GM9S96-U Product Specifications
GM9S96
0403BU
GM9S96
0603BU
GM9S96
0805CU
Heating Data
High Fire Input¹
40,000
60,000
80,000
High Fire Output¹
38,400
57,600
76,800
AFUE²
96
96
96
Temperature Rise Range (°F)
15 - 45
30 - 60
30 - 60
Vent Diameter³
2" - 3"
2" - 3"
2" - 3"
No. of Burners Ports
2
3
4
Circulator Blower
Available AC @ 0.5" ESP
1.5 - 3
1.5 - 3
2.5 - 5
Size (D x W)
10" x 8"
11" x 8"
11" x 10"
Horsepower @ 1075 RPM
½
½
1
Speed
9
9
9
Filter Size (in²) (Qty)
(1) 16 x 25
(side or
bottom)
(1) 16 x 25
(side or
bottom)
(1) 20 x 25
(bottom)
or (2) 16 x 25
(side)
Electrical Data
Min. Circuit Ampacity⁴
10.8
10.8
16.1
Max. Overcurrent Device (amps)⁵
15
15
20
Shipping Weight (lbs)
115
120
145
¹
Natural Gas BTU/h
² DOE AFUE based upon Isolated Combustion System (ICS)
³ Installer must supply one or two PVC pipes: one for combustion air (optional) and one for the flue outlet (required).
Vent pipe must be either 2" or 3" in diameter, depending upon furnace input, number of elbows, length of run
and installation (1 or 2 pipes). The optional Combustion Air Pipe is dependent on installation/code requirements
and must be 2" or 3" diameter PVC.
⁴
Minimum Circuit Ampacity = (1.25 x Circulator Blower Amps) + ID Blower amps. Wire size should be determined
in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
⁵ Maximum Overcurrent Protection Device refers to maximum recommended fuse or circuit breaker size.
May use fuses or HACR-type circuit breakers of the same size as noted.
Notes
•
All furnaces are manufactured for use on 115 VAC, 60 Hz, single-phase electrical supply.
•
Gas Service Connection ½" FNPT
•
Important: Size fuses and wires properly and make electrical connections in accordance with the
National Electrical Code and/or all existing local codes.
•
For bottom return: Failure to unfold flanges may reduce airflow by up to 18%. This could result in performance
and noise issues.
•
For servicing or cleaning, a 24" front clearance is required. Unit connections (electrical, flue and drain)
may necessitate greater clearances than the minimum clearances listed above. In all cases, accessibility
clearance must take precedence over clearances from the enclosure where accessibility clearances are greater.
Downloaded from