Goodman CONDENSING UNIT HEAT PUMP Скачать руководство пользователя страница 13

13

A

IR

 C

ONDITIONER

/H

EAT

 P

UMP

 A

DVANCED

 F

EATURES

 M

ENUS

 (

CONT

D

)

Submenu Item

Indication (for Display Only; not User Modifiable)

Mode (MODE)

Displays the current air conditioner operating mode

CFM (CFM)

Displays the airflow for the current operating mode

STATUS

Submenu Item

User Modifiable Options

Comments

Heat Airflow Trim

(HT TRM)

-10% to +10% in 2% increments, 
default is 0%

Selects the airflow trim amount; applies to 
heat pump only.

Heat ON Delay

(HT ON)

5, 10, or 15 seconds, default is 5 
seconds

Selects the indoor blower heat ON delay; 
applies to heat pump only. 

Heat OFF Delay

(HT OFF)

30, 50, 70, or 90 seconds, default 
is 30 seconds

Selects the indoor blower heat OFF delay; 
applies to heat pump only.

Defrost Interval

(DEFROST)

30, 60, 90, or 120 minutes, default 
is 30 minutes.

Selects the time interval between defrosts; 
applies to heat pump only.

Compressor Delay

(CMP DLY)

0, 5, 15, or 30 seconds, default is 5 
seconds

Selects the compressor off time after a 
reversing valve shift; applies to heat pump 
only.

HEAT SET-UP

T

HERMOSTAT

 M

ENU

If this heat pump is installed with a CT compatible furnace, the system is recognized as a dual fuel system.  The balance point
temperature should be set via the thermostat advanced menu.  Navigate to the 

THERMOSTAT

 menu.  Press the 

INSTALLER

CONFIG

 key.  Navigate to the 

SETUP

 menu and press the 

INSTALLER CONFIG

 button.  Navigate to 

dF BAL PNT

.  Adjust the

dual fuel system balance point using the back/forward arrows.

Содержание CONDENSING UNIT HEAT PUMP

Страница 1: ...the 10 Year Unit Replacement Limited Warranty and the 10 Year Parts Limited Warranty for Goodman branded products online registration must be com pleted within 60 days of installation Online registrat...

Страница 2: ...for the unit s is the angle to obstructions Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clear ance Corner in...

Страница 3: ...ant tubing clean and dry prior to and during installation Tubing should always be cut square keeping ends round and free from burrs Clean the tubing to prevent contamination Do NOT let refrigerant lin...

Страница 4: ...ean any copper oxide present from the inside of the refrigerant lines and spread it throughout the system This may cause a blockage or failure of the metering device 3 After brazing quench the joints...

Страница 5: ...CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK WIRING MUST CONFORM WITH NEC OR CEC AND ALL LOCAL CODES UNDERSIZED WIRES COULD CAUSE POOR EQUIPMENT PERFORMANCE EQUIPMENT DAMAGE O...

Страница 6: ...ING THERMOSTAT 1 2 R C B L U E R E D W H T B L K INDOOR UNIT Communicating Thermostat with Low Voltage Wires to Heat Pump NOTE If the heat pump unit is wired in the communicating mode together with th...

Страница 7: ...L R G W BL BR G W2 C R G W BL INDOOR UNIT 18 GA 7 WIRE NEEDED WHEN TWO OT ARE USED SEE NOTE 4 RED GREEN WHITE BLUE C W2 O Y1 Y2 G R E O Y1 Y2 HEAT PUMP W2 C R TYP H P ROOM THERMOSTAT 18 GA 7 WIRE SYST...

Страница 8: ...or 10 minutes for fixed orifices and 20 minutes for expansion valves CHARGE VERIFICATION REFRIGERANT UNDER PRESSURE DO NOT OVERCHARGE SYSTEM WITH REFRIGERANT DO NOT OPERATE UNIT IN A VACUUM OR AT NEGA...

Страница 9: ...e cleared by depressing the button for greater than five seconds Consecutively repeated faults are displayed a maximum of three times Refer to the fault code definitions at the end of this manual for...

Страница 10: ...ooling Heating M odels CTK0 AAWIRING NOTE Refer to section Electrical Connections High Voltage Connections for 208 230 volt line connections to the air conditioner or heat pump NOTE A removable plug c...

Страница 11: ...first sub menu is then displayed See tables below for listing of furnace sub menus Touch the or _ to step through the list of submenus and view settings If a setting can be adjusted _ and keys will a...

Страница 12: ...itioner or heat pump model number Serial Number SER NUM Displays the air conditioner or heat pump serial number Optional Software SOFTWARE Displays the application software revision IDENTIFICATION Sub...

Страница 13: ...econds Selects the indoor blower heat OFF delay applies to heat pump only Defrost Interval DEFROST 30 60 90 or 120 minutes default is 30 minutes Selects the time interval between defrosts applies to h...

Страница 14: ...t the network may arise The integrated control module has some on board tools that may be used to trouble shoot the network These tools are red communications LED green receive Rx LED and learn button...

Страница 15: ...blocks are securely twisted together prior to inserting into terminal block Verify heat pump installation type legacy traditional or communicating Check data 1 data 2 voltages Rapid Flashing Normal ne...

Страница 16: ...ED SUCTION PRESSURE TEMPERATURE CHART SATURATED SUCTION TEMPERATURE F LIQUID PRESSURE PSIG R 22 R 410A 200 101 70 210 105 73 220 108 76 225 110 78 235 113 80 245 116 83 255 119 85 265 121 88 275 124 9...

Страница 17: ...Faulty Evap Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortage of Refrigerant Test For Leaks Add Refrig...

Страница 18: ...e indicated code 6 Flashes ON OFF OFF x Board miss operation INTERNAL FAULT EE x Compressor relay contacts welded x Replace control x Turn power OFF prior to repair x Replace with correct replacement...

Страница 19: ...emory card x Error code will be cleared once data is loaded Applies only to fully communicating system using ComfortNet thermostat x Air conditioner heat pump fails to operate x Air conditioner heat p...

Страница 20: ...indoor blower motor repair replace as needed x Check indoor thermostat setting x Turn power OFF prior to repair x Fault will clear after 30 consecutive normal cycles x Fault may be cleared by cycling...

Страница 21: ...tdoor fan motor capacitor replace as needed x Turn power OFF prior to repair x Replace with correct replacement part s x Compressor and outdoor fan are off x Low pressure switch trip 3 times within sa...

Страница 22: ...ompressor repair replace as needed x Check compressor wiring repair replace as needed x Turn power OFF prior to repair x Fault will clear after 1 normal cycle x Fault may be cleared by cycling 24VAC t...

Страница 23: ...all x Open Run Circuit Lockout OPEN RUN LOCK 07 x Compressor run winding is open x Compressor not properly wired to control x Faulty compressor wiring x Check compressor repair replace as needed x Che...

Страница 24: ...prior to repair x Fault will clear if secondary voltage rises above 21VAC x Replace with correct replacement part s x Compressor is off x Integrated control module diagnostic status LED s display the...

Отзывы: