D122.A
4 Manual
Page 18
SET
Choose the negative sign pressing the
up-
button.
SET
Touch the
right-
button to select the first figure.
Now hit the
up
-button two times ...
SET
... and the figure ‘2’ will be adjusted.
SET
Press the
right
-button to select the next figure.
SET
Hit the
up
-button until the figure ‘0’ appears.
SET
Confirm the lower scale point pressing the
enter-
button. Now
the...
... item appears.
Repeat the input procedure for the upper scale point like the
lower scale point. Enter [3000] for the upper scale point.
(Confirm by hitting
enter
-button)
Enter the upper scale point correct figured ‘as big as possible’
(the first figures should not be ‘0’)
In this case you get most precision of the indicator.
SET
Now scale the bargraph. Hit the e
nter-
button.
Enter [-0500] (-5°C) for the lower bargraph scale point.
Confirm by hitting the e
nter
-button
SET
Enter [2500] (25°C) for the upper bargraph scale point.
Hitting e
nter
-button accepts and quits the scale menu.
;
Limits, Hysteretic curve and time delay
Start limit menu by pressing the e
nter-
button
.
SET
Press the e
nter-
button for a second time and enter
[1000] (10°C)
for the
lower limit
using the arrow buttons.
Confirm by hitting the e
nter-
button.
(Remember, that the decimal point position is already set)