DOOR PANEL INSTALLATION

DOOR PANEL INSTALLATION

Jumper JP1 loads the installation with a communications
     resistor. For a proper system operation, activate this resistor
     only in the closest door panel to the backbone installation
     or in the general entrance door panel (if exists).
     Factory default: enabled.

Jumper JP2 selects the type of cable to be used for the video
     signal: coaxial cable (RG-59 or RG-11) or twisted pair.
     Twisted pair video transmission requires the use of an
     EL560 module plugged in the CN4 connector.
     Factory default: coaxial cable.

Jumper JP3 selects the volume of the door panel acknowledgement
     signals (call in progress, system busy and door opened).
     If after starting the system it's considered that the volume is too
     high, modify the jumper position.
     Factory default: maximum.

Jumper JP4 selects if the door panel has telecamera or not.
     In case of door panels without telecamera
     (EL540 sound module), change the jumper position.
     Factory default: with camera.

Enabled.

Disabled.

Coaxial.

Twisted pair.

Maximum.

Minimum.

With camera. Without camera.

inary coding of the configuration dip switch.

B

The switches set to OFF have null value. The values of the switches
     set to ON are shown in the enclosed chart.
     The building code will be calculated as the sum result of the
     switches values set to ON.

Example: 64+0+16+0+4+2+1=87

Switch number:
ON value:

4

64

5

32

6

16

7
8

8
4

9
2

10

1

ptional. EL560 module for video installations 

O

with twisted pair cable.

Plug the EL560 module in the CN4 connector.
     The CN4 connector is accessible by opening
     the terminal connector protection cover.
NOTE: on this type of installations the EL562 module
     must be plugged in all the monitors and JP2
     jumper of the EL500 circuit must be placed
     on the position specified on page 83.
     Refer to the specific installation diagram.

escription of the configuration dip switch.

D

Set to ON the switch number 2 for monitor or telephones
     programming. Once the programming progress is finished
     return the switch to OFF position. The programming process
     is described on pages 92 (monitors) and 95 (telephones).

Set to OFF the switch number 3 in case of a master door panel.
     Each system must have only one master door panel; the rest
     must be slaves (ON). In systems with general entrance panel
     set as master one door panel of each internal building.

Switches number 4 to 10 set the building code. In systems with several
     door panels, set the same code in all the panels; in systems with
     general entrance panel, set different codes for each internal building.
     Valid codes are from 0 (factory default) to 99. To set the code use
     binary coding as shown on the next paragraph.

Coming from previous page

escription of the configuration dip switch.

D

The SW1 configuration dip switch is accessible by opening
     the terminal connector protection cover.

Switch number 1 allows to activate the autoswitch-on function
     (audio and video communication without previous call)
     at the door panel that has this switch to ON position.
     In systems with several door panels activate this function
     only in one of them; in systems with general entrance panel
     this function can be activated in one door panel of each
     internal building.

Continue

escription of the configuration jumpers.

D

The JP1, JP2, JP3 and JP4 configuration jumpers
     (from left to right respectively) are placed on the
     left side of the EL500 circuit, and are accessible
     by opening the terminal connector protection cover.

Содержание Stadio Plus T500ML

Страница 1: ...71 Stadio Plus Instructions manual Audio and Video door entry system digital installation T500ML rev 0205 ...

Страница 2: ...half minutes or until the handset is replaced Once the communication has finished the system will be freed O To open the door press the door release push button during call or communication progresses with one press the door release operates during 3 seconds During the lock release activation an acoustic tone will be heard on the door panel confirming the lock release is activated O The monitor an...

Страница 3: ...f the door panel should be placed at 1 65m height roughly The hole dimensions will depend on the number of door panel modules The door panel has been designed to be placed under most of the environmental conditions However it s recommended to take additional cautions like rainproof covers To obtain a good quality picture on video door entry systems avoid direct incidence from light sources reparin...

Страница 4: ...N marked in the lower module and fix it by screwing the module shafts Place the module spacer between lower and next modules assuring that the spacer adjustment notches are inside the panel Fix the module by screwing the shafts Repeat this procedure in case of door panels with one more module the maximum number of modules placed vertically is three Insert the header UP marked in the last module an...

Страница 5: ...el on the embedding box insert the hinges in the embedding box lockers as shown old the door panel on the embedding box H For a quality finish pass the push buttons wires through the spacer hole of the closest module 2 It s recommended to use wires of less than 0 25mm section IMPORTANT link the push buttons common terminal of the several push buttons modules The common terminal of the push buttons...

Страница 6: ...6 circuits With 5 EL516 circuits With 6 EL516 circuits With 7 EL516 circuits With 8 EL516 circuits 8 7 15 22 6 15 15 36 5 15 15 15 50 4 15 15 15 15 64 3 15 15 15 15 15 78 2 15 15 15 15 15 15 92 1 15 15 15 15 15 15 15 106 0 15 15 15 15 15 15 15 15 120 To other encoders or push buttons 1 P2 1 P1 31 P4 61 P6 91 P8 16 P3 46 P5 76 P7 106 2 2 32 62 92 17 47 77 107 3 3 33 63 93 18 48 78 108 4 4 34 64 94 ...

Страница 7: ... installations the EL562 module must be plugged in all the monitors and JP2 jumper of the EL500 circuit must be placed on the position specified on page 83 Refer to the specific installation diagram escription of the configuration dip switch D Set to ON the switch number 2 for monitor or telephones programming Once the programming progress is finished return the switch to OFF position The programm...

Страница 8: ...case of a FA Plus model IMPORTANT Link power supplies to connect more units than the specified as it s shown IMPORTANT on page 96 IMPORTANT The power supply must be installed in a dry and protected place It s recommended to protect the power supply by using a thermo magnetic circuit breaker and to use a ground connection ock release installation L inal adjustments F lose the door panel C Fix the d...

Страница 9: ... Floor Door Stair PLATEA Plus 0000000000 Nº serie a f g b e j l k m d i c h a b c d e f g h i j k l m Handset B W or color screen depending on the model Front film Function push buttons Cord Attachment holes Identification label Connecting points CN4 connector Three positions call reception volume control Cable slot Contrast control color control in case of color screen Brightness control Monitor ...

Страница 10: ...onal device activation output twisted pair video signal Vin Malla Vout A D HZ INT SA CTO 2C A1 Vp Mp L562 module for video installations E with twisted pair cable andling the end of line jumper H hanging the front film C The end of line jumper is placed on the CN4 connector that can be located on the monitor base In case of twisted pair cable installations the end of line jumper is placed in the E...

Страница 11: ...de In systems with more than one door panel the programming process shall be done on the master door panel only Switch off the monitor to be programmed Once the monitor is off press the door release push button With the door release push button pressed switch on the monitor To show that the system is ready for programming the door panel will reproduce a sound and the picture will appears on the mo...

Страница 12: ...allows to call to the master porter s exchange During call reception and communication progresses allows the lock release activation a b c a b c erminal connector description T positive ground audio digital communication intercom auxiliary calling device output door bell push button input A D INT SA HZ A D _ SA INT HZ TELEPHONE INSTALLATION ix the telephone F It will be necessary to open the telep...

Страница 13: ...slaves both monitors or telephones Make a call to check that the telephone has been succesfully programmed Repeat these steps to program the rest of telephones Once the programming has been finished set to OFF the programming switch If you don t the door panel will reproduce a sound to advise that the system is still into programming mode M R B O T R 3 TF 104 SEC CV CV D Malla Vin Ain Aout Vin Vou...

Страница 14: ...istributor INSTALLATION DIAGRAMS ideo installation with coaxial cable v The installation diagram shows the connection of a video system with one or several door panels for the same building If the system has one door panel only override the wiring to the second door panel If the system has more than one door panel wire the second panel as shown on the diagram In case of more than two door panels w...

Страница 15: ... Terminal SECTIONS CHART 50m Distance 150m A A A D in out V V V M in out p d p d CV CV INSTALLATION DIAGRAMS ideo installation without coaxial cable v The installation diagram shows the connection of a video system with one or several door panels for the same building If the system has one door panel only override the wiring to the second door panel If the system has more than one door panel wire ...

Страница 16: ... A 1 00mm 2 50mm 0 25mm 0 25mm Terminal SECTIONS CHART 50m Distance 150m A A A D in out CV CV Place this power supply as closest as possible to the first telephone The installation diagram shows the connection of an audio system with one or several door panels for the same building If the system has one door panel only override the wiring to the second door panel If the system has more than one do...

Страница 17: ...ART connector it will be possible to view the picture from the door panel on the TV screen Remove the end of line jumper that s placed on the CN4 connector Connect the coaxial cable between terminals 17 shield and 20 hot of the SCART connector ntercom function I Platea Plus monitor and T 940 Plus telephone have intercom facility between two units of the same apartment To enable this function check...

Страница 18: ...nits with the exception of a shortcircuit between CTO and monitor or distributor terminals O Nothing operates w Check the output power supply voltage between and terminals it should have 17 5 to 18 5Vd c If not disconnect the power supply from the installation and measure again If it s correct now it means there is a short circuit in the installation disconnect the power supply from mains and chec...

Отзывы: