20 www.goodmanmfg.com
SS-CPH90-150
H
eat
k
it
e
leCtriCal
d
ata
— 7½ t
onS
m
inimum
a
irflow
for
e
leCtriC
H
eat
Heater Size (kW)
Minimum CFM
15
3,000
30
3,000
43
3,000
Model and
Heat Kit Usage
MCA¹
at 208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPH090***3B***
40
50
EHK3-16
74 / 85
80 / 90
15
3000-3375 CFM
EHK3-30
113 / 130
120 / 150
30
3000-3375 CFM
EHK3-45
147 / 169
150 / 175
43
3000-3375 CFM
Model and
Heat Kit Usage
MCA¹
at 208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPH090***4B***
19
25
EHK4-16
42
45
15
3000-3375 CFM
EHK4-30
64
70
30
3000-3375 CFM
EHK4-45
84
90
43
3000-3375 CFM
Model and
Heat Kit Usage
MCA¹
at 208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPH090***7B***
14
15
EHK4-16
32
35
15
---
EHK4-30
51
60
30
---
EHK4-45
68
70
43
---
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protection device
k
w C
orreCtion
f
aCtor
kW Correction Factor for 1- & 3-Phase Units
Supply Voltage
240
230
220
210
208
Correction Factor
1
0.93
0.82
0.78
0.76
kW Correction Factor for 480V Units
Supply Voltage
460
440
430
Correction Factor
0.92
0.84
0.8
For other voltage, use voltage² / 480²
kW Correction Factor for 575V Units
Supply Voltage
560
550
540
Correction Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW.