NOTE:

The gas connection size at the unit does NOT

establish the size of the supply line.

3. These units are designed for either natural or  propane

(LP) gas and are specifically constructed at the factory
for only one of these fuels. The fuels are NOT
interchangeable. However, the furnace can be
converted in the field from natural gas to LP gas with
the appropriate factory kit (see unit Technical Manual
for the appropriate kit). Only a qualified contractor,
experienced with natural and propane gas systems,
should attempt conversion. Kit instructions must be
followed closely to assure safe and reliable unit
operation.

4. With all units on a common line operating under full

fire, natural gas main supply pressure should be
adjusted to approximately 7.0" w.c., measured at the
unit gas valve. If the gas pressure at the unit is greater
than 10.5" w.c., the contractor must furnish and install
an external type positive shutoff service pressure
regulator. The unit will not function satisfactorily if
supply gas pressure is less than 5.5" w.c. or greater
than 10.5" w.c..

NOTE:

A minimum horizontal distance of 48"

between the regulator and the furnace flue discharge
is required.

5. With all units on a common line operating under full

LP gas main supply pressure should be at least 11.0"
w.c. and must be no greater than 14.0" w.c., measured
at the unit gas valve. Unit will not function satisfactorily
if supply gas pressure is less than 11.0" w.c. or greater
than 14.0" w.c..

6. All pipe connections should be sealed with a pipe

thread compound, which is resistant to the fuel used
with the furnace. A soapy water solution should be
used to check all joints for leaks. A 1/8" NPT plugged
tap is located on the entering side of the gas valve for
test gauge connection to measure supply (main) gas
pressure. Another 1/8" tap is provided on the side of
the manifold for checking manifold pressure.

T

HIS

 

UNIT

 

AND

 

ITS

 

INDIVIDUAL

 

SHUTOFF

 

VALVE

 

MUST

 

BE

 

DISCONNECTED

 

FROM

 

THE

 

GAS

 

SUPPLY

 

SYSTEM

 

DURING

 

ANY

 

PRESSURE

 

TESTING

 

OF

 

THAT

 

SYSTEM

 

AT

 

TEST

 

PRESSURES

 

IN

 

EXCESS

 

OF

 

1/2

 

PSIG

 

(13.8”

 

W

.

C

.).

WARNING

T

HIS

 

UNIT

 

MUST

 

BE

 

ISOLATED

 

FROM

 

THE

 

GAS

 

SUPPLY

 

PIPING

 

SYSTEM

 

BY

 

CLOSING

 

ITS

 

INDIVIDUAL

 

MANUAL

 

SHUTOFF

 

VALVE

 

DURING

 

ANY

 

PRESSURE

 

TESTING

 

EQUAL

 

TO

 

OR

 

LESS

 

THAN

 

1/2

 

PSIG.

CAUTION

7. There must be no obstruction to prevent the flow of

combustion and ventilating air. A vent stack is not
required and must never be used. The power ventor
will supply an adequate amount of combustion air as
long as the air passageways are kept free of any
obstructions and the recommended external unit
clearances are maintained.

CIRCULATING AIR AND FILTERS

D

UCTWORK

The supply duct should be provided with an access panel
large enough to inspect the air chamber downstream of the
heat exchanger.  A cover should be tightly attached to pre-
vent air leaks.

Ductwork dimensions are shown in the roof curb installation
manual.

If desired, supply and return duct connections to the unit may
be made with flexible connections to reduce possible unit
operating sound transmission.

VENTING

NOTE:  Venting is self-contained.

CONDENSATE DRAIN CONNECTION

C

ONDENSATE

 D

RAIN

 C

ONNECTION

A 3/4” NPT drain connection is supplied for condensate pip-
ing.  An external trap must be installed for proper condensate
drainage.

UNIT

2" MINIMUM

FLEXIBLE
TUBING-HOSE
OR PIPE

3" MINIMUM

A POSITIVE LIQUID
SEAL IS REQUIRED

DRAIN CONNECTION

Install condensate drain trap as shown. Use 3/4" drain line
and fittings or larger. Do not operate without trap.

H

ORIZONTAL

 D

RAIN

Drainage of condensate directly onto the roof may be ac-
ceptable; refer to local code. It is recommended that a small
drip pad of either stone, mortar, wood or metal be provided to
prevent any possible damage to the roof.

C

LEANING

Due to the fact that drain pans in any air conditioning unit
will have some moisture in them, algae and fungus will
grow due to airborne bacteria and spores. Periodic clean-
ing is necessary to prevent this build-up from plugging the
drain.

Содержание ANSI Z21.47CSA-2.3

Страница 1: ...tion Manual Observe all safety warnings During installation or repair caution is to be observed It is your responsibility to install the product safely and to educate the customer on its safe use This Forced Air Central Unit Design Complies With Requirements Embodied in The American National Standard National Standard of Canada Shown Below ANSI Z21 47 CSA 2 3 Central Furnaces C US 2010 Goodman Man...

Страница 2: ... PHONE FOLLOW THE GAS SUPPLIER S INSTRUCTIONS IF YOU CANNOT REACH YOUR GAS SUPPLIER CALL THE FIRE DEPARTMENT INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER WHAT TO DO IF YOU SMELL GAS WARNING DO NOT CONNECT TO OR USE ANY DEVICE THAT IS NOT DESIGN CERTIFIED BY GOODMAN FOR USE WITH THIS UNIT SERIOUS PROPERTY DAMAGE PERSONAL INJURY REDUCED UNIT ...

Страница 3: ...ONOXYDE DE CARBONE Si ce compartiment n est pas ferme en tout temps sauf en cas de reparation il y a risque d empoisonnement ou monoxyde de carbon ou de mort Ce compartiment doit être ferme sauf au moment de l entretien PELIGRO MONOXIDO DE CARBONO TOXICO El fracaso de no mantener compartimiento cerrado menos durante atender podria tener como resultado envenar de monoxido de carbona o muerte Este c...

Страница 4: ... hardware and supplies needed to complete the installation Some items may need to be purchased locally UNIT LOCATION TO PREVENT POSSIBLE EQUIPMENT DAMAGE PROPERTY DAMAGE PERSONAL INJURY OR DEATH THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT WARNING IMPORTANT NOTE Remove wood shipping rails prior to installation of the unit See important note under Roof Curb Installation Onl...

Страница 5: ... from the furnace flue discharge to any adjacent public walkways adjacent buildings building openings or openable windows must be maintained in accordance with the latest edition of the National Fuel Gas Code ANSI Z223 1 Minimum horizontal clearance of 48 from the furnace flue discharge to any electric meters gas meters regulators and relief equipment is required UNIT PRECAUTIONS Do not stand or w...

Страница 6: ...support must be determined prior to locating and mounting the curb and package unit Ductwork must be constructed using industry guidelines The duct work must be placed into the roof curb before mounting the package unit Our full perimeter curbs include duct connection frames to be assembled with the curb Cantilevered type curbs are not available from the factory Curb insulation cant strips flashin...

Страница 7: ...PREVENT DAMAGE TO THE UNIT CAUTION Provisions for forks have been included in the unit base frame No other fork locations are approved TO PREVENT POSSIBLE EQUIPMENT DAMAGE PROPERTY DAMAGE PERSONAL INJURY OR DEATH THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT WARNING Unit must be lifted by the four lifting holes located at the base frame corners Lifting cables should be atta...

Страница 8: ...unit Check for proper alignment and orientation of supply and return openings with duct RIGGING REMOVAL TO PREVENT DAMAGE TO THE UNIT DO NOT ALLOW CRANE HOOKS AND SPREADER BARS TO REST ON THE ROOF OF THE UNIT CAUTION Remove spreader bars lifting cables and other rigging equip ment ELECTRICAL WIRING HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MA...

Страница 9: ...tribution in accordance with the unit data plate The unit must be electrically grounded in accordance with local codes or in the absence of local codes with the latest edition of the National Electrical Code ANSI NFPA 70 A ground lug is provided for this purpose Size grounding conductor in accordance with Table 250 95 of the National Electrical Code Do not use the ground lug for connecting a neutr...

Страница 10: ...D INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER WARNING IMPORTANT NOTE This unit is factory set to operate on natural gas at the altitudes shown on the rating plate TO PREVENT PROPERTY DAMAGE PERSONAL INJURY OR DEATH WHEN EITHER USING PROPANE GAS ALONE OR AT HIGHER ALTITUDES OBTAIN AND INSTALL THE PROPER CONVERSION KIT S FAILURE TO DO SO CAN RESULT IN UNSATISFACTORY OPERATION AND OR EQUIPMENT DAMAG...

Страница 11: ... to the gas valve to keep it from turning 6 Install a manual shut off valve in a convenient location within six feet of unit between the meter and the unit 7 Tighten all joints securely 8 The unit must be connected to the building piping by one of the following methods Rigid metallic pipe and fittings Semirigid metallic tubing and metallic fittings Aluminum alloy tubing must not be used in exterio...

Страница 12: ...ust be within 9 7 10 3 inches w c for high fire and within 6 7 7 3 inches w c low fire at the manifold with all gas appli ances in operation Maintaining proper gas pressure depends on three main factors 1 Vaporization rate which depends on a temperature of the liquid and b wetted surface area of the container or containers 2 Proper pressure regulation 3 Pressure drop in lines between regulators an...

Страница 13: ...e THIS UNIT AND ITS INDIVIDUAL SHUTOFF VALVE MUST BE DISCONNECTED FROM THE GAS SUPPLY SYSTEM DURING ANY PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF 1 2 PSIG 13 8 W C WARNING THIS UNIT MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY CLOSING ITS INDIVIDUAL MANUAL SHUTOFF VALVE DURING ANY PRESSURE TESTING EQUAL TO OR LESS THAN 1 2 PSIG CAUTION 7 There must be no obstruction t...

Страница 14: ...de ambient rises above 55 F TOOLS REQUIRED Refrigeration gauge and manifold Voltmeter Clamp on ammeter Ohmmeter Test lead Minimum 16 AWG with insulated alligator clips Manometer for verifying gas pressure 0 to 20 w c Air temperature measuring device General refrigeration mechanics tools TEMPORARY HEATING OR COOLING If the unit is to be used for temporary heating or cooling a Startup Adjustments an...

Страница 15: ...emove filter section access panels and check that filters are properly installed Note airflow arrows on filter frames BEARING CHECK Prior to energizing any fans check and make sure that all setscrews are tight so that bearings are properly secured to shafts SET EVAPORATOR FAN RPM Actual RPM s must be set and verified with a tachometer or strobe light Refer to Appendices A and B for basic unit fan ...

Страница 16: ...rmined and repaired prior to resetting this manual reset control TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION A QUALIFIED SERVICER MUST INVESTIGATE THE REASON FOR THE ROLLOUT PROTECTION DEVICE TO OPEN BEFORE MANUALLY RESETTING THE ROLLOUT PROTECTION DEVICE WARNING Secondary Limit Control The secondary limit control is located on the side of the blower scroll assembly ...

Страница 17: ... 3600 34 106 000 BTU per Hour NOTE BTU content of the gas should be obtained from the gas supplier This measured input must not be greater than shown on the unit rating plate 4 Relight all other appliances turned off in step 1 Be sure all pilot burners are operating Main Burner Flame Check Flames should be stable soft and blue dust may cause or ange tips but they must not be yellow and extending d...

Страница 18: ...wall thermostat 11 Open disconnect switch Reconnect the field thermostat wire at terminal R on terminal block TB1 REFRIGERATION PERFORMANCE CHECK Under normal summertime full load operating conditions superheat should be between 8 F and 12 F and sub cooling measured at the condenser outlet should be 15 F nominal A 25 F to 35 F temperature difference should exist between the entering condenser air ...

Страница 19: ...n the system switch in the HEAT or AUTO position and the fan switch in the AUTO position the thermostat will close the circuit between unit terminals R and W R W when the temperature falls below the thermostat setting 2 D1 on IIC energizes relay IDMR 3 Relay IDMR energizes the ventor motor IDM 4 Operation of the vent motor closes the pressure switch PS located in the burner compartment the control...

Страница 20: ... control will recycle for four 4 consecu tive ignition attempts five attempts total before locking out The diagnostic fault code is 1 flash for a lockout due to failed ignition attempts or flame dropouts The integrated control will automatically reset after one hour or it can be reset by removing the thermostat signal or disconnecting the electri cal power supply for over five seconds If the diagn...

Страница 21: ...t The input rate can be calculated by using the formula INPUT Btu Hr 3600 x HV T WHERE HV Heating value of fuel Btu ft of gas T Time in seconds per ft of gas flow as read from gas meter 3 3 Adjust input rate by varying the adjustment of the gas pres sure regulator on the gas valve All adjustments must be made with furnace operating at high fire and at normal operating temperature Clockwise P rotat...

Страница 22: ...NSTALLER SERVICE AGENCY OR THE GAS SUPPLIER WARNING SHEET METAL PARTS SCREWS CLIPS AND SIMILAR ITEMS INHERENTLY HAVE SHARP EDGES AND IT IS NECESSARY THAT THE INSTALLER AND SERVICE PERSONNEL EXERCISE CAUTION CAUTION Preventive maintenance is the best way to avoid unneces sary expense and inconvenience Have this system inspected at regular intervals by qualified service personnel at least twice a ye...

Страница 23: ...ecessary for continued safe operation Par ticular attention should be given to deterioration from corro sion or other sources This examination is accomplished in the following manner 1 Disconnect power to the unit and remove furnace section access panel 2 Remove burner assembly a Disconnect the three wires from the gas valve after noting which wires are connected to each terminal b Disconnect wire...

Страница 24: ...8 5982 1 94 0 4 7079 3 20 6623 2 76 6161 2 34 5706 1 98 5271 1 66 0 6 6903 3 32 6405 2 83 5923 2 41 5434 2 02 4949 1 68 0 8 6717 3 42 6198 2 92 5668 2 45 5152 2 05 1 0 5975 2 99 5418 2 51 1 2 5147 2 55 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 0 2 9359 4 92 8991 3 79 8621 3 54 8188 3 27 7826 3 04 0 4 9018 3 18 8632 4 39 8251 3 39 7867 3 15 7363 2 85 6992 2 63 0 6 8279 2 96 7879 3 86 ...

Страница 25: ...BHP 1 0 6690 3 69 6008 3 02 5321 2 43 1 2 6653 3 95 5922 3 22 5182 2 58 1 4 6634 2 80 5857 3 44 5056 2 74 1 6 6638 4 55 5808 2 43 4948 2 91 1 8 6683 4 93 5784 3 95 4855 2 05 2 0 5803 4 27 4788 3 32 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 1 0 9001 6 83 8394 6 01 7797 4 78 7227 4 28 1 2 8891 6 83 8262 6 15 7632 5 35 7012 4 20 1 4 8811 6 86 8148 6 15 7495 5 48 6841 4 71 1 6 8065 6 19 ...

Страница 26: ...L DATA ID MOTOR APPL COMPRESSOR ea OD FAN MOTORS ea ID FAN MOTOR VOLTAGE LIMITATIONS VOLTAGE NAMEPLATE MODELS MIN MAX Qty RLA LRA Qty RLA LRA Qty HP RLA HP FLA 208 230 60 3 187 253 1 29 5 195 0 1 25 0 164 0 3 1 3 2 40 BD STD STATIC 5 0 12 7 460 60 3 414 506 1 14 7 95 0 1 12 2 100 0 3 1 3 1 20 BD STD STATIC 5 0 6 4 575 60 3 518 633 1 12 2 80 0 1 9 0 78 0 3 1 3 0 90 BD STD STATIC 5 0 5 1 SMALLER COM...

Страница 27: ...27 APPENDIX C UNIT DIMENSIONS VERTICAL DISCHARGE TOP VIEW 21 60 7 48 22 B C D A Model A B C D 15 Ton 20 Ton 133 1 2 88 7 32 50 9 32 5 5 32 ...

Страница 28: ...D RD BR BR BL BL BL PU PU PU PU PU PU PU GR BL BL BL PK BR BR BR BR BR YL YL YL YL YL YL RD RD RD RD BL BL BL BL WH WH WH WH 0140L00954 REV A OR OR OR OR 3 1 VMR 4 6 RD BK BK BK RD BK OR RD BK OR OR BK BK RD OR 4 2 1 6 YL BL CCH1 CCHR2 PU BK BK BK RD OR BL SEE NOTE 2 T2 T1 CC 2 L2 L1 T3 L3 T2 T1 CC 1 L2 L1 T3 L3 T2 T1 L2 L1 T3 L3 T2 T1 BC L2 L1 T3 L3 POWER SUPPLY 208V 240V 3 ph 60 Hz SEE NOTE 4 T1...

Страница 29: ... IGN FS VMR IIC BC 5 4 7 8 6 9 1 2 3 TR 24V TB1 TB1 2 PLF L1 SUPPLY VOLTAGE 208 240 3 60 L2 L3 1 3 1 3 RCCF1 CC1 T3 COMP1 T2 F CM1 EM CC1 T1 C CC1 BC T2 BC BC RCCF3 CC2 T3 T1 COMP2 T2 F CM3 CC2 T1 C CC2 T3 T2 VM VENT MOTOR RELAY VENT MOTOR TRANSFORMER TERMINAL BLOCK 24V SIGNAL ROLLOUT SWITCH PRESSURE SWITCH FEMALE PLUG CONNECTOR LIMIT SWITCH LOW PRESSURE SWITCH IGNITOR INTEGRATED IGNITION CONTROL ...

Страница 30: ...GE 1 24V 3 1 L2 UNUSED COOL HEAT DI FS L1 4 5 6 2 3 1 ECON 11 8 12 9 7 10 IIC LS 3 2 1 9 6 8 7 4 5 R GV W1 C Y1 Y2 G ALS PS RS GRND FS IGN W2 LPS1 LPS2 HPS1 HPS2 VMR S1 S2 TB1 TO THERMOSTAT TB1 SEE NOTE 5 RD RD WH BK BK BK OR OR RD RD BK BK OR RD YL BK RD YL BK RD YL BK RD YL BK RD RD RD BK RD BK BK BK BK BK PU PU PU PU PU PU PU PU BR BR BR BR BR BR BR BR RD RD WH WH WH BK OR RD RD BK RD OR BL BL ...

Страница 31: ...OMPARTMENT REMOVE MALE PLUG AND TO BLOWER HOUSING IN RETURN AIR 2 ACCESSORY ECONOMIZER PLUG ADJACENT 4 USE COPPER CONDUCTORS ONLY USE NEC CLASS 2 WIRE 3 L1 AND L2 ON IIC CONTROL IS 24V INPUT HIGH VOLTAGE OPTIONAL LOW VOLTAGE LINE VOLTAGE FIELD WIRING LOW VOLTAGE HIGH VOLTAGE FIELD WIRING THERMOSTAT FACTORY WIRING 0140L00957 REV A COMPONENT LEGEND Y1 Y Y2 RCCF2 F CM2 C T2 T1 T3 T3 T1 T1 TERMINAL BL...

Страница 32: ...32 2010 Goodman Manufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com www amana hac com ...

Отзывы: