SECTION V: SYSTEM OPERATION

ANTI-SHORT CYCLE DELAY

The control includes a five-minute anti-short cycle delay (ASCD) timer
to prevent the compressor from short cycling after a power or thermo-
stat signal interruption. The ASCD timer is applied when the control is
first powered from the indoor unit thermostat and immediately following
the completion of a compressor run cycle. The compressor and the out-
door fan will not operate during the five minutes that the timer is active. 

The ASCD timer can be bypassed by connecting the TEST terminals
for three seconds while the thermostat is calling for compressor opera-
tion (Y input signal energized).

LOW VOLTAGE DETECTION

The control monitors the transformer secondary (24 VAC) voltage and
provides low voltage protection for the heat pump and its components.
In particular, the control prevents contactor chatter during low voltage
conditions. If the voltage drops below approximately 19 VAC, the con-
trol will continue to energize any relays that are already energized but
will not energize any additional relays until the voltage level increases.
If the voltage drops below approximately 16 VAC, the control will imme-
diately de-energize the relay outputs and will not energize any relays
until the voltage level increases.

TEST INPUT

The control includes a TEST input connector that can be used for vari-
ous testing functions during installation and service. The TEST input
connector is shown in Figures 11 & 12. The following table summarizes
the behavior of the control when the two TEST pins are connected.
More detailed descriptions of the various functions are included in other
sections of this document.

FAULT CODE DISPLAY

X/L Output

The X/L terminal of the heat pump control is typically connected to the
X/L input of the room thermostat. The thermostat uses this signal to
notify the homeowner of a problem with the heat pump using an LED or
LCD display. When the control energizes the X/L terminal, the thermo-
stat displays the flash code so the homeowner can see it.

When the control locks out the compressor because of a pressure
switch lockout, it will energize the X/L output as shown in Table 3. The
control has a three second delay between fault code flashes.

If the conditions above exist during cooling mode, the system could be
in the loss of charge condition.

DEFROST OPERATION

Time/Temperature Defrost (13 Seer 2-5 Ton)

The defrost control is a time/temp. control which includes a field-select-
able (tap located at board edge) time period between defrost cycle (30,
60, and 90 minutes). The jumper is factory set at 60 minutes. See Fig-
ure 13.

The electronic timer and the defrost cycle will start only when the con-
tactor is energized and the defrost thermostat is closed. The defrost
thermostat is closed when the liquid temperature falls below approxi-
mately 31° F.

The defrost mode is identical to the cooling mode except that the out-
door fan motor stops and the first stage of heat is turned on through W1
/ 66 to continue warming the conditioned space.

The defrost cycle will be terminated when the defrost thermostat is
opened at 55° F or 10 minutes of compressor accumulated run time,
whichever comes first. 

Demand Defrost (13 Seer 1.5 ton, 14.5 Seer 1.5-4 Ton)

The control maintains proper airflow through the outdoor coil during
heating operation by melting frost and ice that may form on the coil.
Frost may accumulate unevenly in different sections of the coil because
of the arrangement of the refrigeration circuit within the coil. The control
may initiate a defrost cycle even when the coil is not completely cov-
ered with frost. This is normal operation.

The control regulates the defrost operation of the heat pump based on
accumulated compressor run time, outdoor coil temperature, and out-
door ambient temperature. The control will cause the unit to operate in
the normal heating mode until it determines that a defrost cycle is
needed.

All defrost timings are based on accumulated compressor run time.

Operation

The defrost mode is equivalent to the cooling mode except that the out-
door fan motor is de-energized. The control shall do the following to ini-
tiate a defrost cycle.

De-energize the outdoor fan.

Energize the reversing valve.

Energize the auxiliary heat output through the W1/66 terminal.

Begin the maximum defrost cycle length timer.

If the call for heating (Y) is removed from the control during the defrost
cycle, it will terminate the defrost cycle and de-energize the compres-
sor. The control will also stop the defrost cycle length timer but not reset
it. When the control receives another call for heating, it will restart the
defrost cycle and the timer at the point at which the call for heating was
removed. This will happen only if the liquid line temperature conditions
allow defrost to occur.

Defrost Curves

The control uses a set of defrost curve parameters that are selected
using the defrost curve selection jumper. The location of the defrost
curve selection jumper is shown in Figure 13. Table 4 shows the jumper
position that is appropriate for each heat pump model. Jumper position
4 is not used and the control will not allow the compressor to operate
when the jumper is in this position.

TABLE 2: 

TEST Input Functionality

Duration of Connection (seconds)

Control Behavior

Time-Temp

Demand Defrost

Less than 2

Less than 2

No response

2-9

2-6

Bypass ASCD. If Y is present 

and pressure switch is closed, 

contactors will be energized.

Clear lockout

More than 9

More than 6

Initiate defrost cycle. (Demand 

only: Energize X/L with active 

defrost curve flash code)

Connection removed

Terminate defrost as normal

Connection not removed

Continue defrost cycle (Demand 

only: and X/L flash code) until 

TEST connection removed.

TABLE 3: 

X/L Output Categories

Condition

X/L

Pressure Switch lockout - last mode of operation was heating 2 flashes
Pressure Switch lockout - last mode of operation was defrost 3 flashes
Incorrect Defrost Curve - jumper selection

On

The defrost thermostat delay will make the coil temperature about
75-80° F. Please note that the timer will stop the circuit when R to Y
is disconnected.

NOTICE

Содержание CHJD Series

Страница 1: ...may need to be changed for some indoor out door unit combinations elevation differences or total line lengths Refer to Application Data covering General Piping Recommendations and Refrigerant Line Length Part Number 247077 SECTION II SAFETY This is a safety alert symbol When you see this symbol on labels or in manuals be alert to the potential for personal injury Understand and pay particular atte...

Страница 2: ...erformed in order to insure proper system operation and performance Line set change out is also recommended 1 Change out of the indoor coil to an approved R 410A coil con densing unit combination with the appropriate metering device 2 Change out of the line set when replacing an R 22 unit with an R410 A unit is highly recommended to reduce cross contamina tion of oils and refrigerants 3 If change ...

Страница 3: ...s necessary If soft copper must be used care must be taken to avoid sharp bends which may cause a restriction 2 The lines should be installed so that they will not obstruct service access to the coil air handling system or filter 3 Care must also be taken to isolate the refrigerant lines to minimize noise transmission from the equipment to the structure 4 The vapor line must be insulated with a mi...

Страница 4: ...rigerant piping connections including the service port flare caps to be sure they are leak tight DO NOT OVER TIGHTEN between 40 and 60 inch lbs maximum 9 Evacuate the vapor line evaporator and the liquid line to 500 microns or less 10 Replace cap on service ports Do not remove the flare caps from the service ports except when necessary for servicing the system 11 Release the refrigerant charge int...

Страница 5: ...por line as follows a Hand tighten the 1 4 SAE nut to the Schrader fitting and an additional 1 3 turn to seal 7 Install the TXV bulb to the vapor line near the equalizer line using the bulb clamp s furnished with the TXV assembly Ensure the bulb is making maximum contact a Bulb should be installed on a horizontal run of the vapor line if possible On lines under 7 8 O D the bulb may be installed on...

Страница 6: ...fic charging charts are provided on the access panel of the unit SECTION VIII ELECTRICAL CONNECTIONS GENERAL INFORMATION GROUNDING Check the electrical supply to be sure that it meets the values specified on the unit nameplate and wiring label Power wiring control low voltage wiring disconnect switches and over current protection must be supplied by the installer Wire size should be sized per NEC ...

Страница 7: ...late Contactor Dual Run Fan Capacitor Fan Relay Defrost Control Board Ground Lug Fingered Bushing Low Voltage Box Reversible High Voltage Conduit Plate Contactor Fan Capacitor To eliminate erratic operation seal the hole in the wall at the ther mostat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat A Start Assist Kit is available and recommended for l...

Страница 8: ...KCASE HEATER If this unit is equipped with a crankcase heater for the compressor a warning label with an adhesive back is supplied in the unit installation instruction packet This label should be attached to the field supplied disconnect switch where it will be easily seen In order to energize the crankcase heater set the indoor cooling ther mostat to the OFF position Close the line power disconne...

Страница 9: ...58 164 73 211 88 266 103 331 118 407 59 167 74 214 89 270 104 336 119 412 FIGURE 10 Heat Pump Flow Diagram CHARGE COMPENSATOR Empty in cooling full in heating Not included in all Units FIELD CONNECTED LINE INDOOR COIL OUTDOOR COIL 4 WAY REVERSING VALVE FILTER DRYER Solid core SUCTION ACCUMULATOR LIQUID SENSOR COMPRESSOR BI FLOW TXV CHECK VALVE Cooling BI FLOW TXV CHECK VALVE OR ORIFICE Heating FIG...

Страница 10: ...d the first stage of heat is turned on through W1 66 to continue warming the conditioned space The defrost cycle will be terminated when the defrost thermostat is opened at 55 F or 10 minutes of compressor accumulated run time whichever comes first Demand Defrost 13 Seer 1 5 ton 14 5 Seer 1 5 4 Ton The control maintains proper airflow through the outdoor coil during heating operation by melting fr...

Страница 11: ...be bypassed and the compressor and the W1 66 terminal to auxiliary heat will be energized When the TEST inputs are used to force a defrost cycle the control will ignore the state of the liquid line temperature and outdoor ambient tem perature inputs The coil does not have to be cold and the outdoor tem perature does not have to be within a certain range for the heat pump to be forced into a defros...

Страница 12: ...de energize the compres sor and energize the X L output with the appropriate flash code The control will reset the soft lockout condition when any of the follow ing occur following removal of the fault condition 1 Power is cycled to the R or Y inputs of the control This will cause the soft lockout condition to be reset when the thermostat is satis fied or when the thermostat is set to SYSTEM OFF a...

Страница 13: ...835961 UIM B 0412 Johnson Controls Unitary Products 13 SECTION VII WIRING DIAGRAM FIGURE 14 Wiring Diagram Single Phase Demand Defrost ...

Страница 14: ...ANGE PNK PINK PUR PURPLE RED RED WHT WHITE YEL YELLOW BLK BLK BRN PNK YEL PNK HPS HTS LPS BRN PNK YEL PNK YEL PNK SEE UNIT INSTALLATION INSTRUCTIONS FOR LOW VOLTAGE TERMINATIONS COND FAN X L PUR RED DEFROST CONTROL BLK WHT BRN BLK REV VALVE YEL ORG RV R C Y O W W1 66 PRES SWITCH DFST T STAT M BRN PNK YEL PNK BLK GRY LS BLU DANGER SHOCK HAZARD TURN OFF ELECTRICAL POWER BEFORE SERVICING TO PREVENT P...

Страница 15: ...835961 UIM B 0412 Johnson Controls Unitary Products 15 FIGURE 16 Wiring Diagram Three Phase Demand Defrost 407154 ...

Страница 16: ...LK ORG ORG B L K 4 6 0 V BLK 460V B L K 4 6 0 V BLK 460V RED BRN WHT BLK 208 230 BLK 208 230 BRN PNK YEL PNK HPS HTS LPS BRN PNK YEL PNK YEL PNK SEE UNIT INSTALLATION INSTRUCTIONS FOR LOW VOLTAGE TERMINATIONS COND FAN X L PUR RED DEFROST CONTROL BLK WHT BRN BLK REV VALVE YEL ORG RV R C Y O W W1 66 PRESS SWITCH DFST T STAT M BRN PNK GRY BLK YEL 460V BLK 460V LS BLU DANGER SHOCK HAZARD TURN OFF ELEC...

Отзывы: