P
roduCt
S
PeCifiCationS
P
roduCt
S
PeCifiCationS
22 www.goodmanmfg.com
SS-CPH90-150
H
eat
k
it
e
leCtriCal
d
ata
— 10 t
onS
k
w C
orreCtion
f
aCtor
kW Correction Factor for 1- & 3-Phase Units
Supply Voltage
240
230
220
210
208
Correction Factor
1
0.93
0.82
0.78
0.76
kW Correction Factor for 480V Units
Supply Voltage
460
440
430
Correction Factor
0.92
0.84
0.8
For other voltage, use voltage² / 480²
kW Correction Factor for 575V Units
Supply Voltage
560
550
540
Correction Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW.
m
inimum
a
irflow
for
e
leCtriC
H
eat
Heater Size (kW)
Min. CFM
Down-shot
Min. CFM
Horizontal
15
4,000
4,000
30
4,000
4,000
43
4,000
4,000
Model and
Heat Kit Usage
MCA¹ at
208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPH120***3B***
49
60
EHK3-16
81 / 94
90 / 100
15
3500 - 4500 CFM
EHK3-30
122 / 139
125 / 150
35
3500 - 4500 CFM
EHK3-45
154 / 178
175 / 200
43
4000 - 4500 CFM
Model and
Heat Kit Usage
MCA¹ at
208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPH120***3H***
50
60
EHK3-16
82 / 95
90 / 100
15
---
EHK3-30
122 / 140
125 / 150
35
---
EHK3-45
155 / 179
175 / 200
43
---
Model and
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW
at 480V
Recommended
Airflow Range
CPH120***4B***
24
30
EHK4-16
46
50
15
3500 - 4500 CFM
EHK4-30
69
70
30
3500 - 4500 CFM
EHK4-45
89
90
43
4000 - 4500 CFM
Model and
Heat Kit Usage
MCA¹
at 575V
MOP² (amps)
at 575V
Actual kW
at 575V
Recommended
Airflow Range
CPH0120***7B***
17
20
EHK7-16
36
40
15
3500 - 4500 CFM
EHK7-30
55
60
30
3500 - 4500 CFM
EHK7-45
71
80
43
4000 - 4500 CFM
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protection device