Goodman ANSI Z21.47CSA-2.3 Скачать руководство пользователя страница 17

17

With Power And Gas On:

2. Put unit into heating cycle and turn on all other gas

consuming appliances.

NATURAL

Min.    5.0" W.C., Max. 10.0" W.C.

PROPANE

Min. 11.0" W.C., Max. 14.0" W.C.

INLET GAS PRESSURE

NOTE:

  Inlet Gas Pressure Must Not Exceed the Maximum

Value Shown.

If operating pressures differ from above, make necessary
pressure regulator adjustments, check piping size, etc., and/
or consult with local utility.

Manifold Pressure Check

The gas valve has a tapped opening to facilitate measure-
ment of the manifold pressure. A “U” Tube manometer hav-
ing a scale range from 0 to 12 inches of water should be
used for this measurement. The manifold pressure must be
measured with the burners operating.

To adjust the pressure regulator, remove the adjustment screw
or cover on the gas valve. Turn out (counterclockwise) to
decrease pressure, turn in (clockwise) to increase pressure.
Only small variations in gas flow should be made by means
of the pressure regulator adjustment. In no case should the
final manifold pressure vary more than plus or minus 0.3
inches water column from the specified nominal pressure.
Any major changes in flow should be made by changing the
size of the burner orifices.  The measured input rate to the
furnace must not exceed the rating specified on the unit rat-
ing plate.

For natural gas, the manifold pressure must be between 3.2
and 3.8 inches w.c. (3.5 nominal) for high fire and between
1.7 and 2.3 inches w.c. (2.0 nominal) for low fire.

For propane gas, the manifold pressure must be between
9.7 and 10.3 inches w.c. (10.0 nominal) for high fire and be-
tween 6.7 and 7.3 inches w.c. (7.0 nominal) for low fire.

Gas Input (Natural Gas Only) Check

To measure the gas input use a gas meter and proceed
as follows:
1. Turn off gas supply to all other appliances except the

unit.

2. With the unit operating, time the smallest dial on the

meter for one complete revolution. If this is a 2 cubic
foot dial, divide the seconds by 2; if it is a 1 cubic foot
dial, use the seconds as is. This gives the seconds
per cubic foot of gas being delivered to the unit.

3. INPUT=GAS HTG VALUE x 3600 / SEC. PER CUBIC

FOOT

Example:

 Natural gas with a heating value of 1000 BTU per

cubic foot and 34 seconds per cubic foot as determined by
Step 2, then:

Input = 1000 x 3600 / 34 = 106,000 BTU per Hour.

NOTE: 

BTU content of the gas should be obtained

from the gas supplier. This measured input must not
be greater than shown on the unit rating plate.

4. Relight all other appliances turned off in step 1. Be

sure all pilot burners are operating.

Main Burner Flame Check

Flames should be stable, soft and blue (dust may cause or-
ange tips but they must not be yellow) and extending directly
outward from the burner without curling, floating or lifting off.

Temperature Rise Check

Check the temperature rise through the unit by placing ther-
mometers in supply and return air registers as close to the
unit as possible. Thermometers must not be able to sample
temperature directly from the unit heat exchangers, or false
readings could be obtained.

1. All registers must be open; all duct dampers must be

in their final (fully or partially open) position and the
unit operated for 15 minutes on HIGH FIRE before
taking readings.

2. The temperature rise must be within the range

specified on the rating plate.

NOTE:

 Air temperature rise is the temperature difference

between supply and return air.

With a properly designed system, the proper amount of tem-
perature rise will normally be obtained when the unit is oper-
ated at rated input with the recommended blower speed.

If the correct amount of temperature rise is not obtained, it
may  be necessary to change the blower speed. A higher
blower speed will lower the temperature rise. A slower blower
speed will increase the temperature rise.

NOTE: 

Blower speed MUST be set to give the correct air

temperature rise through the unit as marked on the rating
plate.

R

EFRIGERATION

 S

EQUENCE

 C

HECK

With the disconnect switch open, remove the field connected
thermostat wire from terminal R on TB1 terminal block. Place
a jumper across terminals R and G, and across R and Y on
TB1 terminal block. Close the disconnect switch. The follow-
ing operational sequence should be observed.

1. Current through primary winding of transformer

TRANS1 energizes the 24-volt control circuit.

2. To simulate a mechanical call for cooling from the wall

thermostat, place a jumper across terminals R and
Y1 of terminal block TB1.

3.

UNIT WITH ECONOMIZER OPTION:

 The

compressor circuit is interlocked through terminals 3
and 4 of the economizer module. If the outdoor air
enthalpy (temperature and humidity) is not suitable
for cooling, the economizer terminals will be closed
permitting compressor to be energized.

Содержание ANSI Z21.47CSA-2.3

Страница 1: ...tion Manual Observe all safety warnings During installation or repair caution is to be observed It is your responsibility to install the product safely and to educate the customer on its safe use This Forced Air Central Unit Design Complies With Requirements Embodied in The American National Standard National Standard of Canada Shown Below ANSI Z21 47 CSA 2 3 Central Furnaces C US 2010 Goodman Man...

Страница 2: ... PHONE FOLLOW THE GAS SUPPLIER S INSTRUCTIONS IF YOU CANNOT REACH YOUR GAS SUPPLIER CALL THE FIRE DEPARTMENT INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER WHAT TO DO IF YOU SMELL GAS WARNING DO NOT CONNECT TO OR USE ANY DEVICE THAT IS NOT DESIGN CERTIFIED BY GOODMAN FOR USE WITH THIS UNIT SERIOUS PROPERTY DAMAGE PERSONAL INJURY REDUCED UNIT ...

Страница 3: ...ONOXYDE DE CARBONE Si ce compartiment n est pas ferme en tout temps sauf en cas de reparation il y a risque d empoisonnement ou monoxyde de carbon ou de mort Ce compartiment doit être ferme sauf au moment de l entretien PELIGRO MONOXIDO DE CARBONO TOXICO El fracaso de no mantener compartimiento cerrado menos durante atender podria tener como resultado envenar de monoxido de carbona o muerte Este c...

Страница 4: ... hardware and supplies needed to complete the installation Some items may need to be purchased locally UNIT LOCATION TO PREVENT POSSIBLE EQUIPMENT DAMAGE PROPERTY DAMAGE PERSONAL INJURY OR DEATH THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT WARNING IMPORTANT NOTE Remove wood shipping rails prior to installation of the unit See important note under Roof Curb Installation Onl...

Страница 5: ... from the furnace flue discharge to any adjacent public walkways adjacent buildings building openings or openable windows must be maintained in accordance with the latest edition of the National Fuel Gas Code ANSI Z223 1 Minimum horizontal clearance of 48 from the furnace flue discharge to any electric meters gas meters regulators and relief equipment is required UNIT PRECAUTIONS Do not stand or w...

Страница 6: ...support must be determined prior to locating and mounting the curb and package unit Ductwork must be constructed using industry guidelines The duct work must be placed into the roof curb before mounting the package unit Our full perimeter curbs include duct connection frames to be assembled with the curb Cantilevered type curbs are not available from the factory Curb insulation cant strips flashin...

Страница 7: ...PREVENT DAMAGE TO THE UNIT CAUTION Provisions for forks have been included in the unit base frame No other fork locations are approved TO PREVENT POSSIBLE EQUIPMENT DAMAGE PROPERTY DAMAGE PERSONAL INJURY OR DEATH THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT WARNING Unit must be lifted by the four lifting holes located at the base frame corners Lifting cables should be atta...

Страница 8: ...unit Check for proper alignment and orientation of supply and return openings with duct RIGGING REMOVAL TO PREVENT DAMAGE TO THE UNIT DO NOT ALLOW CRANE HOOKS AND SPREADER BARS TO REST ON THE ROOF OF THE UNIT CAUTION Remove spreader bars lifting cables and other rigging equip ment ELECTRICAL WIRING HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MA...

Страница 9: ...tribution in accordance with the unit data plate The unit must be electrically grounded in accordance with local codes or in the absence of local codes with the latest edition of the National Electrical Code ANSI NFPA 70 A ground lug is provided for this purpose Size grounding conductor in accordance with Table 250 95 of the National Electrical Code Do not use the ground lug for connecting a neutr...

Страница 10: ...D INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER WARNING IMPORTANT NOTE This unit is factory set to operate on natural gas at the altitudes shown on the rating plate TO PREVENT PROPERTY DAMAGE PERSONAL INJURY OR DEATH WHEN EITHER USING PROPANE GAS ALONE OR AT HIGHER ALTITUDES OBTAIN AND INSTALL THE PROPER CONVERSION KIT S FAILURE TO DO SO CAN RESULT IN UNSATISFACTORY OPERATION AND OR EQUIPMENT DAMAG...

Страница 11: ... to the gas valve to keep it from turning 6 Install a manual shut off valve in a convenient location within six feet of unit between the meter and the unit 7 Tighten all joints securely 8 The unit must be connected to the building piping by one of the following methods Rigid metallic pipe and fittings Semirigid metallic tubing and metallic fittings Aluminum alloy tubing must not be used in exterio...

Страница 12: ...ust be within 9 7 10 3 inches w c for high fire and within 6 7 7 3 inches w c low fire at the manifold with all gas appli ances in operation Maintaining proper gas pressure depends on three main factors 1 Vaporization rate which depends on a temperature of the liquid and b wetted surface area of the container or containers 2 Proper pressure regulation 3 Pressure drop in lines between regulators an...

Страница 13: ...e THIS UNIT AND ITS INDIVIDUAL SHUTOFF VALVE MUST BE DISCONNECTED FROM THE GAS SUPPLY SYSTEM DURING ANY PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF 1 2 PSIG 13 8 W C WARNING THIS UNIT MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY CLOSING ITS INDIVIDUAL MANUAL SHUTOFF VALVE DURING ANY PRESSURE TESTING EQUAL TO OR LESS THAN 1 2 PSIG CAUTION 7 There must be no obstruction t...

Страница 14: ...de ambient rises above 55 F TOOLS REQUIRED Refrigeration gauge and manifold Voltmeter Clamp on ammeter Ohmmeter Test lead Minimum 16 AWG with insulated alligator clips Manometer for verifying gas pressure 0 to 20 w c Air temperature measuring device General refrigeration mechanics tools TEMPORARY HEATING OR COOLING If the unit is to be used for temporary heating or cooling a Startup Adjustments an...

Страница 15: ...emove filter section access panels and check that filters are properly installed Note airflow arrows on filter frames BEARING CHECK Prior to energizing any fans check and make sure that all setscrews are tight so that bearings are properly secured to shafts SET EVAPORATOR FAN RPM Actual RPM s must be set and verified with a tachometer or strobe light Refer to Appendices A and B for basic unit fan ...

Страница 16: ...rmined and repaired prior to resetting this manual reset control TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION A QUALIFIED SERVICER MUST INVESTIGATE THE REASON FOR THE ROLLOUT PROTECTION DEVICE TO OPEN BEFORE MANUALLY RESETTING THE ROLLOUT PROTECTION DEVICE WARNING Secondary Limit Control The secondary limit control is located on the side of the blower scroll assembly ...

Страница 17: ... 3600 34 106 000 BTU per Hour NOTE BTU content of the gas should be obtained from the gas supplier This measured input must not be greater than shown on the unit rating plate 4 Relight all other appliances turned off in step 1 Be sure all pilot burners are operating Main Burner Flame Check Flames should be stable soft and blue dust may cause or ange tips but they must not be yellow and extending d...

Страница 18: ...wall thermostat 11 Open disconnect switch Reconnect the field thermostat wire at terminal R on terminal block TB1 REFRIGERATION PERFORMANCE CHECK Under normal summertime full load operating conditions superheat should be between 8 F and 12 F and sub cooling measured at the condenser outlet should be 15 F nominal A 25 F to 35 F temperature difference should exist between the entering condenser air ...

Страница 19: ...n the system switch in the HEAT or AUTO position and the fan switch in the AUTO position the thermostat will close the circuit between unit terminals R and W R W when the temperature falls below the thermostat setting 2 D1 on IIC energizes relay IDMR 3 Relay IDMR energizes the ventor motor IDM 4 Operation of the vent motor closes the pressure switch PS located in the burner compartment the control...

Страница 20: ... control will recycle for four 4 consecu tive ignition attempts five attempts total before locking out The diagnostic fault code is 1 flash for a lockout due to failed ignition attempts or flame dropouts The integrated control will automatically reset after one hour or it can be reset by removing the thermostat signal or disconnecting the electri cal power supply for over five seconds If the diagn...

Страница 21: ...t The input rate can be calculated by using the formula INPUT Btu Hr 3600 x HV T WHERE HV Heating value of fuel Btu ft of gas T Time in seconds per ft of gas flow as read from gas meter 3 3 Adjust input rate by varying the adjustment of the gas pres sure regulator on the gas valve All adjustments must be made with furnace operating at high fire and at normal operating temperature Clockwise P rotat...

Страница 22: ...NSTALLER SERVICE AGENCY OR THE GAS SUPPLIER WARNING SHEET METAL PARTS SCREWS CLIPS AND SIMILAR ITEMS INHERENTLY HAVE SHARP EDGES AND IT IS NECESSARY THAT THE INSTALLER AND SERVICE PERSONNEL EXERCISE CAUTION CAUTION Preventive maintenance is the best way to avoid unneces sary expense and inconvenience Have this system inspected at regular intervals by qualified service personnel at least twice a ye...

Страница 23: ...ecessary for continued safe operation Par ticular attention should be given to deterioration from corro sion or other sources This examination is accomplished in the following manner 1 Disconnect power to the unit and remove furnace section access panel 2 Remove burner assembly a Disconnect the three wires from the gas valve after noting which wires are connected to each terminal b Disconnect wire...

Страница 24: ...8 5982 1 94 0 4 7079 3 20 6623 2 76 6161 2 34 5706 1 98 5271 1 66 0 6 6903 3 32 6405 2 83 5923 2 41 5434 2 02 4949 1 68 0 8 6717 3 42 6198 2 92 5668 2 45 5152 2 05 1 0 5975 2 99 5418 2 51 1 2 5147 2 55 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 0 2 9359 4 92 8991 3 79 8621 3 54 8188 3 27 7826 3 04 0 4 9018 3 18 8632 4 39 8251 3 39 7867 3 15 7363 2 85 6992 2 63 0 6 8279 2 96 7879 3 86 ...

Страница 25: ...BHP 1 0 6690 3 69 6008 3 02 5321 2 43 1 2 6653 3 95 5922 3 22 5182 2 58 1 4 6634 2 80 5857 3 44 5056 2 74 1 6 6638 4 55 5808 2 43 4948 2 91 1 8 6683 4 93 5784 3 95 4855 2 05 2 0 5803 4 27 4788 3 32 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 1 0 9001 6 83 8394 6 01 7797 4 78 7227 4 28 1 2 8891 6 83 8262 6 15 7632 5 35 7012 4 20 1 4 8811 6 86 8148 6 15 7495 5 48 6841 4 71 1 6 8065 6 19 ...

Страница 26: ...L DATA ID MOTOR APPL COMPRESSOR ea OD FAN MOTORS ea ID FAN MOTOR VOLTAGE LIMITATIONS VOLTAGE NAMEPLATE MODELS MIN MAX Qty RLA LRA Qty RLA LRA Qty HP RLA HP FLA 208 230 60 3 187 253 1 29 5 195 0 1 25 0 164 0 3 1 3 2 40 BD STD STATIC 5 0 12 7 460 60 3 414 506 1 14 7 95 0 1 12 2 100 0 3 1 3 1 20 BD STD STATIC 5 0 6 4 575 60 3 518 633 1 12 2 80 0 1 9 0 78 0 3 1 3 0 90 BD STD STATIC 5 0 5 1 SMALLER COM...

Страница 27: ...27 APPENDIX C UNIT DIMENSIONS VERTICAL DISCHARGE TOP VIEW 21 60 7 48 22 B C D A Model A B C D 15 Ton 20 Ton 133 1 2 88 7 32 50 9 32 5 5 32 ...

Страница 28: ...D RD BR BR BL BL BL PU PU PU PU PU PU PU GR BL BL BL PK BR BR BR BR BR YL YL YL YL YL YL RD RD RD RD BL BL BL BL WH WH WH WH 0140L00954 REV A OR OR OR OR 3 1 VMR 4 6 RD BK BK BK RD BK OR RD BK OR OR BK BK RD OR 4 2 1 6 YL BL CCH1 CCHR2 PU BK BK BK RD OR BL SEE NOTE 2 T2 T1 CC 2 L2 L1 T3 L3 T2 T1 CC 1 L2 L1 T3 L3 T2 T1 L2 L1 T3 L3 T2 T1 BC L2 L1 T3 L3 POWER SUPPLY 208V 240V 3 ph 60 Hz SEE NOTE 4 T1...

Страница 29: ... IGN FS VMR IIC BC 5 4 7 8 6 9 1 2 3 TR 24V TB1 TB1 2 PLF L1 SUPPLY VOLTAGE 208 240 3 60 L2 L3 1 3 1 3 RCCF1 CC1 T3 COMP1 T2 F CM1 EM CC1 T1 C CC1 BC T2 BC BC RCCF3 CC2 T3 T1 COMP2 T2 F CM3 CC2 T1 C CC2 T3 T2 VM VENT MOTOR RELAY VENT MOTOR TRANSFORMER TERMINAL BLOCK 24V SIGNAL ROLLOUT SWITCH PRESSURE SWITCH FEMALE PLUG CONNECTOR LIMIT SWITCH LOW PRESSURE SWITCH IGNITOR INTEGRATED IGNITION CONTROL ...

Страница 30: ...GE 1 24V 3 1 L2 UNUSED COOL HEAT DI FS L1 4 5 6 2 3 1 ECON 11 8 12 9 7 10 IIC LS 3 2 1 9 6 8 7 4 5 R GV W1 C Y1 Y2 G ALS PS RS GRND FS IGN W2 LPS1 LPS2 HPS1 HPS2 VMR S1 S2 TB1 TO THERMOSTAT TB1 SEE NOTE 5 RD RD WH BK BK BK OR OR RD RD BK BK OR RD YL BK RD YL BK RD YL BK RD YL BK RD RD RD BK RD BK BK BK BK BK PU PU PU PU PU PU PU PU BR BR BR BR BR BR BR BR RD RD WH WH WH BK OR RD RD BK RD OR BL BL ...

Страница 31: ...OMPARTMENT REMOVE MALE PLUG AND TO BLOWER HOUSING IN RETURN AIR 2 ACCESSORY ECONOMIZER PLUG ADJACENT 4 USE COPPER CONDUCTORS ONLY USE NEC CLASS 2 WIRE 3 L1 AND L2 ON IIC CONTROL IS 24V INPUT HIGH VOLTAGE OPTIONAL LOW VOLTAGE LINE VOLTAGE FIELD WIRING LOW VOLTAGE HIGH VOLTAGE FIELD WIRING THERMOSTAT FACTORY WIRING 0140L00957 REV A COMPONENT LEGEND Y1 Y Y2 RCCF2 F CM2 C T2 T1 T3 T3 T1 T1 TERMINAL BL...

Страница 32: ...32 2010 Goodman Manufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com www amana hac com ...

Отзывы: