— 7½ t
onS
CPC090
***3B***B*
CPC090
***4B***B*
CPC090
***7B***B*
Cooling Capacity
Total BTU/h
90,000
90,000
90,000
Sensible BTU/h
64,000
64,000
64,000
EER / IEER
11.5 / 11.5
11.5 / 11.5
11.5 / 11.5
Decibels
82.0
82.0
82.0
AHRI Reference #s
5104770
5104770
5104770
Evaporator Motor / Coil
Motor Type
Belt Drive
Belt Drive
Belt Drive
Indoor Nominal CFM
3,000
3,000
3,000
Indoor Motor FLA (Cooling)
5.0
2.5
2.3
Horsepower / RPM
1.5 / 1745
1.5 / 1745
1.5 / 1725
Piston Size (Cooling)
0.078
0.078
0.078
Filter Size (Qty)
(4) 16”x20”x2”
(4) 16”x20”x2”
(4) 16”x20”x2”
Drain Size (NPT)
¾”
¾”
¾”
R-410A Refrigerant Charge Cir #1 & #2
175 oz.
175 oz.
175 oz.
Evaporator Coil Face Area (ft²)
8.9
8.9
8.9
Rows Deep / Fins per Inch
4 / 16
4 / 16
4 / 16
Belt Drive Evap Fan Data
# of Wheels (D x W)
1 (15” x 12”)
1 (15” x 12”)
1 (15” x 12”)
Motor Sheave / Blower Sheave
VL40 / AK74
VL40 / AK74
VL40 / AK74
Belt
AX51
AX51
AX51
Condenser Fan / Coil
Quantity of Condenser Fan Motors
2
2
2
Horsepower - RPM
¼ - 1075
¼ - 890
¼ - 1,075
Fan Diameter / # Fan Blades
22 / 4
22 / 4
22 / 4
Outdoor Nominal CFM
7,200
7,200
7,200
Face Area (ft²)
36
36
36
Rows Deep / Fins per Inch
2 / 22
2 / 22
2 / 22
Compressor
Quantity / Type
2 / Scroll
2 / Scroll
2 / Scroll
Stage
1
1
1
Electrical Data
Voltage-Phase-Frequency
208/230-3-60
460-3-60
575-3-60
Quantity of Compressors
2
2
2
Compressor RLA / LRA
13.1 / 83.1
6.1 / 41.0
4.4 / 33.0
Max External Static
1.0”
1.0”
1.0”
Outdoor Fan HP / RLA
(2) ¼ / 1.4
(2) ¼ / 0.8
(2) ¼ / 0.6
Total Unit Amps
34.0
16.3
12.3
Min. Circuit Ampacity¹
37.3
17.8
13.4
Max. Overcurrent Protection (amps)²
50
20
15
Entrance Power Supply
Locating
Dimple
Locating
Dimple
Locating
Dimple
Entrance Control Voltage
Operating Weight (lbs)
975
975
975
Ship Weight (lbs)
1000
1000
1000
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.