REPLACEMENT
The Golmar
V2PLUS
video door entry system is a digital system with simplified installation (2 wire bus
without polarity), designed to new installations and to replace existing audio door entry systems in both
apartment blocks and villas.
In installation for replacement it is necessary a detailed study of the existing installation before installing
the system. To check that your installation complies with the system's minimum recommended
requirements, please read carefully the following chapters, which provide details of the checks to be done.
Before installing this system, we must ensure that the existing installation complies with the following
requirements:
-The installation must be realized by multipaired cable, (not to use single-wire cables).
-The wires must not be spliced, frayed, nor touch metal parts, and must not vary in cross
section throughout the entire installation.
-The entire installation must be at least 40cm away from any other installation otherwise there
is a risk that the audio and video signal be exposed to interference, or that the system
does not work correctly.
-All branch connections must be made using D4L-V2PLUS or D1L-V2PLUS distributors.
-Each floor must have physical space to situate the distributor/s, in case they are necessary.
-Each apartment must have sufficient space to install the video system monitor.
-Maximum installation distance it will depend on the section and the installed cable (see page 40 & 41).
-Installations with independent more common wires,
only use the common wires
(separate and do not
connect the independent ones).
-1 access door panel, (up to 3 access door panel with
MC-V2PLUS
multiplexer).
-Up to 32 (monitors, telephones or call repeaters) and apartments without using converters or multiplexers.
-Up to 16 (monitors, telephones or call repeaters) and apartments in daisy chain installations without
distributor, per installation without using converters or multiplexers.
-Up to 3 elements (monitors, telephones or call repeaters S-45) per apartment.
-Installations with more than 32 elements or 1 riser (it needs the use of the multiplexer
MC-V2PLUS
).
-Installations with general door panels (it needs the use of the
CD-V2PLUS/TP
converters).
-Before connecting the system s power supply, we must ensure that there are
NO old parallel units,
relays or call repeaters in the apartments.
If so, we must disconnect them or replace them with
units that are compatible with the new system, otherwise the installation could be seriously
damaged or burnt.
If any of the first three requirements are not met, it will be necessary to replace the installation riser.
If the branch connections to the apartments are in good condition, their replacement will not be necessary.
If replacing the installation riser, use the Golmar cable
RAP-2150
and the next sections:
Do not use different types of cable in the same installation (contact with our technical support
department).
'
RAP-2150
Terminal
SECTIONS CHART
150m.
Door panel
-Monitor
P.S.- Door panel
+, -
BUS, D
50m.
Door panel - CV
50m.
1,5mm²
CV1,CV2
0,5mm²
(d.c lock release)
CV1,CV2, ~, ~
1mm²
(a.c lock release)
1mm²
*
One access and one riser
MINIMUM REQUIREMENTS
Continue
39
*
*
( )
1