P
roduCt
S
PeCifiCationS
P
roduCt
S
PeCifiCationS
SS-CPH90-150
www.goodmanmfg.com
3
P
roduCt
S
PeCifiCationS
— 7½ t
onS
CPH090
XXX3BXXX
CPH090
XXX4BXXX
CPH090
XXX7BXXX
Cooling Capacity
Total BTU/h
90,000
90,000
90,000
Sensible BTU/h
65,700
65,700
65,700
EER / IEER
11.5 / 11.2
11.5 / 11.2
11.5 / 11.2
IPLV
12.30
12.30
12.30
Decibels
83
83
83
AHRI Reference #s
3000984
3000984
3000984
Heating Capacity
BTU/h / COP (47° F)
90,000 / 3.5
90,000 / 3.5
90,000 / 3.5
BTU/h / COP (17° F)
55,500 / 2.4
55,500 / 2.4
56,500 / 2.4
Evaporator Motor / Coil
Motor Type
Belt Drive
Belt Drive
Belt Drive
Indoor Nominal CFM
3,000
3,000
3,000
Indoor Motor FLA (Cooling)
7.8
3.9
2.5
Horsepower - RPM
2.0 - 1725
2.0 - 1725
2.0 - 1725
Piston Size (Cooling)
0.076
0.076
0.078
Filter Size
16" x 24" x 2"
16" x 24" x 2"
16" x 24" x 2"
Drain Size (NPT)
¾"
¾"
¾"
R-410A Refrigerant Charge: Cir #1 / #2 (oz.)
215 / 215
215 / 215
200 / 200
Evaporator Coil Face Area (ft²)
10.2
10.2
10.2
Rows Deep / Fins per Inch
4 / 16
4 / 16
4 / 16
Belt Drive Evap Fan Data
# of Wheels (D x W)
1 (15" x 12")
1 (15" x 12")
1 (15" x 12")
Motor Sheave / Blower Sheave
VL40 / AK74
VL40 / AK74
VL40 / AK74
Belt
AX51
AX51
AX51
Condenser Fan / Coil
Quantity of Condenser Fan Motors
2
2
2
Horsepower - RPM
¼ - 1090
¼ - 890
¼ - 1075
Fan Diameter / # Fan Blades
22 / 4
22 / 4
22 / 4
Outdoor Expansion Device
0.052
0.052
0.055
Outdoor Nominal CFM
7,600
7,600
7,600
Face Area (ft²)
32.4
32.4
32.4
# Coils / Rows Deep - Fins per Inch
2 / 2 - 20
2 / 2 - 20
2 / 2 - 20
Piston Size (Heating)
0.052
0.052
0.055
Compressor
Quantity / Type / Stage
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
Compressor RLA / LRA
13.1 / 83.1
6.1 / 41.0
4.4 / 33.0
Electrical Data
Voltage / Phase / Frequency
208-230 / 3 / 60
460 / 3 / 60
575 / 3 / 60
Indoor Blower HP / FLA
1.5 / 5.0
1.5 / 2.5
2 / 2.5
Outdoor Fan HP / FLA
¼ / 1.4
¼ / 0.8
¼ / 0.6
Total Unit Amps
36.9
17.7
12.5
Min. Circuit Ampacity¹
40
19
13.6
Max. Overcurrent Protection (amps)²
50
25
15
Entrance Power Supply & Control Voltage
Locating Dimple
Operating Weight (lbs)
1135
1135
1135
Ship Weight (lbs)
1175
1175
1175
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note:
Always check the S&R plate for electrical data on the unit being installed.