![Gold Line DSP2B Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/gold-line/dsp2b/dsp2b_user-manual_2239266010.webp)
10
3. Click YES to allow computer to begin setup.
4. After the opening screen appears click on the USB DRIVER icon.
5. Follow the prompts on the screen for the install shield wizard. The computer will
automatically choose the correct driver required for the operating system.
6. After the USB DRIVERS are installed click on the INSTALL SOFTWARE icon.
7. Follow the prompts on the screen to install the software.
8. After the software is installed click on the EXIT icon and remove the disk.
DIRECTIONS FOR CONNECTING THE DSP2B/BP TO THE COMPUTER
1. Connect the serial cable to the USB serial cable adapter and lightly screw together finger
tight.
2. Attach male end of the serial cable to the serial port on top of the DSP2B/BP.
3. Attach the USB end of the adapter to the USB port on the computer. (preferably not
through a USB hub.)
4. Connect the Gold Line MK8A microphone to the top of the analyzer.
5. Turn on the DSP2B/BP by the switch on the bottom right side of the analyzer.
6. Open the CVOW PLATINUM software on your computer.
7. If your screen is flashing click on the FILE button on the top of your computer screen.
Scroll down and click on SELECT COM PORT.
8. Click on correct COM PORT and then click on HIDE.
9. The computer screen will stop flashing and display the ambient sound dBa level at the
bottom center of the screen along with the Octave band frequency data.
MAKING INTELLIGIBILITY MEASUREMENTS WITH
OPTCVOW PLATINUM ON COMPUTER
INTELLIGIBILITY TESTING FOR
VOICE EVACUATION SYSTEMS
REQUIRED EQUIPMENT:
TALKBOX (requires 110vac or 8 AA Alkaline or Ni cad/NiMH batteries)
DSP2B/BP (requires 110vac or 8 AA Alkaline or Ni cad/NiMH batteries)
STI-PA CD test tones (included with DSP2B/BP & DSP30B/BP)
Computer with OPTCVOW PLATINUM installed
In some situations, hearing protection might be warranted.
See NFPA 72 for other possible requirements where the system being tested is an
Emergency Communications System (ECS).
INSTRUCTIONS TO MEASURE INTELLIGIBILITY (OPT STIcis):
USING TALKBOX AND PUSH TO TALK FEATURE,
WITHOUT ADD NOISE FEATURE
USING COMPUTER
1. Connect the DSP2B/BP to the computer and open the WINCVO PROGRAM.
2. Insert PA system microphone into Talkbox holder facing the speaker
3. Position the Talkbox loudspeaker at the normal mouth to microphone distance.