SCHEDULED MAINTENANCE

14

CLOCKING A GAS METER

1.  Turn off all gas appliances in the home. 
2.  Turn on the furnace. Ensure the furnace is operating at a 100% firing rate on 2 stage and modulating furnace product.

3.  Once heating cycle is at a steady state (typically 15 minutes of operation), use a stopwatch to time how long it takes 

the smallest unit of measure dial on the gas meter to make a full revolution. In Table 1, one cubic foot is selected. The 

smallest unit of measure will vary depending on the gas meter. 

CUBIC

 FEET

1

1

One

 

In this example 

we are using the 

one cubic foot 

dial on the gas 

meter 

TABLE 1

4.  Using Table 2 below, find the number of seconds it took for the dial to make a full revolution. To the right of that num

-

ber of seconds and below the Size of Test Dial (selected in step 3 and shown in Table 1) will be the Cubic Feet per 

Hour (CFH).

1/4

cu/ft

1/2

cu/ft

1

cu/ft

2

cu/ft

5

cu/ft

1/4

cu/ft

1/2

cu/ft

1

cu/ft

2

cu/ft

5

cu/ft

10

90

180

360

720

1800

36

25

50

100

200

500

11

82

164

327

655

1636

37

--

--

97

195

486

12

75

150

300

600

1500

38

23

47

95

189

474

13

69

138

277

555

1385

39

--

--

92

185

462

14

64

129

257

514

1286

40

22

45

90

180

450

15

60

120

240

480

1200

41

--

--

--

176

439

16

56

113

225

450

1125

42

21

43

86

172

429

17

53

106

212

424

1059

43

--

--

--

167

419

18

50

100

200

400

1000

44

--

41

82

164

409

19

47

95

189

379

947

45

20

40

80

160

400

20

45

90

180

360

900

46

--

--

78

157

391

21

43

86

171

343

857

47

19

38

76

153

383

22

41

82

164

327

818

48

--

--

75

150

375

23

39

78

157

313

783

49

--

--

--

147

367

24

37

75

150

300

750

50

18

36

72

144

360

25

36

72

144

288

720

51

--

--

--

141

355

26

34

69

138

277

692

52

--

--

69

138

346

27

33

67

133

265

667

53

17

34

--

136

340

28

32

64

129

257

643

54

--

--

67

133

333

29

31

62

124

248

621

55

--

--

--

131

327

30

30

60

120

240

600

56

16

32

64

129

321

31

--

--

116

232

581

57

--

--

--

126

316

32

28

56

113

225

563

58

--

31

62

124

310

33

--

--

109

218

545

59

--

--

--

122

305

34

26

53

106

212

529

60

15

30

60

120

300

35

--

--

103

206

514

    GAS RATE -- CUBIC FEET PER HOUR

Seconds for 

One 

Revolution

Size of Test Dial

Seconds for 

One 

Revolution

Size of Test Dial

 

Locate 40 seconds for one 

revolu

on in the chart below

 

 

Then locate the 1 cu 

 dial column and select the 

corresponding CFH from the 40 seconds for one revolu

on row 

TABLE 2

Содержание AMES960403BU AA

Страница 1: ...ced only by a qualified service technician who is familiar with the safety procedures required in the repair and who is equipped with the proper tools parts testing instruments and the appropriate ser...

Страница 2: ...arts testing in struments and the appropriate service manual REVIEWALL SERVICEINFORMATIONINTHEAPPROPRIATESERVICE MANUAL BEFORE BEGINNING REPAIRS OUTSIDE THE U S call 1 713 861 2500 Not a technical ass...

Страница 3: ...El mon xido de carbono puede causar enfermedades severas como da o cerebral permanente muerte Las emisiones de mon xido de carbono pueden circular a trav s del aparato cuando se opera en cualquier mo...

Страница 4: ...dman A Initial Release V GMC B 1st Revision Configuration M Upflow Horizontal Major Revision C Downflow Horizontal A Initial Release B 1st Revision Airflow C Variable Speed ComfortNet Nox E High Effic...

Страница 5: ...nless Steel tubular heat exchanger 115 volt silicon nitride igniter Left or right gas entry Line voltage EAC HUM terminals GMES96 U GMES960403BU AA GMES960603BU AA GMES960805CU AA Goodman Brand 96 Ult...

Страница 6: ...a residential home gas furnace It is not designed or certified for use in mobile home trailer or recreational vehicle applications In the U S A this furnace can be used in the following non industria...

Страница 7: ...LOSURE FAILURE TO FOLLOW THIS WARNING CAN RESULT IN PROPERTY DAMAGE EQUIPMENT DAMAGE PERSONAL INJURY OR DEATH Condensate Drain Lines and Drain Trap Acondensing gas furnace achieves its high level of e...

Страница 8: ...ply pressures must be maintained within the ranges specified below The supply pressure must be constant and available with all other household gas fired appliances operating The minimum gas supply pre...

Страница 9: ...ombustion analysis are required for all installations above 4500 ft Refer to Gas Supply Pressure Measurement section for instruction on how to properly measure and adjust manifold outlet pressure The...

Страница 10: ...le electronic air cleaner terminals EAC are energized with 115 volts whenever the circulator blower is energized NOTE Wire routing must not to interfere with circulator blower operation filter removal...

Страница 11: ...90 seconds and display the proper fault code Induced draft blower is energized for 30 second prepurge Igniter warm up begins after 30 second prepurge expires Gas valves open at end of igniter warm up...

Страница 12: ...ntric Vent Kits DCVK Application The DCVK 20 and DCVK 30 kit is designed to allow the terminations of a direct vent furnace to be concentrically vented through a wall or roof This kit allows a single...

Страница 13: ...DRAFT AND CIRCULATION BLOWERS The bearings in the induced draft blower and circulator blower motors are permanently lubricated by the manufacturer No further lubrication is required Check motor windin...

Страница 14: ...2 164 327 655 1636 37 97 195 486 12 75 150 300 600 1500 38 23 47 95 189 474 13 69 138 277 555 1385 39 92 185 462 14 64 129 257 514 1286 40 22 45 90 180 450 15 60 120 240 480 1200 41 176 439 16 56 113...

Страница 15: ...t As the external static pressure goes up the temperature rise will also increase Consult the proper tables for tempera ture rise limitation BTU HR Calculation Example The unit being tested takes 40 s...

Страница 16: ...SERVICING 16 GAS VALVE BURNER ASSEMBLY PRESSURE TRANSDUCER INTEGRATED CONTROL BOARD CONTROL TRANSFORMER PRESSURE SWITCHES VENT PIPE CONNECTION COMBUSTION AIR CONNECTION DRAFT INDUCER Component I D...

Страница 17: ...any wires must be replaced replace with AWM 105 C 2 64 thick insulation of the same gauge or its equivalent THERMOSTAT AND WIRING DISCONNECT ALL POWER BEFORE SERVICING WARNING 1 Remove the blower comp...

Страница 18: ...m High Speed Red wire connected to RED on the control board High Speed Orange wire connected to FAN on the control board Medium Speed Black Low Speed and Brown Medium Low Speed wires connected to PARK...

Страница 19: ...determine the air temperature rise Allow adequate time for thermometer readings to stabilize 4 Adjust temperature rise by adjusting the circulator blower speed Increase blower speed to reduce temperat...

Страница 20: ...test for continuity between each of the motor leads 4 Touch one probe of the ohmmeter to the motor frame ground and the other probe in turn to each lead If the windings do not test continuous or a re...

Страница 21: ...rner compartment door to gain access to the gas valve 2 Connect a calibrated water manometer or appropriate gas pressure gauge at either the gas valve inlet pressure tap or the gas piping drip leg as...

Страница 22: ...est screw inlet outlet pressure boss out one turn counterclockwise not more than one turn b Attach a hose and manometer to the outlet pressure outlet pressure boss c Turn ON the gas supply d Turn on p...

Страница 23: ...ED is blinking in AMBER then release The control will execute the following functions 1 Blower Heat Speed 15 seconds 2 Blower Cool Speed 15 seconds 3 Blower Fan Speed 15 seconds 4 Hot Surface Igniter...

Страница 24: ...minal 3 Place the unit into a heating cycle LINE VOLTAGE NOW PRESENT WARNING 4 As soon as flame is established a micro amp reading should be evident once proof of flame micro amp reading is establishe...

Страница 25: ...TROUBLESHOOTING 25...

Страница 26: ...TROUBLESHOOTING 26...

Страница 27: ...lash the Fault Code History up to 5 fault codes from newest to oldest Fault Code Clear Function When the SW1 button is pressed and held for an extended period more than 5 seconds less than 10 seconds...

Страница 28: ...IED REPLACEMENT PARTS MUST BE USED WHEN SERVICING 1 SET HEAT ANTICIPATOR ON ROOM THERMOSTAT AT 0 7 AMPS NOTES HI VOLTAGE FIELD HI VOLTAGE 115V LOW VOLTAGE FIELD LOW VOLTAGE 24V COLOR CODES RD RED GY G...

Страница 29: ...ntact us Amana Brand Products http www amana hac com about us contact us You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page GOODMAN BRAN...

Отзывы: