7
6
CHANGING ORIENTATION OF VENT BLOWER
1
2
This furnace is shipped from the factory in the upflow
configuration with the vent connection on the left side. It can
be easily converted to right side venting following the
instructions below :
Electrical and Gas Supply must be "OFF" before attempting
any service.
Step 1
Disconnect the Power Supply.
Step 2
Rotate the quarter turn fasteners (items 1) 90 degrees to
release the Control Access Panel (item 2)
Step 3
Disconnect the Power wires to Vent Blower, Stack Overtemp
wires, and Pressure Switch tube leading to Vent Blower.
Step 4
Remove the three screws (item 3) which secure the Vent
Blower (item 4) to the Heat Shield (item 5) on illustration.
Step 5
Rotate Vent Blower 180 degrees counter clockwise. (WARN-
ING) Make sure that the O-Ring, and Restrictor Plate (if
used), (items 6) are located properly.
Step 6
Make sure the Vent Blower is properly seated against the O-
Ring and Vent Blower legs are aligned with the holes in Heat
Shield.
Step 7
Tighten the three screws (item 3), reconnect wiring to Vent
Blower and Stack Overtemp Switch. Reconnect tube from
Pressure Switch to Vent Blower.
4
5
3
5
4