CONDENSING UNIT SPECIFICATIONS
6
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit
breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
ASXC160[24-36]1B*
Dimensions
*
Up to 24' in equivalent line length
(1)
Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device:
MUST
use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
NOTES:
•
Always check the S & R plate for electrical data on the unit being installed.
•
Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections (4 & 5 ton units).
•
Installer will need to supply 3/4" to 7/8" adapters for suction line connections (3 ton unit).
•
Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge
Procedure.
•
Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE
OUTDOOR UNIT, NOT THE INDOOR COIL.
Model
Dimensions - W x D x H
ASXC160241B*
29 x 29 x 30¼
ASXC160361B*
29 x 29 x 30¼
AS XC160241BB
A S XC160241B C
A SXC160361B B
AS XC160361BC
Cooling Capacity, B TUH
24,000
24,000
36,000
36,000
Com pressor
R.L. A m ps
10.3
11.7
16.7
15.3
L.R. A m ps
52.0
58.3
82.0
83.0
Low Pres sure S witch
Open
22 P S IG
22 P SIG
22 PS IG
22 P S IG
Clos e
50 P S IG
50 P SIG
50 PS IG
50 P S IG
High P ress ure Switc h
Open
610 PS IG
610 P S IG
610 P SIG
610 PS IG
Clos e
420 PS IG
420 P S IG
420 P SIG
420 PS IG
Condens er Fan M otor
Hors epower
1/6
1/6
1/6
1/6
F.L. Am ps
1.1
1.1
0.9
0.9
Liquid Line, Inches O.D.*
3/8"
3/8"
3/8"
3/8"
S uction Line, Inches O.D.*
3/4"
3/4"
7/8"
7/8"
Refrigerant Charge
100.0
88.0
110.0
96.0
P ower Supply
208/230-60-1
208/230-60-1
208/230-60-1
208/230-60-1
M inim um Circ uit A m pac ity
(1)
14.0
15.7
21.8
20.0
M axim um Overcurrent Device
(2)
20
20
35
35
E lectrical Conduit S iz e
Power S upply (Inches)
1/2 or 3/4
1/2 or 3/4
1/2 or 3/4
1/2 or 3/4
A pprox im ate Shipping W eight
198
198
202
202