CONDENSING UNIT SPECIFICATIONS
9
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and
wires in accordance with all national and/or local electrical codes. Use copper wire only.
Unit specifications are subject to change without notice.
ALWAYS
refer to the unit's serial plate for the most up-to-date general
and electrical information.
DSXC160[48-60]1B*
Dimensions
Model
Dimensions - W x D x H
DSXC160481B*
35½ x 35½ x 36¼
DSXC160601B*
35½ x 35½ x 38¼
*
Up to 24' in equivalent line length
(1)
Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device:
MUST
use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
NOTES:
•
Always check the S & R plate for electrical data on the unit being installed.
•
Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections (4 & 5 ton units).
•
Installer will need to supply 3/4" to 7/8" adapters for suction line connections (3 ton unit).
•
Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge
Procedure.
•
Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE
OUTDOOR UNIT, NOT THE INDOOR COIL.
DSXC160481B*
DSXC160481BC
DSXC160601B*
DSXC160601BC
Cooling Capacity, BTUH
48,000
48,000
60,000
60,000
Compressor
R.L. Amps
21.2
21.2
25.6
28.8
L.R. Amps
96.0
104.0
118.0
152.9
Low Pressure Switch
Open
55 PSIG
55 PSIG
22 PSIG
22 PSIG
Close
95 PSIG
95 PSIG
50 PSIG
50 PSIG
High Pressure Switch
Open
610 PSIG
610 PSIG
610 PSIG
610 PSIG
Close
420 PSIG
420 PSIG
420 PSIG
420 PSIG
Condenser Fan Motor
Horsepower
1/6
1/6
1/6
1/6
F.L. Amps
1.0
1.2
1.0
1.2
Liquid Line, Inches O.D.*
3/8"
3/8"
3/8"
3/8"
Suction Line, Inches O.D.*
1 1/8"
1 1/8"
1 1/8"
1 1/8"
Refrigerant Charge
135.0
135.0
200.0
200.0
Power Supply
208/230-60-1
208/230-60-1
208/230-60-1
208/230-60-1
Minimum Circuit Ampacity
(1)
27.5
27.7
33.0
37.7
Maximum Overcurrent Device
(2)
45
45
50
60
Electrical Conduit Size
Power Supply (Inches)
1/2 or 3/4
1/2 or 3/4
1/2 or 3/4
1/2 or 3/4
Approximate Shipping Weight
241
241
301
301