SmartBox
®
4 / SmartBox
®
4
PRO
20 / 32
part no. 28 400 57 c
Menu
Setting
Description
22.Test
current
Test function for the current mA value of the
probe
:
ADC = 28A0 = 04.00 mA
If
level probe
is not submerged, the value should
be close to 4 mA. Tolerance range is 3.7 ... 4.3 mA.
For larger deviations, see menu item 9.
23.Test
relay
SmartBox 4
Furthermore, devices connected on the relay contact will also be switched
on and/or off!
•
Connected devices can be damaged (dry running).
•
Operating media may leak.
Disconnect the devices connected before
test relay
.
Only reconnect the devices again after
test relay.
Relay 1 ON/OFF
Test function for the switch function of relay
24.Reset
ESC
Exit this function without executing it.
Restart
Initialisation. The device software restarts and
keeps all device settings.
Factory
settings
Complete reset of all parameters to the original
delivery status.
26.Exit
[Enter] back to display mode.
SmartBox
®
4:
Activation of other indicators (and assignation of the respective tank numbers)
Numbering the tanks:
The contents indicator SmartBox 4 always has tank number 1.
If other content indicators SmartBox
®
1, 2 or 3 (indicator) are to be connected “SERIAL
LINK INPUT“ (terminals 3 + 4), they must be assigned defined tank numbers. The tank
numbers are simply assigned in the sequence in which the indicators log on for the first
time.
•
First, activate indicator 2 for tank number 2 (switch on mains voltage), then for indicator 3,
and so on.
Example: Activate tank 2
•
After connection the indicator of tank 2 as described under Electrical Installation –
Connecting the Interface to SmartBox
®
1, SmartBox
®
2 or SmartBox
®
3, switch on the
indicator
of the tank in question (switch on the mains voltage).
In the display of SmartBox
®
4, the following will be indicated alternatingly: “Tank1:” - “xx.xxxL“
– “Tank2:“ – “yy.yyyL“ (depending on the selection / adjustment in the menu 14.Show tanks).
Then, follow the same steps for the other indicators.
You have now completed the on-site installation.
The order of the displayed tanks can be changed subsequently under menu step
16.Sort. Tanks
SmartBox
®
4
to be changed.