Goodman ANSI Z21.47CSA-2.3 Скачать руководство пользователя страница 4

4

System design and installation should also, where applicable,
follow information presented in accepted industry guides such
as the ASHRAE Handbooks. The manufacturer assumes no
responsibility for equipment installed in violation of any code
or regulation. The mechanical installation of the packaged
roof top units consists of making final connections between
the unit and building services; supply and return duct con-
nections; and drain connections (if required).  The internal
systems of the unit are completely factory-installed and tested
prior to shipment.

Units are generally installed on a steel roof mounting curb
assembly which has been shipped to the job site for installa-
tion on the roof structure prior to the arrival of the unit.  The
model number shown on the unit’s identification plate identi-
fies the various components of the unit such as refrigeration
tonnage, heating input and voltage.

Carefully inspect the unit for damage including damage to
the cabinetry.  Any bolts or screws which may have loosened
in transit must be re-tightened.  In the event of damage, the
receiver should:

1. Make notation on delivery receipt of any visible

damage to shipment or container.

2. Notify carrier promptly and request an inspection.
3. In case of concealed damage, carrier should be

notified as soon as possible-preferably within 5 days.

4. File the claim with the following supporting documents:

a. Original Bill of Lading, certified copy, or indemnity

bond.

b. Original paid freight bill or indemnity in lieu thereof.
c. Original invoice or certified copy thereof, showing

trade and other discounts or reductions.

d. Copy of the inspection report issued by carrier

representative at the time damage is reported to the
carrier. The carrier is responsible for making prompt
inspection of damage and for a thorough
investigation of each claim. The distributor or
manufacturer will not accept claims from dealers for
transportation damage.

NOTE:

 When inspecting the unit for transportation damage,

remove all packaging materials. Recycle or dispose  of the
packaging material according to local codes.

P

RE

-I

NSTALLATION

 C

HECKS

Carefully read all instructions for the installation prior to in-
stalling unit. Ensure each step or procedure is understood
and any special considerations are taken into account be-
fore starting installation.  Assemble all tools, hardware and
supplies needed to complete the installation. Some items may
need to be purchased locally.

UNIT LOCATION

T

O

 

PREVENT

 

POSSIBLE

 

EQUIPMENT

 

DAMAGE

,

 

PROPERTY

 

DAMAGE

,

 

PERSONAL

 

INJURY

 

OR

 

DEATH

,

 

THE

 

FOLLOWING

 

BULLET

 

POINTS

 

MUST

 

BE

 

OBSERVED

 

WHEN

 

INSTALLING

 

THE

 

UNIT

.

WARNING

IMPORTANT NOTE: 

Remove wood shipping rails prior to

installation of the unit.  

See important note under Roof Curb

Installation Only.

A

LL

 I

NSTALLATIONS

:

I

MPORTANT

 N

OTE

Unit should be energized 24 hours prior

to compressor start up to ensure crankcase heater has
sufficiently warmed the compressors. Compressor dam-
age may occur if this step is not followed.

NOTE:

Appliance is shipped from factory for vertical duct

application.

Proper installation of the unit ensures trouble-free operation.
Improper installation can result in problems ranging from
noisy operation to property or equipment damages, danger-
ous conditions that could result in injury or personal property
damage and could void the warranty. Give this booklet to the
user and explain it’s provisions. The user should retain these
instructions for future reference.

For proper flame pattern within the heat exchanger
and proper condensate drainage, the unit must be
mounted level.

The flue outlet must be at least 12 inches from any
opening through which flue gases could enter a
building, and at least three feet above any forced air
inlet located within ten feet. The economizer/manual
fresh air intake/motorized fresh air intake and
combustion air inlet mounted on the unit are not
affected by this restriction.

To avoid possible corrosion of the heat exchanger,
do not locate the unit in an area where the outdoor air
(i.e. combustion air for the unit) will be frequently
contaminated by compounds containing chlorine or
fluorine. Common sources of such compounds include
swimming pool chemicals and chlorine bleaches, paint
stripper, adhesives, paints, varnishes, sealers, waxes
(which are not yet dried) and solvents used during
construction and remodeling. Various commercial and
industrial processes may also be sources of chlorine/
fluorine compounds.

To avoid possible illness or death of the building
occupants, do NOT locate outside air intake device
(economizer, manual fresh air intake, motorized fresh
air intake) too close to an exhaust outlet, gas vent
termination, or plumbing vent outlet. For specific
distances required, consult local codes.

Allow minimum clearances from the enclosure for fire
protection, proper operation, and service access (see
unit clearances). These clearances must be
permanently maintained.

Содержание ANSI Z21.47CSA-2.3

Страница 1: ...tion Manual Observe all safety warnings During installation or repair caution is to be observed It is your responsibility to install the product safely and to educate the customer on its safe use This Forced Air Central Unit Design Complies With Requirements Embodied in The American National Standard National Standard of Canada Shown Below ANSI Z21 47 CSA 2 3 Central Furnaces C US 2010 Goodman Man...

Страница 2: ... PHONE FOLLOW THE GAS SUPPLIER S INSTRUCTIONS IF YOU CANNOT REACH YOUR GAS SUPPLIER CALL THE FIRE DEPARTMENT INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER WHAT TO DO IF YOU SMELL GAS WARNING DO NOT CONNECT TO OR USE ANY DEVICE THAT IS NOT DESIGN CERTIFIED BY GOODMAN FOR USE WITH THIS UNIT SERIOUS PROPERTY DAMAGE PERSONAL INJURY REDUCED UNIT ...

Страница 3: ...ONOXYDE DE CARBONE Si ce compartiment n est pas ferme en tout temps sauf en cas de reparation il y a risque d empoisonnement ou monoxyde de carbon ou de mort Ce compartiment doit être ferme sauf au moment de l entretien PELIGRO MONOXIDO DE CARBONO TOXICO El fracaso de no mantener compartimiento cerrado menos durante atender podria tener como resultado envenar de monoxido de carbona o muerte Este c...

Страница 4: ... hardware and supplies needed to complete the installation Some items may need to be purchased locally UNIT LOCATION TO PREVENT POSSIBLE EQUIPMENT DAMAGE PROPERTY DAMAGE PERSONAL INJURY OR DEATH THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT WARNING IMPORTANT NOTE Remove wood shipping rails prior to installation of the unit See important note under Roof Curb Installation Onl...

Страница 5: ... from the furnace flue discharge to any adjacent public walkways adjacent buildings building openings or openable windows must be maintained in accordance with the latest edition of the National Fuel Gas Code ANSI Z223 1 Minimum horizontal clearance of 48 from the furnace flue discharge to any electric meters gas meters regulators and relief equipment is required UNIT PRECAUTIONS Do not stand or w...

Страница 6: ...support must be determined prior to locating and mounting the curb and package unit Ductwork must be constructed using industry guidelines The duct work must be placed into the roof curb before mounting the package unit Our full perimeter curbs include duct connection frames to be assembled with the curb Cantilevered type curbs are not available from the factory Curb insulation cant strips flashin...

Страница 7: ...PREVENT DAMAGE TO THE UNIT CAUTION Provisions for forks have been included in the unit base frame No other fork locations are approved TO PREVENT POSSIBLE EQUIPMENT DAMAGE PROPERTY DAMAGE PERSONAL INJURY OR DEATH THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT WARNING Unit must be lifted by the four lifting holes located at the base frame corners Lifting cables should be atta...

Страница 8: ...unit Check for proper alignment and orientation of supply and return openings with duct RIGGING REMOVAL TO PREVENT DAMAGE TO THE UNIT DO NOT ALLOW CRANE HOOKS AND SPREADER BARS TO REST ON THE ROOF OF THE UNIT CAUTION Remove spreader bars lifting cables and other rigging equip ment ELECTRICAL WIRING HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MA...

Страница 9: ...tribution in accordance with the unit data plate The unit must be electrically grounded in accordance with local codes or in the absence of local codes with the latest edition of the National Electrical Code ANSI NFPA 70 A ground lug is provided for this purpose Size grounding conductor in accordance with Table 250 95 of the National Electrical Code Do not use the ground lug for connecting a neutr...

Страница 10: ...D INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER WARNING IMPORTANT NOTE This unit is factory set to operate on natural gas at the altitudes shown on the rating plate TO PREVENT PROPERTY DAMAGE PERSONAL INJURY OR DEATH WHEN EITHER USING PROPANE GAS ALONE OR AT HIGHER ALTITUDES OBTAIN AND INSTALL THE PROPER CONVERSION KIT S FAILURE TO DO SO CAN RESULT IN UNSATISFACTORY OPERATION AND OR EQUIPMENT DAMAG...

Страница 11: ... to the gas valve to keep it from turning 6 Install a manual shut off valve in a convenient location within six feet of unit between the meter and the unit 7 Tighten all joints securely 8 The unit must be connected to the building piping by one of the following methods Rigid metallic pipe and fittings Semirigid metallic tubing and metallic fittings Aluminum alloy tubing must not be used in exterio...

Страница 12: ...ust be within 9 7 10 3 inches w c for high fire and within 6 7 7 3 inches w c low fire at the manifold with all gas appli ances in operation Maintaining proper gas pressure depends on three main factors 1 Vaporization rate which depends on a temperature of the liquid and b wetted surface area of the container or containers 2 Proper pressure regulation 3 Pressure drop in lines between regulators an...

Страница 13: ...e THIS UNIT AND ITS INDIVIDUAL SHUTOFF VALVE MUST BE DISCONNECTED FROM THE GAS SUPPLY SYSTEM DURING ANY PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF 1 2 PSIG 13 8 W C WARNING THIS UNIT MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY CLOSING ITS INDIVIDUAL MANUAL SHUTOFF VALVE DURING ANY PRESSURE TESTING EQUAL TO OR LESS THAN 1 2 PSIG CAUTION 7 There must be no obstruction t...

Страница 14: ...de ambient rises above 55 F TOOLS REQUIRED Refrigeration gauge and manifold Voltmeter Clamp on ammeter Ohmmeter Test lead Minimum 16 AWG with insulated alligator clips Manometer for verifying gas pressure 0 to 20 w c Air temperature measuring device General refrigeration mechanics tools TEMPORARY HEATING OR COOLING If the unit is to be used for temporary heating or cooling a Startup Adjustments an...

Страница 15: ...emove filter section access panels and check that filters are properly installed Note airflow arrows on filter frames BEARING CHECK Prior to energizing any fans check and make sure that all setscrews are tight so that bearings are properly secured to shafts SET EVAPORATOR FAN RPM Actual RPM s must be set and verified with a tachometer or strobe light Refer to Appendices A and B for basic unit fan ...

Страница 16: ...rmined and repaired prior to resetting this manual reset control TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION A QUALIFIED SERVICER MUST INVESTIGATE THE REASON FOR THE ROLLOUT PROTECTION DEVICE TO OPEN BEFORE MANUALLY RESETTING THE ROLLOUT PROTECTION DEVICE WARNING Secondary Limit Control The secondary limit control is located on the side of the blower scroll assembly ...

Страница 17: ... 3600 34 106 000 BTU per Hour NOTE BTU content of the gas should be obtained from the gas supplier This measured input must not be greater than shown on the unit rating plate 4 Relight all other appliances turned off in step 1 Be sure all pilot burners are operating Main Burner Flame Check Flames should be stable soft and blue dust may cause or ange tips but they must not be yellow and extending d...

Страница 18: ...wall thermostat 11 Open disconnect switch Reconnect the field thermostat wire at terminal R on terminal block TB1 REFRIGERATION PERFORMANCE CHECK Under normal summertime full load operating conditions superheat should be between 8 F and 12 F and sub cooling measured at the condenser outlet should be 15 F nominal A 25 F to 35 F temperature difference should exist between the entering condenser air ...

Страница 19: ...n the system switch in the HEAT or AUTO position and the fan switch in the AUTO position the thermostat will close the circuit between unit terminals R and W R W when the temperature falls below the thermostat setting 2 D1 on IIC energizes relay IDMR 3 Relay IDMR energizes the ventor motor IDM 4 Operation of the vent motor closes the pressure switch PS located in the burner compartment the control...

Страница 20: ... control will recycle for four 4 consecu tive ignition attempts five attempts total before locking out The diagnostic fault code is 1 flash for a lockout due to failed ignition attempts or flame dropouts The integrated control will automatically reset after one hour or it can be reset by removing the thermostat signal or disconnecting the electri cal power supply for over five seconds If the diagn...

Страница 21: ...t The input rate can be calculated by using the formula INPUT Btu Hr 3600 x HV T WHERE HV Heating value of fuel Btu ft of gas T Time in seconds per ft of gas flow as read from gas meter 3 3 Adjust input rate by varying the adjustment of the gas pres sure regulator on the gas valve All adjustments must be made with furnace operating at high fire and at normal operating temperature Clockwise P rotat...

Страница 22: ...NSTALLER SERVICE AGENCY OR THE GAS SUPPLIER WARNING SHEET METAL PARTS SCREWS CLIPS AND SIMILAR ITEMS INHERENTLY HAVE SHARP EDGES AND IT IS NECESSARY THAT THE INSTALLER AND SERVICE PERSONNEL EXERCISE CAUTION CAUTION Preventive maintenance is the best way to avoid unneces sary expense and inconvenience Have this system inspected at regular intervals by qualified service personnel at least twice a ye...

Страница 23: ...ecessary for continued safe operation Par ticular attention should be given to deterioration from corro sion or other sources This examination is accomplished in the following manner 1 Disconnect power to the unit and remove furnace section access panel 2 Remove burner assembly a Disconnect the three wires from the gas valve after noting which wires are connected to each terminal b Disconnect wire...

Страница 24: ...8 5982 1 94 0 4 7079 3 20 6623 2 76 6161 2 34 5706 1 98 5271 1 66 0 6 6903 3 32 6405 2 83 5923 2 41 5434 2 02 4949 1 68 0 8 6717 3 42 6198 2 92 5668 2 45 5152 2 05 1 0 5975 2 99 5418 2 51 1 2 5147 2 55 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 0 2 9359 4 92 8991 3 79 8621 3 54 8188 3 27 7826 3 04 0 4 9018 3 18 8632 4 39 8251 3 39 7867 3 15 7363 2 85 6992 2 63 0 6 8279 2 96 7879 3 86 ...

Страница 25: ...BHP 1 0 6690 3 69 6008 3 02 5321 2 43 1 2 6653 3 95 5922 3 22 5182 2 58 1 4 6634 2 80 5857 3 44 5056 2 74 1 6 6638 4 55 5808 2 43 4948 2 91 1 8 6683 4 93 5784 3 95 4855 2 05 2 0 5803 4 27 4788 3 32 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 1 0 9001 6 83 8394 6 01 7797 4 78 7227 4 28 1 2 8891 6 83 8262 6 15 7632 5 35 7012 4 20 1 4 8811 6 86 8148 6 15 7495 5 48 6841 4 71 1 6 8065 6 19 ...

Страница 26: ...L DATA ID MOTOR APPL COMPRESSOR ea OD FAN MOTORS ea ID FAN MOTOR VOLTAGE LIMITATIONS VOLTAGE NAMEPLATE MODELS MIN MAX Qty RLA LRA Qty RLA LRA Qty HP RLA HP FLA 208 230 60 3 187 253 1 29 5 195 0 1 25 0 164 0 3 1 3 2 40 BD STD STATIC 5 0 12 7 460 60 3 414 506 1 14 7 95 0 1 12 2 100 0 3 1 3 1 20 BD STD STATIC 5 0 6 4 575 60 3 518 633 1 12 2 80 0 1 9 0 78 0 3 1 3 0 90 BD STD STATIC 5 0 5 1 SMALLER COM...

Страница 27: ...27 APPENDIX C UNIT DIMENSIONS VERTICAL DISCHARGE TOP VIEW 21 60 7 48 22 B C D A Model A B C D 15 Ton 20 Ton 133 1 2 88 7 32 50 9 32 5 5 32 ...

Страница 28: ...D RD BR BR BL BL BL PU PU PU PU PU PU PU GR BL BL BL PK BR BR BR BR BR YL YL YL YL YL YL RD RD RD RD BL BL BL BL WH WH WH WH 0140L00954 REV A OR OR OR OR 3 1 VMR 4 6 RD BK BK BK RD BK OR RD BK OR OR BK BK RD OR 4 2 1 6 YL BL CCH1 CCHR2 PU BK BK BK RD OR BL SEE NOTE 2 T2 T1 CC 2 L2 L1 T3 L3 T2 T1 CC 1 L2 L1 T3 L3 T2 T1 L2 L1 T3 L3 T2 T1 BC L2 L1 T3 L3 POWER SUPPLY 208V 240V 3 ph 60 Hz SEE NOTE 4 T1...

Страница 29: ... IGN FS VMR IIC BC 5 4 7 8 6 9 1 2 3 TR 24V TB1 TB1 2 PLF L1 SUPPLY VOLTAGE 208 240 3 60 L2 L3 1 3 1 3 RCCF1 CC1 T3 COMP1 T2 F CM1 EM CC1 T1 C CC1 BC T2 BC BC RCCF3 CC2 T3 T1 COMP2 T2 F CM3 CC2 T1 C CC2 T3 T2 VM VENT MOTOR RELAY VENT MOTOR TRANSFORMER TERMINAL BLOCK 24V SIGNAL ROLLOUT SWITCH PRESSURE SWITCH FEMALE PLUG CONNECTOR LIMIT SWITCH LOW PRESSURE SWITCH IGNITOR INTEGRATED IGNITION CONTROL ...

Страница 30: ...GE 1 24V 3 1 L2 UNUSED COOL HEAT DI FS L1 4 5 6 2 3 1 ECON 11 8 12 9 7 10 IIC LS 3 2 1 9 6 8 7 4 5 R GV W1 C Y1 Y2 G ALS PS RS GRND FS IGN W2 LPS1 LPS2 HPS1 HPS2 VMR S1 S2 TB1 TO THERMOSTAT TB1 SEE NOTE 5 RD RD WH BK BK BK OR OR RD RD BK BK OR RD YL BK RD YL BK RD YL BK RD YL BK RD RD RD BK RD BK BK BK BK BK PU PU PU PU PU PU PU PU BR BR BR BR BR BR BR BR RD RD WH WH WH BK OR RD RD BK RD OR BL BL ...

Страница 31: ...OMPARTMENT REMOVE MALE PLUG AND TO BLOWER HOUSING IN RETURN AIR 2 ACCESSORY ECONOMIZER PLUG ADJACENT 4 USE COPPER CONDUCTORS ONLY USE NEC CLASS 2 WIRE 3 L1 AND L2 ON IIC CONTROL IS 24V INPUT HIGH VOLTAGE OPTIONAL LOW VOLTAGE LINE VOLTAGE FIELD WIRING LOW VOLTAGE HIGH VOLTAGE FIELD WIRING THERMOSTAT FACTORY WIRING 0140L00957 REV A COMPONENT LEGEND Y1 Y Y2 RCCF2 F CM2 C T2 T1 T3 T3 T1 T1 TERMINAL BL...

Страница 32: ...32 2010 Goodman Manufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com www amana hac com ...

Отзывы: