8
www.goodmanmfg.com
SS-GMVM96
SS-GMVM96
www.goodmanmfg.com
9
P
roduct
S
PecificationS
P
roduct
S
PecificationS
GCVM96 a
irflow
d
ata
— C
ooliNG
s
peeds
GCVM960604CX
GCVM960805DX
High- or Single Stage
Low Stage
High- or Single Stage
Low Stage
Cooling
Speed Tap
Adjust
Tap
CFM *
Cooling
Speed Tap
Adjust
Tap
CFM *
Cooling
Speed Tap
Adjust
Tap
CFM *
Cooling
Speed Tap
Adjust
Tap
CFM *
A
Minus(-)
594
A
Minus(-)
333
A
Minus(-)
810
A
Minus(-)
477
Normal
660
Normal
370
Normal
900
Normal
530
Plus (+)
726
Plus (+)
407
Plus (+)
990
Plus (+)
583
B
Minus(-)
774
B
Minus(-)
486
B
Minus(-)
990
B
Minus(-)
657
Normal
860
Normal
540
Normal
1100
Normal
730
Plus (+)
946
Plus (+)
594
Plus (+)
1210
Plus (+)
803
C
Minus(-)
1035
C
Minus(-)
711
C
Minus(-)
1287
C
Minus(-)
837
Normal
1150
Normal
790
Normal
1430
Normal
930
Plus (+)
1265
Plus (+)
869
Plus (+)
1573
Plus (+)
1023
D
Minus(-)
1323
D
Minus(-)
882
D
Minus(-)
1692
D
Minus(-)
1098
Normal
1470
Normal
980
Normal
1880
Normal
1220
Plus (+)
1617
Plus (+)
1078
Plus (+)
2068
Plus (+)
1342
* @ .1” - .8” w.c. ESP
Notes
• All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
• For most jobs, about 400 CFM per ton when cooling is desirable.
• Operation is recommended below .5” w.c. ESP in heating mode. Operating CFM between .5” and .8” w.c. is tabulated for cooling purposes only.
GCVM961005DX
High- or Single Stage
Low Stage
Cooling
Speed Tap
Adjust
Tap
CFM *
Cooling
Speed Tap
Adjust
Tap
CFM *
A
Minus(-)
702
A
Minus(-)
450
Normal
780
Normal
500
Plus (+)
858
Plus (+)
550
B
Minus(-)
963
B
Minus(-)
666
Normal
1070
Normal
740
Plus (+)
1177
Plus (+)
814
C
Minus(-)
1242
C
Minus(-)
828
Normal
1380
Normal
920
Plus (+)
1518
Plus (+)
1012
D
Minus(-)
1602
D
Minus(-)
1044
Normal
1780
Normal
1160
Plus (+)
1958
Plus (+)
1276
* @ .1” - .8” w.c. ESP
Notes
• All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
• For most jobs, about 400 CFM per ton when cooling is desirable.
• Operation is recommended below .5” w.c. ESP in heating mode. Operating CFM between .5” and .8” w.c. is tabulated for cooling purposes only.