12
A
IR
C
ONDITIONER
/H
EAT
P
UMP
A
DVANCED
F
EATURES
M
ENUS
Submenu Item
Indication (for Display Only; not User Modifiable)
Number of AC Stages (CL STG)
Displays the number of air conditioning stages; applies to AC and
Number of HP Stages (HT STG)
Displays the number of heat pump stages; applies to HP only.
AC Tonnage (TONS)
Displays the air conditioning tonnage; applies to AC and HP.
CONFIGURATION
Submenu Item
Indication/User Modifiable Options
Comments
Fault 1 (FAULT #1)
Most recent AC/HP fault
For display only
Fault 2 (FAULT #2)
Next most recent AC/HP fault
For display only
Fault 3 (FAULT #3)
Next most recent AC/HP fault
For display only
Fault 4 (FAULT #4)
Next most recent AC/HP fault
For display only
Fault 5 (FAULT #5)
Next most recent AC/HP fault
For display only
Fault 6 (FAULT #6)
Least recent AC/HP fault
For display only
Clear Fault History (CLEAR)
NO or YES
Selecting "YES" clears the fault
history
NOTE:
Consecutively repeated faults are shown a maximum of 3 times
DIAGNOSTICS
Submenu Item
Indication (for Display Only; not User Modifiable)
Model Number (MOD NUM)
Displays the air conditioner or heat pump model number
Serial Number (SER NUM)
Displays the air conditioner or heat pump serial number (Optional)
Software (SOFTWARE)
Displays the application software revision
IDENTIFICATION
Submenu Item
User Modifiable Options
Comments
Outdoor Air Temperature
(AIR TMP)
Displays the outdoor air
temperature
Sensor may or may not be available on an
air conditioner. Check air conditioner
instructions for details.
Outdoor Coil Temperature
(COIL TMP)
Displays the outdoor coil
temperature
Required for heat pump operation.
SENSORS
Submenu Ite m
User Modifiable Options
Comm ents
Cool Airflow Trim
(CL TRM)
-10% to +10% in 2% increments,
default is 0%
Selects the airflow trim amount; applies to
air conditioner only.
Cool Airflow Profile
(CL PRFL)
A, B, C, or D, default is A
Selects the airflow profile; applies to air
conditioner only.
Cool ON Delay
(CL ON)
5, 10, 20, or 30 seconds, default
is 5 seconds
Selects the indoor blower ON delay;
applies to air conditioner only.
Cool OFF Delay
(CL OFF)
30, 60, 90, or 120 seconds,
default is 30 seconds
Selects the indoor blower OFF delay;
applies to air conditioner only.
Dehumidification Select
(DEHUM)
ON or OFF (default is OFF)
Selecting "OFF" disables dehumidification;
selecting "ON" enables dehumidification;
applies to air conditioner only.
COOL SET-UP