Goodman GMN SERIES Скачать руководство пользователя страница 21

21

TEMPERATURE RISE

The difference between the temperature of the outlet air and the inlet air is known as the furnace temperature rise. This furnace
is designed to operate within the rise range displayed on the furnace series and rating plate. To ensure satisfactory
performance, the temperature rise of the furnace must be measured. Use the following procedure to measure and adjust the
furnace temperature rise:

1.) Prior to starting the furnace visually check the supply and return air ducts for restrictions or leaks. Make all necessary
repair to the ductwork prior to continuing.
2.) Adjust the room thermostat to obtain a continuous burner operation. Allow the furnace to operate for 15 minutes  before
proceeding to the next step.
3.) With an accurate thermometer measure the air temperature at the return air grille. If a combination of indoor / outdoor
air is used for return air, the temperature must be obtained from a point in the return air ductwork close to the connecting
point with the furnace.
4.) Measure the outlet air temperature of the furnace with a thermometer inserted into the supply duct approximately 12"
to 18" above the furnace outlet. It may be necessary to measure the outlet air in several places in the supply plenum in order
to obtain an accurate average.
5.) Subtract the inlet air temperature from the outlet air temperature to obtain the furnace temperature rise.
6.) Compare the temperature rise measured with that indicated on the furnace series and rating plate. If the measured rise
is above the tolerance shown on the series and rating plate the blower speed must be increased (a higher speed). If the
measured rise is below the furnace design rise range the blower speed must be decreased (a lower motor speed). Prior to
making any motor speed changes allow the furnace adequate time to cool down, and turn off electric supply to the appli-
ance. Repeat steps 2 thru 5 until satisfactory performance is achieved.
7.) Repair any holes which may have been made in the ductwork prior to putting the furnace into operation.

MOTOR LUBRICATION AND MAINTENANCE

Circulating air blower motor has sleeve bearings which are prelubricated by the motor manufacturer. There is no provision
for additional oiling. Clean the motor periodically to prevent the possibility of overheating due to an accumulation of dust and
dirt on the windings or on the motor exterior. As suggested elsewhere in these instructions, the air filters should be kept
clean. Dirty filters will restrict the airflow the blower motor requires and possibly overheat the motor.

The Vent Blower motor has bearings which are prelubricated by the motor manufacturer. There is no provision for additional
oiling.

SYSTEM OPERATION INFORMATION and HEAT EXCHANGER CLEANING

GENERAL GUIDELINES FOR MAXIMUM PERFORMANCE

1.) Keep the air filters clean. Your heating system will operate more efficiently and economically.
2.) Arrange your furniture and drapes so that the supply air registers and the return air grilles are unobstructed.
3.) Close doors and windows. This will reduce the heating load on your system.
4.) Avoid excessive use of kitchen and bathroom exhaust fans.
5.) Do not permit the heat generated by television, lamps, radios, etc. to influence the thermostat operation.
6.) Exclusive of the mounting platform, keep all combustible articles three feet from the furnace jacket.
7.) 

CAUTION:

 Replace all blower doors and compartment covers after servicing the furnace.

Do not operate the unit without all panels and doors securely in place.

Содержание GMN SERIES

Страница 1: ...INSTALLATION OPERATING INSTRUCTIONS for GMN SERIES GAS FURNACES PATENT PENDING GoodmanManufacturingCompany L P IO 554 1501 Seamist Houston Texas 77008 11 93...

Страница 2: ...Piping 8 Circulating Supply Air and Return Air 8 9 ElectricalConnection 9 Thermostat Location and Low Voltage Connections 9 10 ToRateFurnace 10 Main Burner Adjustment 11 Safety Controls Functions Che...

Страница 3: ...OW INSTALLATION GAS PIPING See pages 13 14 ELECTRICAL CONNECTIONS See page 16 RETURN AIR See pages 14 15 VENTING See pages 10 12 and VentingTables SUPPLY AIR See pages 14 15 VENTILATION COMBUSTION AIR...

Страница 4: ...ATION RETURN AIR See pages 14 15 VENTING See pages 10 12 andVentingTables ELECTRICAL CONNECTIONS See page 16 SPECIAL BASE See page 6 SUPPLY AIR See pages 14 15 GAS SUPPLY See pages 13 14 COMBUSTION VE...

Страница 5: ...are available from National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 LOCATION Donotinstallthisfurnaceinamobilehome Thefurnacedesignedonlyforinstallationinbuildingsconstructed...

Страница 6: ...WHEN THE FURNACE IS INSTALLED WITH SIDE AIR RETURN DUCTS FAILURE TO LEAVE THIS BASE PLATE INSTALLED COULD CAUSE PRODUCTS OF COMBUSTION TO BE CIRCULATED INTO LIVING SPACE AND CREATE POTENTIALLY HAZARDO...

Страница 7: ...nnectthePowerwirestoVentBlower StackOvertemp wires and Pressure Switch tube leading to Vent Blower Step 4 Remove the three screws item 3 which secure the Vent Blower item 4 to the Heat Shield item 5 o...

Страница 8: ...combustionandventila tionair Thefollowing Figure1throughFigure3 outlinethe minimum combustion ventilation air this furnace and any additional gas fired equipment require when installed in a confined a...

Страница 9: ...refer to Figure 3 3 The combustion and ventilation air openings must be of equal size and sized appropriately Use the table below as a guide TOTAL 1000 BTUH SQ INCH 2000 BTUH SQ INCH 4000 BTUH SQ INC...

Страница 10: ...sed to change from a vertical run to a horizontal run should be type DWV long radius to provide the correct slope in horizontal run If other types are used then 2 45 degree elbows should be used in pl...

Страница 11: ...t for proper fit Wipe socket and pipe with cleaner primer Apply a generous coat of primer to connecting areas DO NOT ALLOW PRIMER TO DRY BEFORE APPLYING CEMENT Apply a thin coat of cement in the socke...

Страница 12: ...r expected snow level c If adjacent to a public walkway the vent termination must be a minimum of 7 feet above the walkway d Avoid area where condensate drainage may be a problem such as flower beds p...

Страница 13: ...ng use a soap and water solution or other approved method DO NOT USE AN OPEN FLAME CONNECTGASSERVICEfrommetertocontrolassembly Seepreviousdrawingfortypicalhook up AGROUND JOINT UNIONMUSTBEINSTALLED EX...

Страница 14: ...INES WHICH HAVE PREVIOUSLY SERVICED ANOTHER APPLIANCE CIRCULATING SUPPLY AIR AND RETURN AIR The circulating air return may be taken from 1 outside the building 2 return ducts from several rooms 3 cent...

Страница 15: ...INGS IN THE CLOSET DOOR AND THE CIRCULATING AIR OPENINGS MUST BE SEPARATED AN ADEQUATE DISTANCE TO PREVENT THE CIRCULATING AIR FROM INTERFERING WITH THE NATURAL FLOW OF VENTILATION AIR FAILURE TO PREV...

Страница 16: ...quipment in polarity sensitive The neutral ground connection must be connected to the equipment white power connector Failure to observe this practice will result in no flame sensing ability THERMOSTA...

Страница 17: ...m the table below resulting in the furnace input being reduced at a rate of 4 for each 1000 feet above sea level U S only ALTITUDE BURNER ORIFICE NATURAL GAS 0 2000 45 3000 47 4000 47 5000 47 6000 48...

Страница 18: ...h the exception of pilot burners 5 Place the furnace into operation 6 Adjust inlet pressure to obtain a pressure range between 5 and 7 W C 7 After 15 minutes of furnace operation time meter with an ac...

Страница 19: ...tem occurs DO NOT tamper with or bypass this switch For more details of the venting installation see the section titled VENTING To check this switch remove the hose from the vent motor with the burner...

Страница 20: ...zed The main valve is opened after the ignitor has been glowing for about 17 seconds If main burner flame is detected by the flame sensor see flame sensor section the burners will continue operation U...

Страница 21: ...ace design rise range the blower speed must be decreased a lower motor speed Prior to making any motor speed changes allow the furnace adequate time to cool down and turn off electric supply to the ap...

Страница 22: ...r assembly 11 Remove the vent blower heat shield and flue collector box 12 Withastiffwirebrushonaflexiblehandleremoveanyloosescalefromtheheatexchanger bothflueopeningandburner opening Use a 1 2 diamet...

Страница 23: ...if service is to be performed 3 Remove control access panel OPERATING INSTRUCTIONS 4 Turn gas control knob clockwise to OFF Do not force 5 Replace control access panel FOR YOUR SAFETY READ BEFORE OPE...

Страница 24: ...rner flame The ignitor will de energize about 7 to 9 seconds If the flame sensor does not detect the presence of main burner flame the gas valve will close and steps 6 through 9 will be repeated for a...

Страница 25: ...ARMS UP GAS VALVE OPENS FLAME SENSED IGNITOR DEACTIVATES VENTER OFF BLOWER OFF BLWR STARTS HTG SPEED BLOWER OFF BLOWER STARTS ON COOLING SPEED CONTACTOR OPENS GAS VALVE OFF VENT MOTOR STARTS TSAT CALL...

Страница 26: ...WIRINGDIAGRAM 26...

Отзывы: