p
RoduCt
s
pECifiCations
p
RoduCt
s
pECifiCations
8 www.goodmanmfg.com
SS-CPC90-150
a
iRflow
d
ata
— 8½ t
ons
Standard Belt Drive — Down Shot
ESP
(“ W.C.)
Turns Open
0
1
2
3
4
5
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
0.1
3467
701
1.04
3143
650
0.81
0.3
3391
746
1.12
3029
701
0.85
2607
653
0.63
0.5
3297
795
1.20
2899
751
0.91
2456
707
0.68
0.7
3250
845
1.30
2800
795
0.98
0.9
3153
887
1.38
2721
845
1.08
1.1
2688
894
1.20
High-Static Belt-Drive — Down Shot
ESP
(“ W.C.)
Turns Open
0
1
2
3
4
5
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
0.9
3251
906
1.48
1.1
3278
962
1.68
2793
912
1.27
1.3
3321
1012
1.87
2862
968
1.47
1.5
3572
1060
2.22
2891
1020
1.64
1.7
3209
1072
2.01
1.9
3231
1116
2.19
2740
1077
1.75
2.1
3256
1156
2.31
2939
1126
2.01
Standard Belt Drive — Horizontal
ESP
(“ W.C.)
Turns Open
0
1
2
3
4
5
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
0.1
3475
698
1.05
3159
657
0.83
0.3
3665
794
1.41
3318
744
1.08
3027
700
0.85
2646
660
0.65
0.5
3630
838
1.49
3255
800
1.2
2903
750
0.91
2458
706
0.65
0.7
3537
882
1.57
3177
844
1.26
2818
802
0.99
0.9
3086
888
1.36
2700
849
1.07
1.1
2563
893
1.14
High-Static Belt-Drive — Horizontal
ESP
(“ W.C.)
Turns Open
0
1
2
3
4
5
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
CFM
RPM
BHP
0.9
3297
899
1.51
1.1
3248
953
1.62
2856
905
1.28
1.3
3336
1005
1.84
2810
959
1.41
1.5
3364
1054
2.04
2799
1016
1.59
1.7
3238
1100
2.15
2886
1066
1.81
1.9
3188
1146
2.23
2809
1111
1.97
Notes :
Assume dry coil with filter in place; CFM correction for wet coil = 3%
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that exceed the above could require a
larger motor. Minimum rated SCFM is 350 per ton.