Goodman CONDENSING UNIT HEAT PUMP Скачать руководство пользователя страница 1

I

MPORTANT

 S

AFETY

 I

NSTRUCTIONS

The following symbols and labels are used throughout this
manual to indicate immediate or potential safety hazards.  It is
the owner’s and installer’s responsibility to read and comply
with all safety information and instructions accompanying these
symbols.  Failure to heed safety information increases the risk
of personal injury, property damage, and/or product damage.

HIGH

 

VOLTAGE!

D

ISCONNECT

 

ALL

 

POWER

 

BEFORE

 

SERVICING

.

 

M

ULTIPLE

 

POWER

 

SOURCES

 

MAY

 

BE

 

PRESENT

.

 

F

AILURE

 

TO

 

DO

 

SO

 

MAY

 

CAUSE

 

PROPERTY

 

DAMAGE

,

 

PERSONAL

 

INJURY

 

OR

 

DEATH

.

WARNING

ONLY

 

INDIVIDUALS

 

MEETING

 

THE

 

REQUIREMENTS

 

OF

 

AN

 

“E

NTRY

 

L

EVEL

 

T

ECHNICIAN

AS

 

SPECIFIED

 

BY

 

THE

 

A

IR

 

C

ONDITIONING

,

 

H

EATING

 

AND

 

R

EFRIGERATION

 

I

NSTITUTE

 

(AHRI)

 

MAY

 

USE

 

THIS

 

INFORMATION

.

 

A

TTEMPTING

 

TO

 

INSTALL

 

OR

 

REPAIR

 

THIS

 

UNIT

 

WITHOUT

 

SUCH

 

BACKGROUND

 

MAY

 

RESULT

 

IN

 

PRODUCT

 

DAMAGE

,

 

PERSONAL

 

INJURY

,

 

OR

 

DEATH

.

,

 

AT

 

A

 

MINIMUM

,

 

WARNING

S

CROLL

 

EQUIPPED

 

UNITS

 

SHOULD

 

NEVER

 

BE

 

USED

 

TO

 

EVACUATE

 

THE

 

AIR

 

CONDITIONING

 

SYSTEM

.

 

V

ACUUMS

 

THIS

 

LOW

 

CAN

 

CAUSE

 

INTERNAL

 

ELECTRICAL

 

ARCING

 

RESULTING

 

IN

 

A

 

DAMAGED

 

OR

 

FAILED

 

COMPRESSOR

.

CAUTION

I

MPORTANT

 N

OTE

 

TO

 

THE

 O

WNER

 

REGARDING

 P

RODUCT

W

ARRANTY

Your warranty certificate is supplied as a separate document
with the unit installed by your contractor. Read the limited war-
ranty certificate carefully to determine what is and is not cov-
ered and keep the warranty certificate in a safe place. If you
are unable to locate the warranty certificate please contact
your installing contractor or contact customer service (877-
254-4729) to obtain a copy.
To receive the Lifetime Unit Replacement Limited Warranty
(good for as long as you own your home) and the 10-Year
Parts Limited Warranty for Amana

®

 branded products, online

registration must be completed within 60 days of installation.
Online registration is not required in California or Quebec.

CONDENSING UNIT

HEAT PUMP
INSTALLATION & SERVICE REFERENCE

© 2009-2011 Goodman Manufacturing Company, L.P.
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com -or- www.amana-hac.com
P/N: IO-348E

Date:  September 2011

To receive the Lifetime Compressor Limited Warranty (good for
as long as you own your home), the 10-Year Unit Replacement
Limited Warranty, and the 10-Year Parts Limited Warranty for
Goodman

®

 branded products, online registration must be com-

pleted within 60 days of installation.  Online registration is not
required in California or Quebec.
Complete warranty details available from your local dealer or,
for Goodman

®

 brand products, visit  www.goodmanmfg.com,

and for Amana

®

 brand products, visit www.amana-hac.com.

IMPORTANT: 

To register your Goodman

®

 brand unit, go to

www.goodmanmfg.com and click “Warranty Registration”.
Complete registration as prompted.
To register your Amana

®

 brand unit, go to www.amana-hac.com

and click “Warranty Registration”. Complete registration as
prompted.

IMPORTANT:

Product limited warranty certificates for models currently in
production can be viewed at www.goodmanmfg or www.amana-
hac.com.  If your model is not currently in production or does
not appear on the website, please contact your installing con-
tractor or contact customer service (877-254-4729) to obtain a
copy of your warranty certificate.
Each product overview page contains a Product Warranty link;
by clicking on it you will be able to view the limited warranty
coverage for that specific product. To view warranty registration
information, click on the Product Warranty text on the left navi-
gation panel on the home page of each website. The Online
Product Registration pages are located in this same section.

S

HIPPING

 I

NSPECTION

Always keep the unit upright; laying the unit on its side or top
may cause equipment damage. Shipping damage, and subse-
quent investigation is the responsibility of the carrier.  Verify
the model number, specifications, electrical characteristics,
and accessories are correct prior to installation. The distribu-
tor or manufacturer will not accept claims from dealers for trans-
portation damage or installation of incorrectly shipped units.

C

ODES

 & R

EGULATIONS

This product is designed and manufactured to comply with
national codes. Installation in accordance with such codes
and/or prevailing local codes/regulations is the responsibility
of the installer.  The manufacturer assumes no responsibility
for equipment installed in violation of any codes or regulations.

 

is a registered trademark of Maytag Corporation or its related companies and is used under

license to Goodman Company, L.P., Houston, TX.  All rights reserved.

 

Содержание CONDENSING UNIT HEAT PUMP

Страница 1: ...the 10 Year Unit Replacement Limited Warranty and the 10 Year Parts Limited Warranty for Goodman branded products online registration must be com pleted within 60 days of installation Online registrat...

Страница 2: ...for the unit s is the angle to obstructions Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clear ance Corner in...

Страница 3: ...ant tubing clean and dry prior to and during installation Tubing should always be cut square keeping ends round and free from burrs Clean the tubing to prevent contamination Do NOT let refrigerant lin...

Страница 4: ...ean any copper oxide present from the inside of the refrigerant lines and spread it throughout the system This may cause a blockage or failure of the metering device 3 After brazing quench the joints...

Страница 5: ...CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK WIRING MUST CONFORM WITH NEC OR CEC AND ALL LOCAL CODES UNDERSIZED WIRES COULD CAUSE POOR EQUIPMENT PERFORMANCE EQUIPMENT DAMAGE O...

Страница 6: ...ING THERMOSTAT 1 2 R C B L U E R E D W H T B L K INDOOR UNIT Communicating Thermostat with Low Voltage Wires to Heat Pump NOTE If the heat pump unit is wired in the communicating mode together with th...

Страница 7: ...L R G W BL BR G W2 C R G W BL INDOOR UNIT 18 GA 7 WIRE NEEDED WHEN TWO OT ARE USED SEE NOTE 4 RED GREEN WHITE BLUE C W2 O Y1 Y2 G R E O Y1 Y2 HEAT PUMP W2 C R TYP H P ROOM THERMOSTAT 18 GA 7 WIRE SYST...

Страница 8: ...or 10 minutes for fixed orifices and 20 minutes for expansion valves CHARGE VERIFICATION REFRIGERANT UNDER PRESSURE DO NOT OVERCHARGE SYSTEM WITH REFRIGERANT DO NOT OPERATE UNIT IN A VACUUM OR AT NEGA...

Страница 9: ...e cleared by depressing the button for greater than five seconds Consecutively repeated faults are displayed a maximum of three times Refer to the fault code definitions at the end of this manual for...

Страница 10: ...ooling Heating M odels CTK0 AAWIRING NOTE Refer to section Electrical Connections High Voltage Connections for 208 230 volt line connections to the air conditioner or heat pump NOTE A removable plug c...

Страница 11: ...first sub menu is then displayed See tables below for listing of furnace sub menus Touch the or _ to step through the list of submenus and view settings If a setting can be adjusted _ and keys will a...

Страница 12: ...itioner or heat pump model number Serial Number SER NUM Displays the air conditioner or heat pump serial number Optional Software SOFTWARE Displays the application software revision IDENTIFICATION Sub...

Страница 13: ...econds Selects the indoor blower heat OFF delay applies to heat pump only Defrost Interval DEFROST 30 60 90 or 120 minutes default is 30 minutes Selects the time interval between defrosts applies to h...

Страница 14: ...t the network may arise The integrated control module has some on board tools that may be used to trouble shoot the network These tools are red communications LED green receive Rx LED and learn button...

Страница 15: ...blocks are securely twisted together prior to inserting into terminal block Verify heat pump installation type legacy traditional or communicating Check data 1 data 2 voltages Rapid Flashing Normal ne...

Страница 16: ...ED SUCTION PRESSURE TEMPERATURE CHART SATURATED SUCTION TEMPERATURE F LIQUID PRESSURE PSIG R 22 R 410A 200 101 70 210 105 73 220 108 76 225 110 78 235 113 80 245 116 83 255 119 85 265 121 88 275 124 9...

Страница 17: ...Faulty Evap Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortage of Refrigerant Test For Leaks Add Refrig...

Страница 18: ...e indicated code 6 Flashes ON OFF OFF x Board miss operation INTERNAL FAULT EE x Compressor relay contacts welded x Replace control x Turn power OFF prior to repair x Replace with correct replacement...

Страница 19: ...emory card x Error code will be cleared once data is loaded Applies only to fully communicating system using ComfortNet thermostat x Air conditioner heat pump fails to operate x Air conditioner heat p...

Страница 20: ...indoor blower motor repair replace as needed x Check indoor thermostat setting x Turn power OFF prior to repair x Fault will clear after 30 consecutive normal cycles x Fault may be cleared by cycling...

Страница 21: ...tdoor fan motor capacitor replace as needed x Turn power OFF prior to repair x Replace with correct replacement part s x Compressor and outdoor fan are off x Low pressure switch trip 3 times within sa...

Страница 22: ...ompressor repair replace as needed x Check compressor wiring repair replace as needed x Turn power OFF prior to repair x Fault will clear after 1 normal cycle x Fault may be cleared by cycling 24VAC t...

Страница 23: ...all x Open Run Circuit Lockout OPEN RUN LOCK 07 x Compressor run winding is open x Compressor not properly wired to control x Faulty compressor wiring x Check compressor repair replace as needed x Che...

Страница 24: ...prior to repair x Fault will clear if secondary voltage rises above 21VAC x Replace with correct replacement part s x Compressor is off x Integrated control module diagnostic status LED s display the...