPLY B NOTE 2 B B BL BL BL BL B PU L1 B R CC L2 T1 T2 R B Y GRD R Y1 PU PU BL BL BL PU Y Y...

Страница 26: ...NSER MOTOR CC CONTACTOR CH CRANKCASE HEATER FS FLAME SENSOR COMPONENT LEGEND CAP CAPACITOR L2 L2 MARKED TERMINAL LINE VOLTAGE LOW VOLTAGE UNMARKED TERMINAL WIRING WIRE SPLICE SOL SOLENOID 2 STAGE nd Y...

Страница 27: ...U PU PU BL BR 1 4 3 2 5 6 F C 240 24V 1 C 2 208 3 NOTE 4 GAS VALVE NOTE 5 ALT HONEYWELL W R GAS VALVE PLF Y1 Y2 Y C R W G CH OPTIONAL CONNECTED AT L1 L2 NOTE 3 NOTE 4 NOTE 2 208 230 3 60 CH OPTIONAL P...

Страница 28: ...ALS LS 8 6 3 RS PLF 6 5 2 3 C 1 4 GV FALSE FLAME SENSED OUTPUT DELAY OPEN LIMIT SWITCH COMPRESSOR ANTI CYCLE TIMER MAIN LIMIT OPEN STICKING GAS VALVE BAD SWITCH 3 MIN COMP WITHOUT INDUCER ON PRESSURE...

Страница 29: ...ECON 120 150 11 8 12 9 7 10 4 2 5 6 3 1 DI L1 FS HEAT UNUSED L2 GND POWER SUPPLY 208 230 3 60 CH OPTIONAL CONNECTED AT L1 L2 NOTE 3 Y1 Y2 CH OPTIONAL NOTE 5 PLF T1 T2 T3 T4 T5 NOTE 4 NO TE2 SEE NOTE 6...

Страница 30: ...CITOR WITH ECONOMIZER OPTION WH GR RD PU BL BL YL RD GR WH NO ECONOMIZER WH W W 0140G00087 Y C W R G Y C R G PU Y1 BL YL Y2 C GR RD G R THERMOSTAT FIELD WIRING 2 STAGE COOLING NOTE 3 TR NOTE NOTE 7 NO...

Страница 31: ...IONAL 460 3 60 SEE NOTE 6 BK BK PU RD BK YL RD GND RD BK BK RD CH OPTIONAL CONNECTED AT L1 L2 NOTE 2 SEE NOTE 3 SEE NOTE 5 TO THERMOSTAT VM GAS VALVE IGN FS MV ALT HONEYWELL GAS VALVE MV W R GV 5 4 1...

Страница 32: ...TYPE OF INSULATION AS ORIGINAL USE COPPER CONDUCTOR ONLY 0140G00088 4 ACCESSORY ECONOMIZER PLUG ON SELECT MODELS ADJACENT SPEED REPLACE THE BLACK MOTOR LEAD AT IBR 3 WITH RED 3 460V UNITS ARE SINGLE...

Страница 33: ...WH WH RD BK PU BL W R GAS VALVE GAS VALVE ALT HONEYWELL TO THERMOSTAT R C G Y W COOL P1 ECON 11 8 12 9 7 10 4 2 5 6 3 1 DI L1 FS HEAT UNUSED L2 GND POWER SUPPLY 460 3 60 CH OPTIONAL CONNECTED AT L1 L...

Страница 34: ...PTION WH GR RD PU BL BL YL RD GR WH NO ECONOMIZER WH W W 0140G00089 Y C W R G Y C R G PU Y1 BL YL Y2 C GR RD G R THERMOSTAT FIELD WIRING 2 STAGE COOLING NOTE 2 TR NOTE NOTE 6 NOTE 6 4 SEE NOTE 7 EM R...

Страница 35: ...135 ECON 120 150 11 8 12 9 7 10 4 2 5 6 3 1 DI L1 FS HEAT UNUSED L2 GND POWER SUPPLY 208 230 1 60 CH OPTIONAL CONNECTED AT L1 L2 NOTE 3 Y1 Y2 CH OPTIONAL NOTE 5 PLF T1 T2 T3 T4 T5 NOTE 4 N OTE2 SEE N...

Страница 36: ...ZER OPTION WH GR RD PU BL BL YL RD GR WH NO ECONOMIZER WH W W 0140G00267 Y C W R G Y C R G PU Y1 BL YL Y2 C GR RD G R THERMOSTAT FIELD WIRING 2 STAGE COOLING NOTE 3 TR NOTE NOTE 7 NOTE 7 5 NOTE 2 EM R...

Страница 37: ...Ton 2 1 2 Ton 3 Ton 3 1 2 4 Ton 5 Ton Min Filter Size 1 20 x 20 x 1 1 20 x 25 x 1 1 25 x 25 x1 2 20 x 20 x 1 2 20 x 25 x 1 MINIMUM CLEARANCES NOTE Roof overhang should be no more than 36 3 MIN 12 MIN...

Страница 38: ...38 THIS PAGE LEFT BLANK INTENTIONALLY...

Страница 39: ...39 THIS PAGE LEFT BLANK INTENTIONALLY...

Страница 40: ...significantly reduce the most frequent causes of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it...

Отзывы: